Auxiliary Power; Overload Operation; Simultaneous Weld And Power Table; Auxiliary Power Receptacles - Lincoln Electric Ranger 330MPX Operator's Manual

Hide thumbs Also See for Ranger 330MPX:
Table of Contents

Advertisement

RANGER
®
330MPX

AuXILIARY POWER

WARNING
An electric shock can result in serious injury or death.
Always perform the GFCI test before using the
generator. If the GFCI system fails the test, the
machine must be repaired by an authorized service
center.
If the GFCI fails to trip when the test button is pressed
(power "ON" light does not go off) or fails to reset
(power "ON" light does not go on) the device is
inoperative and should be replaced immediately.
If the GFCI tests properly without any appliance
connected to it but trips each time an appliance is
connected to it, the appliance has a ground fault and
needs to be repaired or replaced. DO NOT USE THE
APPLIANCE IF THIS CONDITION OCCURS: A REAL
SHOCK HAZARD MAY EXIST.
Due to the risk of power interruption, do not power life
support equipment from this machine.
GFCI's do not protect against short circuits or
overloads.
Unplug accessories and tools before attempting
service.
Close the front service doors protecting the receptacles
when operating the machine.
Do not test or reset the GFCI while at idle speed.
If the LED blinks, stop using the GFCI receptacle and
have it replaced by an authorized service center.
Long extension cords or cords with poor insulation may
allow enough leakage current to trip the GFCI.

OvERLOAD OPERATION:

In the event that the combined weld + auxiliary power load
exceeds the machine's capability, the welding circuit will continue
to drive as much power as possible without causing damage to
any components. Continued operation in an overload state will bog
and stall the engine. Overloading just the auxiliary power circuits
will cause the circuit breakers to trip.

SIMuLTANEOuS WELD AND POWER TABLE

AuXILIARY POWER RECEPTACLES:

Combined continuous output of all receptacles is limited to 10.0
kW for the Ranger 330MPX. The current rating of any plug used
with a receptacle must be at least equal to the rating of the
receptacle.
Output voltage is within ±5% at all loads up to rated capacity.
FIGURE B.2
3
2
4
1
5
1 GFCI
The GFCI module protects the (2) 120 VAC
module
duplex receptacles. A red light illuminates when
power is applied to the 120 VAC duplexes.
2 50 amp
circuit
breaker
3 20 amp
Protects the GFCI and (2) 120 VAC duplexes
circuit
from overload. If the circuit breaker opens, the
breaker
receptacles will not work. Press to reset. If it
continues to remain open, contact an authorized
Lincoln service shop.
4 120 VAC
The 120 VAC duplex receptacles should only be
duplex
used with three wire grounded type plugs or
approved double insulated tools with two wire
plugs.
5 120/240
VAC 14-
50R
recept.
6 240 VAC
6-50R
recept.
7 Neutral
If the machine is to be grounded, use a AWG #8
Stud
copper wire or larger to a solid earth ground.
Refer to local codes and the U.S. National
Electrical Code.
B-13
OPERATION
TABLE B.6
6
7
4

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents