Daikin VRV II RXYQ8MY1K Service Manual page 124

R-410a heat pump 50/60hz for high outdoor temperature use
Table of Contents

Advertisement

Si39-502A
Test Operation
No.
Setting item
Emergency
operation
(Setting for the
master unit
38
operation
prohibition in multi-
outdoor-unit
system)
Emergency
operation
(Setting for the
slave unit 1
39
operation
prohibition in multi-
outdoor-unit
system)
Emergency
operation
(Setting for the
slave unit 2
40
operation
prohibition in multi-
outdoor-unit
system)
Emergency
operation
42
(prohibition of INV
compressor
operation)
Description
Used to temporarily prohibit the applicable outdoor unit
from operating should there be any faulty part in multi-
outdoor-unit system. Since the comfortable environment
is extremely impaired, prompt replacement of the part is
required.
If the INV compressor has a failure, used to run the
system only with STD compressor(s). This is a temporary
running of the system until the compressor is replaced,
thus making comfort extremely worse. Therefore, it is
recommended to replace the compressor soonest
possible.
Field Setting
113

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents