Testing the integral expansion vessel or the expansion vessel fitted to the mounting frame
Integral expansion vessel in the
Vitodens 200
Inlet pressure
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Blow-off pressure
. . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Capacity
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Integral expansion vessel in the
Vitodens 300, 13 kW
Inlet pressure
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Blow-off pressure
. . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Capacity
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Mounting frame with expansion vessel
(accessory for Vitodens 300, 26 kW 35 kW)
Inlet pressure
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Blow-off pressure
. . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Capacity
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
V
= f ((V
+ V
) A
+ 2.4)
DEV
A
K
f
V
= Expansion vessel volume
DEV
f
= Expansion factor (= 2 for
expansion vessel)
V
= System volume
A
V
= Boiler water volume
K
Af
= Heating water expansion factor
Calculating the heating system volume (approx. values)
1000
800
600
400
200
130
0
5
10
20
Output in kW
A Convectors
B Plate-type radiators
C Radiators
D Underfloor heating
VITODENS
Integral expansion vessel in the
Vitodens 333
0.75 bar
Inlet pressure
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
2.5 bar
Blow-off pressure
. . . . . . . . . . . . . . . . . . . . . . . . . . . . .
10 litres
Capacity
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Integral expansion vessel in the
Vitodens 343
0.75 bar
Inlet pressure
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
2.5 bar
Blow-off pressure
. . . . . . . . . . . . . . . . . . . . . . . . . . . . .
8 litres
Capacity
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
0.75 bar
2.5 bar
11 litres
Example:
System: Vitodens 200
Boiler water volume 5 litres
Output 20 kW
Plate radiator
System volume approx. 130 litres
Heating system 70 ºC/65 ºC
Calculation:
Heating system 70 ºC/65 ºC: average water
temperature approx. 60 ºC
A
= 0.0171
f
V
= 2 · ((130 + 5)· 0.0171 + 2.4)
DEV
V
= 9.42 litres
DEV
Result:
The integral expansion vessel
(10 litres capacity) is sufficiently large
for this system.
D
C
B
A
30
40
3.3 Expansion vessels
When making the water interconnections,
check that the size of the expansion
0.75 bar
vessel matches the system conditions.
2.5 bar
12 litres
The following steps will enable you to
make a rough check.
0.75 bar
2.5 bar
8 litres
Note
If the integral expansion vessel or the
expansion vessel in the mounting frame
is insufficient, connect an adequately
sized expansion vessel to the expansion
vessel connector on the Vitodens.
Calculating the expansion factor A
Average water temp.
[ºC]
50
60
70
50
3
f
Expansion factor
A
f
0.0121
0.0171
0.0228
117