Heating

Enable setpoint limitation

This defines whether setpoint limitation of the room temperatures is
basically be disabled or enabled. Only when setpoint limitation is
enabled does the central apartment unit respond to the setpoint limi-
tation signals received over the wire-bound bus.
Main menu > Heating > Apartment > Settings > Setpoint limitation:
Factory setting
Your setting

Limitation setpoint

This defines the maximum permissible room temperature setpoint
(0..35 °C) during the period of time a setpoint limitation is transmitted
over the wire-bound bus.
Main menu > Heating > Apartment > Settings > Limitation setpoint:
Factory setting
Your setting

Pump overrun time

The overrun time for the apartment pump and the DHW pump can be
set (0..30 min).
Main menu > Heating > Apartment > Settings > Pump overrun:
Factory setting
Your setting

Valve override

Valve override enables all valves of the apartment to be jointly driven
to the required valve position (0..100 %, e.g. for hydraulic balancing).
Main menu > Heating > Apartment > Settings > Valve override:
Guide value
Your setting
Valve override must be manually switched off again.
Otherwise, room temperature control stays deactivated. During
the period of time valve override is active, status message
"Valve override active" is displayed.
Siemens
Building Technologies
Enabled
Disabled
Enabled
25 °C
6 min
--- (off)
Synco 900
Function settings
65/88
CE1C2707en
05.07.2007