Potterton SIRIUS THREE FS 130 Installation, User And Service Manual page 75

Floor-standing condensing gas boiler
Table of Contents

Advertisement

Fig.91
303:Fonct ramonage
Puissance brûleur
Pleine charge
Régler ?
MENU
Fig.92
130 - 150 kW
7702639 - v03 - 10072018
4. Turn the
5. Press the
6. Confirm the selection by pressing the
MW-4000284-FR-01
200 - 250 kW
7. Unscrew:
SIRIUS THREE FS
130
SIRIUS THREE FS
150
SIRIUS THREE FS
200
SIRIUS THREE FS
250
8. Connect the flue gas analyser to the measurement point.
Important
9. Set the boiler's heat input to 100% at full load.
10. Measure the percentage of CO
11. Compare the values measured with the set point values in the Control
and setting values table.
12. If necessary, adjust the air/gas ratio using the gas flow rate
adjustment screw.
button to select Full load.
button to adjust the setting.
the left-hand plug, which corresponds to
the flue gas measurement point connec­
tion.
the plug for the rear nozzle.
Ensure that the opening around the sensor is completely sealed
when taking measurements.
SIRIUS THREE FS 130 and SIRIUS THREE FS 150: Insert the
sensor into the flue gas measurement point to at least 8 cm.
8 Commissioning
button.
in the flue gases.
2
75

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents