Daikin VRV II RXYQ8MY1K Service Manual page 25

R-410a heat pump 50/60hz for high outdoor temperature use
Table of Contents

Advertisement

Specifications
Model Name (Combination Unit)
Model Name (Independent Unit)
1 / 2 Cooling Capacity
3 / 4 Cooling Capacity
5 Heating Capacity
Casing Color
Dimensions: (H×W×D)
Heat Exchanger
Type
Piston Displacement
Number of Revolutions
Comp.
Motor Output×Number
of Units
Starting Method
Type
Motor Output
Fan
Air Flow Rate
Drive
Liquid Pipe
Connecting
Pipes
Gas Pipe
Product Mass (Machine Weight)
6 Sound Level
Safety Devices
Defrost Method
Capacity Control
Refrigerant Name
Refrigerant
Charge
Control
Refrigerator Oil
Standard Accessories
Drawing No.
Notes:
1 Indoor temp. : 27°CDB, 19.5°CWB / outdoor temp. : 35°CDB.
2 Indoor temp. : 27°CDB, 19.5°CWB / outdoor temp. : 46°CDB.
3 Indoor temp. : 27°CDB, 19.0°CWB / outdoor temp. : 35°CDB.
4 Indoor temp. : 27°CDB, 19.0°CWB / outdoor temp. : 46°CDB.
5 Indoor temp. : 20°CDB / outdoor temp. : 7°CDB, 6°CWB.
6 Sound level : Anechoic chamber conversion value, measured at a point 1 m in front of the unit at a height
7 The units with anti-corrosion treatment will be available as standard. Please specify the suffix "E" as
14
RXYQ24MYLK(E)
RXYQ8MYLK(E)+RXYQ8MYLK(E)+RXYQ8MYLK(E)
RT
Btu / h
236,000 / 233,000
kcal / h
59,600 / 58,800
kW
RT
Btu / h
229,000 / 229,000
kcal / h
57,800 / 57,800
kW
RT
Btu / h
kcal / h
kW
Without (E): Ivory White (5Y7.5 / 1)
With (E): Light Camel (2.5Y6.5 / 1.5)
mm
(1600×1240×765)+(1600×1240×765)+(1600×1240×765)
Cross Fin Coil
Hermetically Sealed Scroll Type
m³/h
(13.72+10.53)×3
r.p.m
(6480, 2900)×3
kW
(0.7+4.5)×3
Direct on line (inverter drive)
Propeller Fan
kW
m³/min
210+210+210
Direct Drive
φ15.9 (Flare Connection)
mm
φ34.9 (Brazing Connection)
mm
kg
268+268+268
dBA
High Pressure Switch, Fan Driver Overload Protector,
Over Current Relay, Inverter Overload Protector,
Fusible Plugs
%
kg
Electronic Expansion Valve
Refer to the nameplate of compressor
Installation Manual, Operation Manual, Connection Pipes,
Clamps
C: 4D050535
of 1.5m. The Sound level of "Combination Unit" is a supposed value. During actual operation, these
values are normally somewhat higher as a result of ambient conditions.
RXYQ8MYLKE.
19.7 / 19.4
69.3 / 68.4
19.1 / 19.1
67.2 / 67.2
21.3
256,000
64,500
75.0
0.75×3
65
Deicer
5~100
R-410A
28.2
RXYQ26MYLK(E)
RXYQ8MYLK(E)+RXYQ8MYLK(E)+RXYQ10MYLK(E)
21.1 / 19.8
254,000 / 238,000
64,000 / 59,900
74.4 / 69.7
20.7 / 19.6
248,000 / 235,000
62,600 / 59,300
72.8 / 68.9
23.1
278,000
70,100
81.5
Without (E): Ivory White (5Y7.5 / 1)
With (E): Light Camel (2.5Y6.5 / 1.5)
(1600×1240×765)+(1600×1240×765)+(1600×1240×765)
Cross Fin Coil
Hermetically Sealed Scroll Type
(13.72+10.53)×3
(6480, 2900)×3
(0.7+4.5)×2+(1.6+4.5)
Direct on line (inverter drive)
Propeller Fan
0.75×3
210+210+210
Direct Drive
φ19.1 (Flare Connection)
φ34.9 (Brazing Connection)
268+268+268
65
High Pressure Switch, Fan Driver Overload Protector,
Over Current Relay, Inverter Overload Protector,
Fusible Plugs
Deicer
5~100
R-410A
28.4
Electronic Expansion Valve
Refer to the nameplate of compressor
Installation Manual, Operation Manual, Connection Pipes,
Clamps
C: 4D050535, 4D050536
Conversion Formulae
cfm=m³/min×35.3
Si39-502A
RT=kW×0.284
Btu/h=kW×3412
kcal/h=kW×860
Specifications

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents