4.2.2
Startup when expected/actual config differ
If the parameter is enabled and
● modules are removed and inserted during operation, this does not lead to a station failure
of the ET 200SP distributed I/O system.
● If the preset configuration does not match the actual configuration, the ET 200SP
distributed I/O system continues to exchange data with the DP master.
If the parameter is disabled and
● modules are removed and inserted during operation, this leads to a station failure of the
ET 200SP distributed I/O system.
● If the preset configuration does not match the actual configuration, data exchange does
not take place between the DP master and the ET 200SP distributed I/O system.
4.2.3
Diagnostic interrupt
You can use this parameter to enable or disable diagnostic interrupts.
4.2.4
Hardware interrupt
You can use this parameter to enable or disable hardware interrupts.
4.2.5
Insert/remove module interrupt
You can use this parameter to enable or disable insert/remove module interrupts.
Interface module IM 155-6 DP HF (6ES7155-6BA01-0CN0)
Manual, 10/2018, A5E03916550-AD
Parameters/address space
4.2 Description of parameters
23