Specifications
Concealed Floor Standing Type
Model
1 Cooling Capacity (19.5°CWB)
2 Cooling Capacity (19.0°CWB)
3 Heating Capacity
Casing Color
Dimensions: (H×W×D)
Rows×Stages×Fin
Coil (Cross Fin
Pitch
Coil)
Face Area
Model
Type
Motor Output ×
Number of Units
Fan
Air Flow Rate (H/L)
Drive
Temperature Control
Sound Absorbing Thermal Insulation Material
Air Filter
Liquid Pipes
Piping
Gas Pipes
Connections
Drain Pipe
Machine Weight (Mass)
50/60Hz
220V
5 Sound Level (H/L)
50Hz
240V
Safety Devices
Refrigerant Control
Connectable Outdoor Unit
Standard Accessories
Drawing No.
Notes:
1 Indoor temp. : 27°CDB, 19.5°CWB / outdoor temp.: 35°CDB / Equivalent piping length: 7.5m, level
2 Indoor temp. : 27°CDB, 19.0°CWB / outdoor temp.: 35°CDB / Equivalent piping length: 7.5m, level
3 Indoor temp. : 20°CDB / outdoor temp.: 7°CDB, 6°CWB / Equivalent piping length: 7.5m, level difference:
4 Capacities are net, including a deduction for cooling (an addition for heating) for indoor fan motor heat.
5 Anechoic chamber conversion value, measured at a point 1.5 m in front of the unit at a height of 1.5 m.
36
FXNQ40MVE
RT
1.3
kcal/h
4,000
Btu/h
16,000
kW
4.7
kW
4.5
RT
1.4
kcal/h
4,300
Btu/h
17,100
kW
5.0
Galvanized Steel Plate
mm
610×1,070×220
mm
3×14×1.5
0.200
2D14B13
Sirocco Fan
W
25×1
m³/min
11/8.5
cfm
388/300
Direct Drive
Microprocessor Thermostat for
Cooling and Heating
Glass Fiber / Urethane Foam
Resin Net (with Mold Resistant)
φ6.4 (Flare Connection)
mm
φ12.7 (Flare Connection)
mm
φ21 O.D (Vinyl Chloride)
mm
kg
23
38/33
dBA
40/35
Fuse,
Thermal Protector for Fan Motor
Electronic Expansion Valve
R-410A M(A) Series
Operation Manual, Installation
Manual, Insulation for Fitting, Drain
Hose, Clamps, Screws, Washers,
Level Adjustment Screw.
difference: 0m.
difference: 0m.
0m. (Heat pump only)
During actual operation, these values are normally somewhat higher as a result of ambient conditions.
FXNQ50MVE
1.6
5,000
19,800
5.8
5.6
1.8
5,400
21,500
6.3
Galvanized Steel Plate
610×1,350×220
3×14×1.5
0.282
2D14B20
Sirocco Fan
35×1
14/11
494/388
Direct Drive
Microprocessor Thermostat for
Cooling and Heating
Glass Fiber / Urethane Foam
Resin Net (with Mold Resistant)
φ6.4 (Flare Connection)
φ12.7 (Flare Connection)
φ21 O.D (Vinyl Chloride)
27
39/34
41/36
Fuse,
Thermal Protector for Fan Motor
Electronic Expansion Valve
R-410A M(A) Series
Operation Manual, Installation
Manual, Insulation for Fitting, Drain
Hose, Clamps, Screws, Washers,
Level Adjustment Screw.
C: 3D038817
Si39-502A
FXNQ63MVE
2.1
6,300
24,900
7.3
7.1
2.3
6,900
27,300
8.0
Galvanized Steel Plate
610×1,350×220
3×14×1.5
0.282
2D14B20
Sirocco Fan
35×1
16/12
565/424
Direct Drive
Microprocessor Thermostat for
Cooling and Heating
Glass Fiber / Urethane Foam
Resin Net (with Mold Resistant)
φ9.5 (Flare Connection)
φ15.9 (Flare Connection)
φ21 O.D (Vinyl Chloride)
27
40/35
42/37
Fuse,
Thermal Protector for Fan Motor
Electronic Expansion Valve
R-410A M(A) Series
Operation Manual, Installation
Manual, Insulation for Fitting, Drain
Hose, Clamps, Screws, Washers,
Level Adjustment Screw.
Conversion Formulae
kcal/h=kW×860
Btu/h=kW×3412
RT=kW×0.284
cfm=m³/min×35.3