Operation Conditions - Bosch Uni Condens 8000 F Installation And Maintenance Instructions Manual

Floor standing condensing boiler
Hide thumbs Also See for Uni Condens 8000 F:
Table of Contents

Advertisement

2)
Boiler return (RK1)
2)
Boiler return (RK2)
Pressure relief valve/flow safety pipe
Boiler safety assembly connection
Condensate discharge
Drain
Fitting clearance (width)
1)
Fitting clearance height
4)
Delivery length
1) The transport height can be reduced by removing the base frame rails.
2) Acc. to EN 1092-1 PN 6.
3) Acc. to EN 1092-1 PN 16.
4) Following disassembly of burner door
Table 5 Boiler dimensions
2.9

Operation conditions

Observe the maximum rated heat input Qn (Hi) specified on the data
plate when setting the burner output.
Operation conditions
Maximal permissible temperature of
high limit safety cut-out /(STB)
Maximum operating pressure
Maximum number of burner starts
Table 6 Operation conditions
Uni Condens 8000 F – 6720867056 (2016/10)
Abbreviation
Unit
Ø RK1
DN
H
mm
RK1
A
mm
5
Ø RK2
DN
H
mm
RK2
A
mm
6
3)
Ø VSLP
DN
A
mm
3
Ø AAB
inch
A
mm
1
Ø AKO
DN
H
mm
AKO
A
mm
7
Ø EL
inch
H
mm
EL
B
mm
H
mm
EB
mm
Unit
Value
°C
110
bar
Dependent on boiler
size
per
15 000
annum
Boiler type
800
100
1007
320
80
300
320
65
400
G1
1200
40
180
71
R1
161
960
1874
2405
Operation conditions Uni Condens 8000 F
800...1200 with
modulating
operation
Volumetric flow rate
None –
In conjunction with a
Min. boiler water
CFB/CC control unit
temperature
for modulating
Operating Interruption
operation (CFB 840;
(complete boiler shut-
CFB 810; CFB 830 or
down)
CC 8311; CC 8312).
Heating circuit control
unit with heating mixer
Minimum return
temperature
1)2)
Miscellaneous
1) Maximum 15,000 burner starts per year. In order not to exceed the number of
burner starts, observe the information on setting the control unit and burner in
the technical guide or installation instructions. If this value is still however
exceeded, please contact the customer service of the manufacturer.
2) The number of burner starts per year is influenced by the boiler system's
operating settings (control parameters in the boiler control and the combustion
setting) and by the design of the boiler system with regard to the consumer's
heat requirement. To avoid exceeding the number of burner starts per year as a
result of operating settings that have not been optimised, the manufacturer
offers complete commissioning and regular system inspections for boilers,
burners and boiler controls (CFB/CC controllers with function modules).
Table 7 Operation conditions
It must be possible to check the number of burner starts, e.g. at the user
interface, third-party control unit, building control system or burner
control unit.
Product Information
1000
1200
125
125
1148
1148
380
380
100
100
263
263
390
390
65
65
400
400
G1
G1
1245
1245
40
40
180
180
70
70
R1
R1
164
164
1040
1040
2052
2052
2455
2455
Uni Condens 8000 F
800...1200 with
constant boiler
temperature
None
In conjunction with a
CFB/CC control unit
for constant boiler
temperature CFB 810
or CC 8312, or when
supplemented by a
third party control
unit.
1)
9

Hide quick links: