Empire Comfort Systems DVLXG55BP90N Installer's Manual page 31

Direct vent zero clearance gas fireplace heater
Table of Contents

Advertisement

INSTALLATION
Framing
1. Once termination location has been determined build
a frame with material that has the same dimensions as
the current wall, as shown in the figure below.
14 1/2"
2. Cut a 9-1/2 inches tall by 14-1/2 inches wide hole into
the wall, be sure to stay inside the new framing.
Remove (6) screws
3. Remove the front fascia by removing the 6 #10-24 X
3/8 inch screws shown above. Set the front
fascia and foam gasket aside.
4. Set the Power-Vent on its face and apply a bead of
silicone sealant to the rear surface of the flange to
create a weather tight seal between the mounting
flange and the wall.
VENT FRAMING AND FINISHING
NOTE: Sealant must be rated for 300° F continuous
exposure at minimum.
5. Place the Power-vent into the hole with the inducer
outlet toward the bottom and secure with 8 #10X 1
inch screws as shown below.
6. Apply a bead of silicone sealant to create a watertight
seal between finishing material and the Power-Vent
flange.
NOTE: Sealant must be rated for 300° F continuous
exposure at minimum.
7. Reinstall foam gasket with the cutout on the bottom
and front fascia with 6 #10-24 X 3/8 inch screws.
GASKET
HORIZONTAL FASCIA
31