4415 HO - Combustible "Over-Facing" (Optional)

When using the CoolSmart TV kit, Combustible material can be installed over the front of the fireplace. The
combustible material MUST be installed over ½" non-combustible board.
WARNING: If using a trim kit or the Gallery face, a ½ " air space is required from all four sides of the tile stop on
the fireplace. If no trim is being used, the airspace is not required (see below for details).
NOTE: The maximum facing depth (combustible + non-combustible facing) is 1-1/4". Any facing that extends
farther than 1-1/4" must meet mantel clearances.
Over Facing
Over Facing
WARNING: The front of the appliance is subject to high temperatures which may cause discoloration and/or
material degradation. Take this into account when choosing finishing materials.
Page 22 of 33
CoolSmart TV
864, PB 42 Linear, PB 42 CF, 4415 HO
Sku# 98900779
WITH
Trim Kit
Combustible Facing
Allowed
OVER
Non-Combustible board
Non-Combustible
Facing Only
Trim Kit
WITH OUT
Combustible Facing
Allowed
OVER
Non-Combustible board
Non-Combustible
Facing Only
17602029- 11/22/19
Combustible Facing
Required
1/2" (13mm)
Air Space
Fireplace side
Tile Stop
Trim Kit
Combustible Facing
Combustible Facing
can be flush with the
Tile Stop on the fireplace
Fireplace side
Tile Stop