3.5.10

Group 3.8: Limit supervisions

Choose here:
1. One or two (P3.8.1/P3.8.5) signal values for supervision.
2. Whether the low or high limits are supervised (P3.8.2/P3.8.6)
3. The actual limit values (P3.8.3/P3.8.7).
4. The hysteresis for the set limit values (P3.8.4/P3.8.8).
Code
Parameter
Supervision #1 item
P3.8.1
selection
P3.8.2
Supervision #1 mode
P3.8.3
Supervision #1 limit
Supervision #1 limit
P3.8.4
hysteresis
Supervision #2 item
P3.8.5
selection
P3.8.6
Supervision #2 mode
P3.8.7
Supervision #2 limit
Supervision #2 limit
P3.8.8
hysteresis
Table 38: Limits supervision settings.
Min
Max
Unit
0
7
0
2
-200.000 200.000
Varies
-200.000 200.000
Varies
0
7
0
2
-200.000 200.000
Varies
-200 000 200.000
Varies
Siemens Application
Default
ID
0 = Output frequency
1 = Frequency reference
2 = Motor current
3 = Motor torque
0
1431
4 = Motor power
5 = DC-link voltage
6 = Analog input 1
7 = Analog input 2
0 = Not used
1 = Low limit supervision
0
1432
(output active over limit)
2 = High limit supervision
(output active under limit)
Supervision limit for selected
25.00
1433
item. Unit appears automati-
cally.
Supervision limit hysteresis
5.00
1434
for selected item. Unit is set
automatically.
1
1435 See P3.8.1
0
1436 See P3.8.2
40.00
1437 See P3.8.3
5.00
1438 See P3.8.4