Calendar Zone (Holidays And Special Days); Dhw Zone - Siemens Synco 900 Mounting And Commissioning

Hide thumbs Also See for Synco 900:
Table of Contents

Advertisement

Calendar zone (holidays and special days)

When using calendar zone setting "Autonomous", the device does not
receive or send calendar dates. If several devices in the system are
to use a common calendar, holiday / special day operation must be
set to "Master" on every such device, and to "Slave" on the other
devices.
Main menu > Commissioning > Bus communication >
Holidays/special days > Hol/spec day op:
Factory setting
Your setting
In addition, with master / slave operation, set the required holiday /
special day zone (1..31).
Main menu > Commissioning > Bus communication >
Holidays/special days > Hol/spec day zone:
Factory setting
Your setting
Ensure that only one device per holiday / special day zone is
defined as the holiday / special day master.

DHW zone

Use the following operating line to set the DHW zone for DHW
heating (1..31):
Main menu > Commissioning > Bus communication > DHW >
DHW zone:
The DHW zone setting must be unambiguous. For example,
only one DHW heating system may have DHW zone 1.
DHW zone
When operating external DHW heating, set the DHW zone of the
central apartment unit to the same value as with external DHW
heating.
Main menu > Commissioning > Bus communication > DHW >
Time switch op:
Factory setting
Your setting
When using setting "Autonomous", the central apartment unit does
not receive or send any time switch data. When using setting
"Master", the time switch data is distributed in the DHW zone for
62/88
Siemens
Building Technologies
Autonomous
Autonomous
Slave
Master
1
Factory setting
1
Autonomous
Autonomous
Slave
Master
Synco 900
Commissioning the system
Your setting
CE1C2707en
05.07.2007

Advertisement

Table of Contents
loading

Table of Contents