Viessmann Vitodens 200 Technical Manual page 86

4.2 kw to 66.0 kw
Hide thumbs Also See for Vitodens 200:
Table of Contents

Advertisement

3.1 Water interconnections
300
Vitodens 300 from 49 kW
Circulation pump VIRS 7 BUS
variable speed, fully wired, for installation
into the boiler or as an external pump for
pipe installation.
Rated voltage
V ~
Rated current
A max.
A
min.
Condenser
mF
Power
W max.
consumption
W
min.
W
in delivered condition
Residual head of the circulation pump
700
70
60
600
3
500
50
40
400
30
300
20
200
10
100
0
0
0
200
Flow rate in l/h
O Operating range
Curve
Capacity
Circulation
pump
A
30 %
B
40 %
C
50 %
D
60 %
E
65 %
F
70 %
G
80 %
H
90 %
K
100 %
86
230
0.55
0.37
3.5
126
42
93
400
600
800
1000
Example
Setting
H Vitodens 300, 12.2 kW to 49 kW
Coding
H Design temperatures 75 ºC/55 ºC
address "E 6"
H Radiator heating system, heating
E 6:030
demand 40 kW
E 6:040
¢ Volume flow 1 720 l/h L
E 6:050
H Pressure drop 15 kPa (¢ 1.5 mWS) M
E 6:060
H Design point N
E 6:065
E 6:070
E 6:080
Optimum pump curve acc. to diagram:
E 6:090
F = Coding address "E 6:070".
E 6:100
1200
1400
1600
1800
2000
2200
2400
2600