Installing Series 505 Remote Base Controller (continued)
WARNING
!
Series 505 RBC
LED Display
Installing Series 505 System Hardware
3-20
Control devices can fail in an unsafe condition that could result in
death or serious injury and/or damage to equipment.
Do not change the base thumbwheel numbers when the system is
operating. This may cause the base to be logged off the system.
When the base is logged off the system, all discrete outputs will be
turned off, analog outputs will be frozen, and word and discrete
inputs will go to 0.
The display at the top of the module (see Figure 3-15) indicates the status of
the Series 505 RBC. Status is displayed in integer format; see Table 3-6 for
definitions of the displays.

Table 3-6 Series 505 RBC LED Messages

Display
0
RBC Good
1
Self Diagnostics Failure
2
Module Mismatch
3
I/O Communication Time Out
4
RAM Parity Error
5
Standby, No Configuration
6
Address Mismatch
7
Communication Good, No Configuration
8
Watchdog Time Out
C
Standby, Configuration
Base Thumbwheel

Figure 3-15 Series 505 Remote Base Controller

Definitions
LED Display
RS-232 port (male)
I/O port (female)