System design 11
Vitodens 300 (from 49 kW) with/without DHW heating with three or more heating circuits with mixer and low loss header
A
2/K
R
P
O
N
Required equipment
Item
Description
A
Vitodens 300 (from 49 kW) with control unit for weather-compensated mode
and LON communication module
and LON cable
and LON terminator (2 pieces)
C
Vitotronic 050 (type HK3W)
with LON communication module
D
Temperature limiter for limiting the max. temperature of underfloor heating systems
Immersion thermostat
or
Contact thermostat
E
Flow temperature sensor
F
Heating circuit pump (e.g. in Modular Divicon)
G
Extension kit for one heating circuit with mixer plus flow temperature sensor
K
Flow temperature sensor for low loss header
L
Low loss header in conjunction with Modular Divicon
M
Primary pump (boiler circuit), variable speed
N
Cylinder primary pump
O
Cylinder temperature sensor
P
DHW cylinder
R
Internal extension H 1 (system without DHW circulation; optional connection of an external
safety valve for LPG)
or
internal extension H 2 (system without DHW circulation; optional connection of an interlock
for extraction equipment)
or
external extension H 1 (system with DHW circulation)
VITODENS
B
2/K
C
LON
3/230V
3/230V
D
E
E
B
F
H
G
G
2/K
2/K
2/K
3/230V
M
K
L
3.2 Installation examples
A Vitodens 300 (from 49 kW) with
weather-compensated control unit
and LON communication
B Outside temperature sensor
C Vitotronic 050 (type HK3W)
D Maximum temperature limiter
E Flow temperature sensor
2/K
F Heating circuit pump
G Extension kit for one heating circuit
with mixer
H Regulating valve
E
K Flow temperature sensor for low loss
header
L Low loss header
F
F
M Primary pump (boiler circuit)
N Cylinder primary pump
G
O Cylinder temperature sensor
P DHW cylinder
R Internal extension H 1 or H 2
or
external extension H 1
Required electrical connecting cables
2/K
3/230 V Number of cores/230 V~
System design 11
Number of cores/low voltage
Quantity Part no.
1
as per pricelist
1
7179 113
1
7143 495
1
7143 497
1
Z001 844
1
7172 173
1
7151 728
1
7151 729
1 per
Standard delivery of
heating
the extension kit
circuit
1 per
as per pricelist
heating
circuit
1 per
7450 650
heating
circuit
1
7179 488
1
as per pricelist
1
7178 820
1
7339 468
1
7179 114
1
as per pricelist
1
7179 057
1
7179 144
1
7179 058
300
3
101