Viessmann Vitodens 200 Technical Manual page 85

4.2 kw to 66.0 kw
Hide thumbs Also See for Vitodens 200:
Table of Contents

Advertisement

Vitodens 300, 6.6 kW to 35.0 kW
Vitodens 333
Circulation pump VICUPE 60 BUS
Rated voltage
V ~
Rated current
A max.
A
min.
Power
W max.
consumption
W
min.
W
in the delivered condition
W
26
W
35
Residual head of the integral circulation pump
450
40
400
350
30
300
N
250
20
200
L
150
10
100
50
0
0
0
100
200
Flow rate in l/h
N Operating range
Curve
Capacity
Setting
Circulation
Coding
pump
address "E 6"
A
30 %
B
40 %
C
50 %
D
60 %
E
70 %
F
80 %
G
90 %
H
100 %
VITODENS
230
0.45
0.21
100
50
65
80
300
400
500
600
Example
H Vitodens 300, 6.6 kW to 26.0 kW
H Design temperatures 75 ºC/55 ºC
H Radiator heating system, heating
E 6:030
demand 20 kW
E 6:040
¢ Volume flow 860 litres/h K
E 6:050
H Pressure drop 15 kPa (¢ 1.5 mWS) L
E 6:060
H Design point M
E 6:070
E 6:080
Optimum pump curve acc. to diagram:
E 6:090
C = coding address "E 6:050".
E 6:100
3.1 Water interconnections
M
B
A
700
800
900
1000
K
H
G
E
F
D
C
1100
1200
1300
1400
300
333
3
85