Table A-1 Environmental Specifications - Siemens SIMATIC TI555 System Manual

Table of Contents

Advertisement

A.1
Series 505 System Specifications
A-2
System Specifications

Table A-1 Environmental Specifications

Models
Storage Temperature
Operating Temperature
Relative Humidity
Vibration
Sinusoidal:
Random:
Impact Shock
Pollution Degree
Electric Noise Immunity
Conducted noise:
Radiated noise:
Electrostatic discharge:
System Isolation
PPX:545–1102 Controller
PPX:555–1101 Controller
PPX:555–1102 Controller
PPX:505–6851 Remote Base Controller
PPX:505–6660A Power Supply
PPX:505–6663 Power Supply
–40 to 70 C; –40 to 158 F
0 to 60 C; 32 to 140 F
5% to 95% noncondensing
IEC 68-2-6, Test Fc;
0.15 mm peak-to-peak, 10–57 Hz;
1.0 g, 57–150 Hz
NAVMAT P–9492 or IEC 68–2–34,
2
Test Fdc with 0.04 g
/Hz, 80–350 Hz, and
3 dB/octave rolloff, 80–20 Hz and
350–2000 Hz at 10 min/axis
IEC, 68–2–27, Test Ea; Half sine, 15 g 11 ms
2, IEC664, 684A
IEC 801, Part 4, Level 3
MIL-STD-461B, Part 4; CS01, CS02, CS06
IEC 255–4, Appendix C
EEC 4517/79 Com(78) 766 Final, Part 4
IEEE 472, 2.5 kV
IEC 801 Part 3, Level 3
MIL-STD-461B, Part 4; RS01, RS02
IEC 801, Part 2, Level 4 (15 kV)
1500 Vrms (user-side to controller-side)