3.25 " J3 " Outdoor Unit:

Thermistor (R3, R31 or 32T)
J3
Remote
Controller
Display
Applicable
RXYQ8~30MY1K (E), YLK (E)
Models
Method of
Malfunction is detected from the temperature detected by discharge pipe temperature
thermistor.
Malfunction
Detection
Malfunction
When a short circuit or an open circuit in the discharge pipe temperature thermistor is detected.
Decision
Conditions
Supposed
Causes
Troubleshooting
The alarm indicator is displayed when the fan is being used also.
∗ Refer to "Thermistor Resistance / Temperature Characteristics" table on P278.
Troubleshooting
Malfunction of Discharge Pipe
Defect of thermistor (R31T or R32T) for outdoor unit discharge pipe
Defect of outdoor unit PC board (A1P)
Be sure to turn off power switch before connect or disconnect connector,
Caution
or parts damage may be occurred.
Connector
is connected to X34A
of outdoor unit
PC board
(A1P).
YES
Resistance
is normal when
measured after
disconnecting the thermistor
R31 or 32T from the outdoor
unit PC board.
(3.5kΩ~
400kΩ)
YES
Troubleshooting by Indication on the Remote Controller
NO
NO
Connect the connector and turn on
again.
Replace the thermistor
(R31 or 32T).
Replace outdoor unit PC board
(A1P).
(V3072)