Siemens TIM 1531 IRC Operating Instructions Manual

Siemens TIM 1531 IRC Operating Instructions Manual

Telecontrol
Table of Contents

Advertisement

SIMATIC NET
S7-1500 - TeleControl
TIM 1531 IRC
Operating Instructions
02/2018
C79000-G8976-C468-02
___________________
Preface
___________________
Application and functions
LEDs, connectors, switches,
___________________
card slot
Installation, connecting up,
___________________
commissioning
___________________
Configuration
Block library TeleControl
___________________
ST7
___________________
The Web server (WBM)
___________________
Diagnostics and upkeep
___________________
Technical specifications
___________________
Approvals
___________________
Dimension drawings
___________________
Accessories
STEP 7 V5 configuration of
___________________
the proxy
___________________
Documentation references
1
2
3
4
5
6
7
8
9
A
B
C
D

Advertisement

Table of Contents
loading

Summary of Contents for Siemens TIM 1531 IRC

  • Page 1 ___________________ Application and functions LEDs, connectors, switches, ___________________ SIMATIC NET card slot Installation, connecting up, ___________________ commissioning S7-1500 - TeleControl TIM 1531 IRC ___________________ Configuration Block library TeleControl ___________________ Operating Instructions ___________________ The Web server (WBM) ___________________ Diagnostics and upkeep...
  • Page 2 Note the following: WARNING Siemens products may only be used for the applications described in the catalog and in the relevant technical documentation. If products and components from other manufacturers are used, these must be recommended or approved by Siemens. Proper transport, storage, installation, assembly, commissioning, operation and maintenance are required to ensure that the products operate safely and without any problems.
  • Page 3: Preface

    CAUTION To prevent injury, read the manual before use. Validity of this manual This manual is valid for the following product: TIM 1531 IRC Article number: 6GK7 543-1MX00-0XE0 Hardware product version 1 Firmware version 1.1 Communications module for SIMATIC S7-1500 / S7-400 / S7-300, SINAUT ST7 protocol,...
  • Page 4 Abbreviations/acronyms This manual often uses the following abbreviations/acronyms: ● TIM / submodule / module The names are used instead of the full product name "TIM 1531 IRC" of the device. ● ST7 Short form for the telecontrol protocol "SINAUT ST7"...
  • Page 5 To be able to return to the initial page after jumping to a cross reference, some PDF readers support the command <Alt>+<left arrow>. Current manual release on the Internet You will also find the current version of this manual on the Internet pages of Siemens Industry Online Support: Link: (https://support.industry.siemens.com/cs/ww/en/ps/24710/man) Sources of information and other documentation You can find an overview of further reading and references in the Appendix of this manual.
  • Page 6 The firmware is signed and encrypted. This ensures that only firmware created by Siemens can be downloaded to the device. Device defective If a fault develops, please send the device to your SIEMENS service center for repair. Repairs on-site are not possible. Recycling and disposal The product is low in pollutants, can be recycled and meets the requirements of the WEEE directive 2012/19/EU "Waste Electrical and Electronic Equipment".
  • Page 7: Table Of Contents

    Notes on use in hazardous areas according to UL HazLoc and FM ........42 Installation ..........................43 Wiring ............................45 Inserting the SD card ......................47 Commissioning ........................48 Startup - LED pattern ......................49 TIM 1531 IRC Operating Instructions, 02/2018, C79000-G8976-C468-02...
  • Page 8 Protection ..........................96 4.20.4 Configuring access protection ....................97 4.21 Creating telecontrol connections for the ST7 communication ..........99 4.22 Data points ........................... 104 4.22.1 Data point configuration ....................... 104 4.22.2 "General" tab ........................111 TIM 1531 IRC Operating Instructions, 02/2018, C79000-G8976-C468-02...
  • Page 9 Parameter typical Par12D_S ....................198 5.7.1.19 Parameter typical Par12D_S ....................208 5.7.1.20 FC Safe ..........................214 5.7.1.21 Setpoint typical Set01W_S ....................218 5.7.1.22 Setpoint typical Set01W_R ....................222 5.7.2 Optional blocks ........................226 TIM 1531 IRC Operating Instructions, 02/2018, C79000-G8976-C468-02...
  • Page 10 System time ......................... 267 6.5.4 NTP ............................267 6.5.5 Web server ........................... 268 6.5.6 DNS configuration ........................ 268 Maintenance ......................... 268 6.6.1 Firmware ..........................268 6.6.2 Operating status ........................270 Diagnostics ........................... 270 TIM 1531 IRC Operating Instructions, 02/2018, C79000-G8976-C468-02...
  • Page 11 STEP 7 V5 configuration of the proxy ....................313 Configuration in STEP 7 V5 ....................313 Proxies in HW Config ......................314 Special features of the PROXY TIM 1531 IRC ..............315 SINAUT configuration ......................315 TIM 1531 IRC Operating Instructions, 02/2018, C79000-G8976-C468-02...
  • Page 12 Table of contents Exporting configuration data ....................316 Documentation references ........................319 Glossary .............................. 323 Index ..............................337 TIM 1531 IRC Operating Instructions, 02/2018, C79000-G8976-C468-02...
  • Page 13: Application And Functions

    Application and functions Properties of the TIM Application The TIM 1531 IRC is a telecontrol communications module for the following SIMATIC automation systems: ● S7-300 ● S7-400 ● S7-1500 The TIM serves as the connection of the SIMATIC stations via public or private infrastructures to a telecontrol master station.
  • Page 14: Communications Services

    ● Station Expansion of existing SINAUT systems In existing SINAUT systems with SIMATIC S7-300/400 stations and TIM modules for the telecontrol functions, the TIM 1531 IRC can be used universally for expansions. Communications services The following communications services are supported:...
  • Page 15 You configure the messages in the message editor, see section Messages (Page 127). The use of program blocks is not necessary for this. You will find information about addressing in ST7 and configuring in the section Communication types (Page 56). TIM 1531 IRC Operating Instructions, 02/2018, C79000-G8976-C468-02...
  • Page 16 The Ethernet interfaces of the TIM must be configured with the network type "Neutral" for the S7 communications services. You will find information on the communications functions and the program blocks in the STEP 7 information system. TIM 1531 IRC Operating Instructions, 02/2018, C79000-G8976-C468-02...
  • Page 17: Pg Routing

    PG routing is supported between the modules listed in the table and via the specified media. A requirement for the CPs is that the options "S7 communication" and "Online functions" are enabled in the "Communication types" parameter group. Module TIM 1531 IRC TIM 4R-IE TIM 3V-IE / TIM CP 1243-8 IRC...
  • Page 18: Security Functions

    • If you have systems with high security requirements, use the secure protocols for example HTTPS or SNMPv3. • If you connect to public networks, you should use security modules with a firewall, see below. Refer to the information in the section Security recommendations (Page 51). TIM 1531 IRC Operating Instructions, 02/2018, C79000-G8976-C468-02...
  • Page 19 ● Logging To allow monitoring, events can be stored in log files that can be read out using the configuration tool or can be sent automatically to a Syslog server. TIM 1531 IRC Operating Instructions, 02/2018, C79000-G8976-C468-02...
  • Page 20: Other Services And Properties

    ● Storage and event-driven transfer of process data The TIM can store events of different classes and transfer the corresponding process values individually or bundled together to the communications partner. The transfer can be triggered by various triggers. TIM 1531 IRC Operating Instructions, 02/2018, C79000-G8976-C468-02...
  • Page 21: Configuration Examples

    Below, you will find configuration examples for the TIM. Sending SMS messages Figure 1-1 Sending messages by SMS The TIM can send SMS messages to a mobile phone. SMS messages are generated and sent due to events. TIM 1531 IRC Operating Instructions, 02/2018, C79000-G8976-C468-02...
  • Page 22 Inter-station communication between S7 stations with a TIM is possible via IP-based and WAN networks. Inter-station communication via mobile wireless runs via a master station that forwards the messages to a target subscriber. TIM 1531 IRC Operating Instructions, 02/2018, C79000-G8976-C468-02...
  • Page 23 In these examples the TIM modules of the master communicate with the station or node station TIMs via mobile wireless: ● Left: Use of the Ethernet interface with VPN ● Right: Use of the serial interface and the transmission protocol MSCsec TIM 1531 IRC Operating Instructions, 02/2018, C79000-G8976-C468-02...
  • Page 24 An IP-based wireless network could also be connected via the Ethernet interface. Figure 1-4 Communication using mobile wireless (at the top) and wireless (at the bottom) TIM 1531 IRC Operating Instructions, 02/2018, C79000-G8976-C468-02...
  • Page 25: Performance Data And Configuration Limits

    4 connection resources only for PG/OP connections (see below) ● PG/OP connections 4 connection resources for connections to the engineering station or HMI devices (included in the configuration limits of the S7 connections, see above) TIM 1531 IRC Operating Instructions, 02/2018, C79000-G8976-C468-02...
  • Page 26 ● Number of characters per e-mail Maximum number of characters that can be transferred per e-mail: 256 ASCII characters including any value sent at the same time TIM 1531 IRC Operating Instructions, 02/2018, C79000-G8976-C468-02...
  • Page 27: Requirements And Compatibility

    All CPUs that can be configured in STEP 7 as of firmware version V2.1 ● S7-300 All CPUs that can be configured in STEP 7 with a PROFINET interface ● S7-400 All CPUs that can be configured in STEP 7 TIM 1531 IRC Operating Instructions, 02/2018, C79000-G8976-C468-02...
  • Page 28: Expansion Of Sinaut Projects

    • TIM 4R-IE Stand-alone • CP 1243-8 IRC (V3.0) CP 1243-8 IRC STEP 7 Basic TIM 1531 IRC (V1.0) TIM 1531 IRC STEP 7 Profession- CP 1542SP-1 IRC (V2.0) CP 1542SP-1 IRC STEP 7 Profession- Extension of existing SINAUT projects in the TIA Portal...
  • Page 29: Requirements For The Expansion

    TIM 4R-IE Stand-alone for S7-400 becomes TIM 1531 IRC A TIM 4R-IE Stand-alone required in STEP 7 V5 that is assigned to a CPU-400 must be replaced by a TIM 1531 IRC for the expansion of classic SINAUT projects in STEP 7 Professional.
  • Page 30 The following firmware versions of the communication modules used are required: – TIM 1531 IRC - V1.1 A TIM 1531 IRC V1.0 can be exchanged for a TIM 1531 IRC V1.1 but not the other way round. The mode of the "Telecontrol configuration" ("Basic settings") is set to "Configure".
  • Page 31: Leds, Connectors, Switches, Card Slot

    Serial number (2D matrix code, alphanumeric) ⑥ ⑬ MAC address Ethernet interface X1 MAC address Ethernet interface X3 ⑦ ⑭ X4: Serial interface, plug (RS-232/RS-485) LEDs for Ethernet communication status: X1, X2, X3 TIM 1531 IRC Operating Instructions, 02/2018, C79000-G8976-C468-02...
  • Page 32: Leds

    Missing or incorrect configuration Duplicate IP address detected * During startup and during the firmware update the TIM shows deviant LED patterns. ** Relates to connections both to the CPU and to the communications partner. TIM 1531 IRC Operating Instructions, 02/2018, C79000-G8976-C468-02...
  • Page 33: Electrical Connectors

    The three Ethernet interfaces are not designed as a switch, but are intended for connection to different networks. Operation in the same physical network is not permitted. The pin assignment of the Ethernet interfaces and other data can be found in the section Technical specifications (Page 293). TIM 1531 IRC Operating Instructions, 02/2018, C79000-G8976-C468-02...
  • Page 34: Serial Interface X4

    Labeling Function Reference ground 24 VDC For information on the connector, refer to the section "Wiring (Page 45)". You will find further data on the power supply in section Technical specifications (Page 293). TIM 1531 IRC Operating Instructions, 02/2018, C79000-G8976-C468-02...
  • Page 35: Switch

    – Time-of-day synchronization via Telecontrol connections – S7 connections are terminated. The following functions remain enabled: – Access to the WBM of the TIM – Time-of-day synchronization with NTP – Diagnostic functions of the TIM TIM 1531 IRC Operating Instructions, 02/2018, C79000-G8976-C468-02...
  • Page 36 The TIM is reset to the factory set- restart tings. All the configuration data is deleted. For the relevant LED patterns see the following section: ● Startup - LED pattern (Page 49) ● Resetting to factory settings (Page 287) TIM 1531 IRC Operating Instructions, 02/2018, C79000-G8976-C468-02...
  • Page 37: Sd Card Slot

    (see below) can be saved retentively. Card errors / diagnostics Card errors are indicated by entries in the diagnostics buffer. Inserting the card Inserting the SD is described in the section Inserting the SD card (Page 47). TIM 1531 IRC Operating Instructions, 02/2018, C79000-G8976-C468-02...
  • Page 38 You can specify whether values of events are stored globally in the configuration of the TIM. There are also options for storing on the SD card for every data point created as an event. TIM 1531 IRC Operating Instructions, 02/2018, C79000-G8976-C468-02...
  • Page 39: Installation, Connecting Up, Commissioning

    A suitable device is, for example, the Dehn Blitzductor BVT AVD 24, article number 918 422 or a comparable protective element. Manufacturer: DEHN+SOEHNE GmbH+Co.KG Hans Dehn Str.1 Postfach 1640 D-92306 Neumarkt, Germany TIM 1531 IRC Operating Instructions, 02/2018, C79000-G8976-C468-02...
  • Page 40: Notes On Use In Hazardous Areas

    60 °C. TIM 1531 IRC Operating Instructions, 02/2018, C79000-G8976-C468-02...
  • Page 41: Notes On Use In Hazardous Areas According To Atex / Iecex

    Notes on use in hazardous areas according to ATEX / IECEx WARNING DIN rail In the ATEX and IECEx area of application only a Siemens DIN rail 6ES7590-1Axx0-0AB0 may be used to mount the TIM. WARNING Requirements for the cabinet To comply with EC Directive 2014/34 EU (ATEX) or the conditions of IECEx, this enclosure or cabinet must meet the requirements of at least IP54 in compliance with EN 60529.
  • Page 42: Notes On Use In Hazardous Areas According To Ul Hazloc And Fm

    The control cabinet cover or housing must be secured so that it can only be opened with a tool. An appropriate strain-relief assembly for the cable must be used. WARNING Substitution of components may impair suitability for Division 2. TIM 1531 IRC Operating Instructions, 02/2018, C79000-G8976-C468-02...
  • Page 43: Installation

    Switch off the power supply of the TIM before you install or remove the TIM. Installing and removing modules with the power supply on can lead to damage to the modules and to loss of data. TIM 1531 IRC Operating Instructions, 02/2018, C79000-G8976-C468-02...
  • Page 44 Protecting the modules from slipping on the DIN rail If you install the modules in an area with mechanical load, use suitable clamping devices at both ends of the device group to secure the modules on the DIN rail, e.g. Siemens and retainer 8WA1808.
  • Page 45: Wiring

    A PELV circuit contains a connection to protective ground. Without a connection to protective ground, or in case there is a fault in the connection to the protective ground, the voltage for the circuit is not stabilized. TIM 1531 IRC Operating Instructions, 02/2018, C79000-G8976-C468-02...
  • Page 46 Contacting the shield of the cable on the plug The shield of the cable must be contacted. To do this, strip the insulation from the end of the cable and connect the shield to functional earth. TIM 1531 IRC Operating Instructions, 02/2018, C79000-G8976-C468-02...
  • Page 47: Inserting The Sd Card

    Installation, connecting up, commissioning 3.4 Inserting the SD card For the network connection products from the Siemens accessories program are recommended, see Appendix Cables, connecting cables (Page 310) Turn the power supply on only after the TIM has been completely wired and connected.
  • Page 48: Commissioning

    You will find more detailed information on loading in the following sections of the STEP 7 information system: ● “Loading project data" ● “Using online and diagnostics functions" On completion of the download close the front cover of the TIM. TIM 1531 IRC Operating Instructions, 02/2018, C79000-G8976-C468-02...
  • Page 49: Startup - Led Pattern

    The startup was incorrect and was aborted. * * If the startup is incorrect, note which phase (1, 2, 3) is reached and when it is aborted. You may be able to localize the error. TIM 1531 IRC Operating Instructions, 02/2018, C79000-G8976-C468-02...
  • Page 50 Installation, connecting up, commissioning 3.6 Startup - LED pattern TIM 1531 IRC Operating Instructions, 02/2018, C79000-G8976-C468-02...
  • Page 51: Configuration

    ● Keep the firmware up to date. Check regularly for security updates of the firmware and use them. ● Check regularly for new features on the Siemens Internet pages. – You can find information on Industrial Security here: Link: (http://www.siemens.com/industrialsecurity) –...
  • Page 52 The following table provides you with an overview of the open ports on this device. ● Protocol / function Protocols that the device supports. ● Port number (protocol) Port number assigned to the protocol. TIM 1531 IRC Operating Instructions, 02/2018, C79000-G8976-C468-02...
  • Page 53 These can be: ● MSC / 26382 (TCP) - configurable with a central interface: 1024 .. 65535 ● NTP / 123 (UDP) ● DNS / 53 (UDP) TIM 1531 IRC Operating Instructions, 02/2018, C79000-G8976-C468-02...
  • Page 54: Configuration In Step 7

    4. Create the necessary networks for networking the interfaces. Refer to the information in the section Networking a TIM (Ethernet addresses / WAN settings) (Page 61). 5. Complete the configuration of the modules and networks. TIM 1531 IRC Operating Instructions, 02/2018, C79000-G8976-C468-02...
  • Page 55 ● Copying data points In much the same way as with PLC tags, you can also copy data points. For a detailed description of the functions, refer to the section Data point configuration (Page 104). TIM 1531 IRC Operating Instructions, 02/2018, C79000-G8976-C468-02...
  • Page 56: Communication Types

    Creating telecontrol connections for the ST7 communication (Page 99). When different networks between two subscribers have been created in the network configuration, you can create redundant telecontrol connections. In the configuration these TIM 1531 IRC Operating Instructions, 02/2018, C79000-G8976-C468-02...
  • Page 57 With a CP and a classic TIM in the S7-300 rack, the CPU is assigned automatically to the communication module via the rack. With the TIM 1531 IRC and a TIM 4R-IE Stand-alone, you must assign the local CPU manually.
  • Page 58: Basic Settings

    Retentive saving of events If you use an optional SD card in the TIM, in this parameter group you set the conditions for saving the values of messages whose data points are configured as an event. TIM 1531 IRC Operating Instructions, 02/2018, C79000-G8976-C468-02...
  • Page 59: Overview: Connection To Lan / Wan

    IP-based mobile phone communication (with gateway to the Internet) only with SCALANCE M router Serial interface ● Classic WAN – Dedicated line (incl. analog wireless network) – Dial-up network (analog, ISDN mobile phone) ● IP-based – MSC / MSCsec via GPRS TIM 1531 IRC Operating Instructions, 02/2018, C79000-G8976-C468-02...
  • Page 60 ● MODEM MD720 (Page 306) ● Connecting cables between TIM and modem: Cables, connecting cables (Page 310) To connect a modem to the TIM a cable must be ordered. ● SCALANCE S: /10/ (Page 321) TIM 1531 IRC Operating Instructions, 02/2018, C79000-G8976-C468-02...
  • Page 61: Networking A Tim (Ethernet Addresses / Wan Settings)

    In the graphic network view, you have an overview of the subnets of the entire system in the project. 2. First configure the interface parameters described in the section WAN settings of the interfaces (Page 63): – WAN type – Network type – Network node type – Modem type TIM 1531 IRC Operating Instructions, 02/2018, C79000-G8976-C468-02...
  • Page 62 MSC connection via Ethernet interface X1 (left) and via serial interface (right) The color of the serial changes from blue to green if the WAN type is changed from "Classic WAN" to "IP-based". TIM 1531 IRC Operating Instructions, 02/2018, C79000-G8976-C468-02...
  • Page 63: Wan Settings Of The Interfaces

    With the classic network types dedicated line and dialup network, a modem needs to be connected to the serial interface of the TIM. You select the suitable modem type using the following parameters (serial interface only): TIM 1531 IRC Operating Instructions, 02/2018, C79000-G8976-C468-02...
  • Page 64: Parameters Of Wan Networks

    Modem for analog dialup networks (network type "Dialup network") – MD4 ISDN modem (network type "Dialup network") – MD720 Siemens-GSM modem MD720 (network type "Dialup network") – Third-party modem Any compatible modem for the network types "Dedicated line" or "Dial-up network" (analog / ISDN) If you configure "Dialup network"...
  • Page 65 From this parameter time values (e.g. send repetition time) are derived for monitoring functions. Network settings ● Dependence on direction Direction dependency of the network – Duplex – Half duplex ● Transmission speed Speed at which the CP and modem communicate. TIM 1531 IRC Operating Instructions, 02/2018, C79000-G8976-C468-02...
  • Page 66 The connected TIM modules adopt the settings made here on the network. Station list This is where you can find an overview table of the stations connected to the network with their most important parameters. TIM 1531 IRC Operating Instructions, 02/2018, C79000-G8976-C468-02...
  • Page 67: Ethernet Interface

    First, specify whether the MSC center or the router should be available via DNS, a fixed or a dynamic IP address. The MSC master station is connected to the Internet via a router. TIM 1531 IRC Operating Instructions, 02/2018, C79000-G8976-C468-02...
  • Page 68 MSC protocol settings - Ethernet: MSC station/node station The description applies to the parameter group of the Ethernet interface with the Network node type "Station" / "Node station". TIM 1531 IRC Operating Instructions, 02/2018, C79000-G8976-C468-02...
  • Page 69 If there is still a disruption on the connection when the set time has elapsed, the disruption is signaled to all accessible connection partners of the disrupted station. Default setting: 0. Permitted range: 0...255. If you enter 0 (zero), the function is disabled. TIM 1531 IRC Operating Instructions, 02/2018, C79000-G8976-C468-02...
  • Page 70 Entry of the user name for Internet access via the mobile wireless network. You obtain this information from your network provider. ● APN password Entry of the password for Internet access via the mobile wireless network. You obtain this information from your network provider. TIM 1531 IRC Operating Instructions, 02/2018, C79000-G8976-C468-02...
  • Page 71: Tcp Connection Monitoring

    If there is still a disruption on the connection when the set time has elapsed, the disruption is signaled to all accessible connection partners of the disrupted station. Default setting: 0. Permitted range: 0...255. If you enter 0 (zero), the function is disabled. TIM 1531 IRC Operating Instructions, 02/2018, C79000-G8976-C468-02...
  • Page 72: Web Server Access

    With parallel connection of several modems to the interface of the TIM (star-shaped network) ● RS-485 termination Enable the option when connecting a terminating resistor for the RS-485 bus when a star- shaped network is connected. TIM 1531 IRC Operating Instructions, 02/2018, C79000-G8976-C468-02...
  • Page 73 (RTS/CTS delay time = 0). As soon as the CTS signal comes from the modem, the send delay time is started. Sending starts after the time has elapsed. Default setting: 0. Permitted range: 0...65535 TIM 1531 IRC Operating Instructions, 02/2018, C79000-G8976-C468-02...
  • Page 74 Default setting: 0. Permitted range: 0...255. If you enter 0 (zero), the function is disabled. Event transmission ● Type of transmission Specifies the form in which data messages are sent. – As single messages – Several messages as a block TIM 1531 IRC Operating Instructions, 02/2018, C79000-G8976-C468-02...
  • Page 75: Dialup Network

    Default setting: 50. Permitted range: 0...90 If 0 (zero) is set, all spontaneous frames are sent at the call. TIM 1531 IRC Operating Instructions, 02/2018, C79000-G8976-C468-02...
  • Page 76 Entry of your own telephone number for the network node including the area code. Permitted values: – Digits 0 ... 9 – Plus character (+) as placeholder for the trunk prefix (usually 00 or 09) before the international area code Example: +1230123456789 TIM 1531 IRC Operating Instructions, 02/2018, C79000-G8976-C468-02...
  • Page 77 The TIM sends conditional spontaneous messages at a configured time of day, configurable with "Hours" / "Minutes". – Time scheme The TIM sends the conditional spontaneous messages cyclically at a configurable interval, configurable with "Hours" / "Minutes". TIM 1531 IRC Operating Instructions, 02/2018, C79000-G8976-C468-02...
  • Page 78 Specifies the form in which data messages are sent. – As single messages – Several messages as a block Mobile wireless settings ● PIN PIN of the SIM card of the modem MD720 TIM 1531 IRC Operating Instructions, 02/2018, C79000-G8976-C468-02...
  • Page 79: Web Server

    ● Web: Access Web diagnostics and the file system of the module Read and write access to all data in the Web server You will find further help on the roles and rights of users in the STEP 7 information system. TIM 1531 IRC Operating Instructions, 02/2018, C79000-G8976-C468-02...
  • Page 80: Partner Stations

    Follow the steps below to import the configuration data from STEP 7 V5 1. In your STEP 7 Professional project, select the TIM into which you want to import the SDBs from the STEP 7 V5 project. 2. Select the "Partner stations" parameter group. TIM 1531 IRC Operating Instructions, 02/2018, C79000-G8976-C468-02...
  • Page 81: Communication With The Cpu

    ● Cycle idle time Wait time between two scan cycles of the CPU memory area ● Max. number of write jobs Maximum number of write jobs to the CPU memory area within a CPU scan cycle TIM 1531 IRC Operating Instructions, 02/2018, C79000-G8976-C468-02...
  • Page 82 Assignment of the PLC tags for partner status / path status In the two bytes of the PLC tag of the data type Word (DB, memory bit, output) the following information is output: ● Byte 0: Partner status ● Byte 1: Path status TIM 1531 IRC Operating Instructions, 02/2018, C79000-G8976-C468-02...
  • Page 83 ● Two bits for the interface of the main path ● Two bits for the interface of the substitute path ● Two bits for the status of the main path ● Two bits for the status of the substitute path TIM 1531 IRC Operating Instructions, 02/2018, C79000-G8976-C468-02...
  • Page 84 Same coding of the configured interface for the main and the substitute path means that there is no path redundancy (only one interface configured). The path status is output via the bits of the main path (1st path). TIM 1531 IRC Operating Instructions, 02/2018, C79000-G8976-C468-02...
  • Page 85: Time-Of-Day Synchronization

    WAN networks. When using an external time source, the connected S7 station can obtain the current time of day both via the CPU as well as via the TIM or a CP. TIM 1531 IRC Operating Instructions, 02/2018, C79000-G8976-C468-02...
  • Page 86 ● Setting the time of day manually using the WBM If you have configured a time source for the TIM, you can also set the time via the WBM, see section System time (Page 267). TIM 1531 IRC Operating Instructions, 02/2018, C79000-G8976-C468-02...
  • Page 87 The send direction of the time-of-day messages is derived automatically from the node type of the connected interfaces: Master staion ⇒ Node station ⇒ Station The settings for the network are not necessary with time-of-day synchronization via Ethernet. TIM 1531 IRC Operating Instructions, 02/2018, C79000-G8976-C468-02...
  • Page 88 3. For the stations set the parameters of time-of-day synchronization in the parameter group "Receive time". 4. If necessary, enable the "To local station" option in the "Send time" parameter group if the assigned CPU should also be synchronized. TIM 1531 IRC Operating Instructions, 02/2018, C79000-G8976-C468-02...
  • Page 89: Time Stamp

    Format of the time stamp The ST7 time stamp is coded in BCD format. The exception is the half byte (nibble) with the time status. The structure of 8 bytes is assigned as follows: TIM 1531 IRC Operating Instructions, 02/2018, C79000-G8976-C468-02...
  • Page 90: Msc Authentication

    Relevant on the serial interface when using MSC via mobile wireless Parameter ● User name User name for communication using MSC ● Password Password for communication using MSC The user name and password must be different for every MSC station in the network. TIM 1531 IRC Operating Instructions, 02/2018, C79000-G8976-C468-02...
  • Page 91: Smsc

    To be able to use encrypted transfer, you need to load the certificate of your e-mail account in the certificate manager of STEP 7. You obtain the certificate from your e-mail service provider. TIM 1531 IRC Operating Instructions, 02/2018, C79000-G8976-C468-02...
  • Page 92: Snmp

    Enables the use of SNMPv3 for the device. For information on the configuration of the required algorithms see below (SNMPv3). SNMPv1 The community strings need to be sent along with queries to the device via SNMPv1. TIM 1531 IRC Operating Instructions, 02/2018, C79000-G8976-C468-02...
  • Page 93 SNMP. For new roles, you can freely configure individual rights. You will find information on users, roles and the password policy in the information system of STEP 7. TIM 1531 IRC Operating Instructions, 02/2018, C79000-G8976-C468-02...
  • Page 94: Security And Protection

    If you use communication with authentication for the module, for example SSL/TLS for secure transfer of e-mails, certificates are required. You need to import certificates of non- Siemens communications partners into the STEP 7 project and download them to the module with the configuration data: 1.
  • Page 95 (see above). Follow the steps outlined below: 1. In the STEP 7 project open the global certificate manager: Global security settings > Certificate manager 2. Open the "Device certificates" tab. TIM 1531 IRC Operating Instructions, 02/2018, C79000-G8976-C468-02...
  • Page 96: Protection

    The default access level is "Full access (no protection)". Every user can read and modify the configuration. No password has been configured and no password is required for online access. TIM 1531 IRC Operating Instructions, 02/2018, C79000-G8976-C468-02...
  • Page 97: Configuring Access Protection

    You can enter several passwords setting up different access rights for different user groups. The passwords are entered in the table so that precisely one access level is assigned to each password. The "Access level" column shows how the password takes effect. TIM 1531 IRC Operating Instructions, 02/2018, C79000-G8976-C468-02...
  • Page 98 The hardware configuration and the blocks are protected from unauthorized online access according to the set access level. If an operation cannot be executed without a password due to the set access level, a dialog appears prompting entry of a password. TIM 1531 IRC Operating Instructions, 02/2018, C79000-G8976-C468-02...
  • Page 99: Creating Telecontrol Connections For The St7 Communication

    For connections between an application on the master station PC and an S7 station, always select the application as the starting point because it can only be selected in the list of starting points. TIM 1531 IRC Operating Instructions, 02/2018, C79000-G8976-C468-02...
  • Page 100 – If no connection is displayed in the upper table, there is a configuration error in the corresponding stations or networks. In this case, close the dialog with the "Close" button and complete the configration. TIM 1531 IRC Operating Instructions, 02/2018, C79000-G8976-C468-02...
  • Page 101 (starting point, node, endpoint). Based on the color of the symbols for the connection endpoint you can recognize connections that are not permitted. ● Blue symbols for the connection point: Valid connections ● Red symbols for the connection point: Invalid connections TIM 1531 IRC Operating Instructions, 02/2018, C79000-G8976-C468-02...
  • Page 102 – Incompatible settings between modem and network parameters – Connections via nodes that are not configured as node stations. ● Two connections to one partner (endpoint) via the same interface of a module (start point) are not permitted. TIM 1531 IRC Operating Instructions, 02/2018, C79000-G8976-C468-02...
  • Page 103 – Add redundant ST7cc/cc partner Activate the option for the selected telecontrol connection between application and module. – Redundant application Select the second application from the "Redundant application" drop-down list. TIM 1531 IRC Operating Instructions, 02/2018, C79000-G8976-C468-02...
  • Page 104: Data Points

    Address areas of the PLC tags are input, output or bit memory areas on the CPU. Note Number of PLC tags Remember the maximum possible number of PLC tags the can be used for data point configuration in the section Performance data and configuration limits (Page 25). TIM 1531 IRC Operating Instructions, 02/2018, C79000-G8976-C468-02...
  • Page 105 Project > directory of the relevant station > Local modules > required communication module By double-clicking on the entry, the data point or message editor opens. Figure 4-8 Configuring data points and messages TIM 1531 IRC Operating Instructions, 02/2018, C79000-G8976-C468-02...
  • Page 106 ● In the name box of the PLC tag, enter part of the name of the required data source. All configured PLC tags and tags of the data blocks whose names contain the letters you have entered are displayed. Select the required data source. TIM 1531 IRC Operating Instructions, 02/2018, C79000-G8976-C468-02...
  • Page 107 If you click in a parameter box of an object in the table with the right mouse key, you can use the functions named with the shortcut menu (copy, paste, cut, delete). You can paste cut or copied objects within the table or in the first free row below the table. TIM 1531 IRC Operating Instructions, 02/2018, C79000-G8976-C468-02...
  • Page 108 When you import this file into another module, the changed parameter values of the CSV file are adopted in the data point configuration of this module. TIM 1531 IRC Operating Instructions, 02/2018, C79000-G8976-C468-02...
  • Page 109 You can import the data points from several modules into the modules of a different project. To do this in the import dialog select all the required CSV files with the control key. TIM 1531 IRC Operating Instructions, 02/2018, C79000-G8976-C468-02...
  • Page 110 If a PLC tag with a matching name is found for a data point by the repair function, the assignment is restored. However the data type of the tag is not checked. After the assignment repair make sure that you check whether the newly assigned PLC tags are correct. TIM 1531 IRC Operating Instructions, 02/2018, C79000-G8976-C468-02...
  • Page 111: General" Tab

    During the configuration of the user data to be transferred by the module, each data point is assigned a protocol-specific data point type. The data point types supported by the module along with the compatible S7 data types are listed below. They are grouped according to format (memory requirements). TIM 1531 IRC Operating Instructions, 02/2018, C79000-G8976-C468-02...
  • Page 112 DInt / UDInt / Data output Dat12D_R DWord / Real Parameter output Par12D_R Parameter input Par12D_S Only ST7-TIM as master station or node station See below, section "1: Mirroring back” See below, section "2: Data block" TIM 1531 IRC Operating Instructions, 02/2018, C79000-G8976-C468-02...
  • Page 113: Process Image, Type Of Transmission, Event Classes

    The values are sent only after a query by the communications partner - see below "Transfer after call" in the "Types of transmission" section - or along with a message from the send buffer that needs to be transferred immediately. TIM 1531 IRC Operating Instructions, 02/2018, C79000-G8976-C468-02...
  • Page 114 The current value of the data point is entered in the image memory. New values of a data point overwrite the last stored value in the image memory. After being called by the communications partner, the current value at this time is transferred. TIM 1531 IRC Operating Instructions, 02/2018, C79000-G8976-C468-02...
  • Page 115: Read Cycle

    "Communication with the CPU" parameter group with the "Max. number of write jobs" parameter. The tags whose number exceeds this value are then written in the next or one of the following cycles. TIM 1531 IRC Operating Instructions, 02/2018, C79000-G8976-C468-02...
  • Page 116: Trigger" Tab

    If the memory area of a trigger tag is in the bit memory or in a data block, the module resets the trigger tag itself to 0 (zero) as soon as the value of the data point has been transferred. This can take up to 500 milliseconds. TIM 1531 IRC Operating Instructions, 02/2018, C79000-G8976-C468-02...
  • Page 117 ● The "Enable retentive saving" option is selected in the parameter group "Basic settings > Retentive saving of events" of the TIM. For information on the options and mechanisms of the parameter, see section Configuration (Page 58). TIM 1531 IRC Operating Instructions, 02/2018, C79000-G8976-C468-02...
  • Page 118: Threshold Value Trigger

    As soon as the process value reaches the upper or lower limit of the threshold value band, the value is saved. The newly saved value serves as the basis for calculating the new threshold value band. TIM 1531 IRC Operating Instructions, 02/2018, C79000-G8976-C468-02...
  • Page 119: Analog Value Preprocessing

    1.5 ... 2.5 would need to be configured. 4.22.8 Analog value preprocessing The TIM supports analog value preprocessing. For analog value data points, some or all of the functions described below can be configured. TIM 1531 IRC Operating Instructions, 02/2018, C79000-G8976-C468-02...
  • Page 120 In these cases, the read process value of the data point is entered in the image memory and transferred transparently before the preprocessing cycle of the threshold value calculation (500 ms) elapses. TIM 1531 IRC Operating Instructions, 02/2018, C79000-G8976-C468-02...
  • Page 121 Sequence of the analog value preprocessing options The values of analog inputs configured as an event are processed on the TIM according to the following scheme: Figure 4-12 Sequence of the analog value preprocessing TIM 1531 IRC Operating Instructions, 02/2018, C79000-G8976-C468-02...
  • Page 122 As soon as a value is acquired in the overflow or underflow range, mean value generation is stopped. The value 32767 / 7FFF or -32768 / 8000 is saved as an invalid mean value for the current mean value calculation period and sent with the next message. TIM 1531 IRC Operating Instructions, 02/2018, C79000-G8976-C468-02...
  • Page 123 If the value returns to the measuring range before the fault suppression time elapses, the current value is transferred. TIM 1531 IRC Operating Instructions, 02/2018, C79000-G8976-C468-02...
  • Page 124 The following values can be configured for the module as the smoothing factor. ● 1 = No smoothing ● 4 = Weak smoothing ● 32 = Medium smoothing ● 64 = Strong smoothing TIM 1531 IRC Operating Instructions, 02/2018, C79000-G8976-C468-02...
  • Page 125 -100.004 -32512 8100 -23.516 -117.593 Undershoot / wire break -32768 8000 < -3.518 < 1.185 < -17.593 Please note: The entry of the value 0 (zero) is interpreted as a deactivated limit value. TIM 1531 IRC Operating Instructions, 02/2018, C79000-G8976-C468-02...
  • Page 126: Command Output

    Only for the "PULSE_ON/OFF" option. When the time expires, the output is automatically reset. With zero, a set command output is not automatically reset. In this case, you need to reset the output via the user program. TIM 1531 IRC Operating Instructions, 02/2018, C79000-G8976-C468-02...
  • Page 127: Partner Stations

    For the trigger signal to send the message, the edge change (0 → 1) of the trigger bit "PLC tag for trigger" is evaluated that is set by the user program. When necessary, a TIM 1531 IRC Operating Instructions, 02/2018, C79000-G8976-C468-02...
  • Page 128 $$ can be a placeholder for data point types with a simple data type up to a size of 32 bits. ● PLC tag for value PLC tag in which the value to be sent is written. TIM 1531 IRC Operating Instructions, 02/2018, C79000-G8976-C468-02...
  • Page 129: Block Library Telecontrol St7

    9. Click "OK". The library is unpacked and opened. You can find the library in the STEP 7 project in the library view (task card) in the "Global libraries" pane under the name "Telecontrol ST7_<Version>". TIM 1531 IRC Operating Instructions, 02/2018, C79000-G8976-C468-02...
  • Page 130: Structure Of The Library

    Blocks for processing the communication mailbox of the S7-400 and S7-1500 – PCom Blocks for processing the communication mailbox of an S7-300 with P bus (CPU without partyline) – XCom Blocks for processing the communication mailbox of an S7-300 with X connections TIM 1531 IRC Operating Instructions, 02/2018, C79000-G8976-C468-02...
  • Page 131: Generating, Using And Calling The Blocks

    The following requirements must be met before generating the blocks: ● The communication modules must be networked with each other. ● A TIM 1531 IRC must be networked with a CPU via Ethernet. ● A TIM 1531 IRC cannot be assigned to a CPU.
  • Page 132 You should also use the optional blocks on the CPU depending on the communications tasks of the station. Drag the individual blocks with the mouse from the global library to the user program of the CPU. TIM 1531 IRC Operating Instructions, 02/2018, C79000-G8976-C468-02...
  • Page 133: Note On The "Basictask_*" Fcs

    Since the "Telecontrol ST7" library has no "know-how protection", you can ignore these error notifications. Note on the "BasicTask_*" FCs Versions of the "BasicTask" FC There are different versions of the "BasicTask" FC in the TD7 block library "Telecontrol ST7" for STEP 7 Professional. TIM 1531 IRC Operating Instructions, 02/2018, C79000-G8976-C468-02...
  • Page 134: Structure Of User Program For Td7Oncpu

    All data point typicals are FBs. An instance DB must be specified when an FB is called. The number of this instance DB is identical to the object number of the data point object. TIM 1531 IRC Operating Instructions, 02/2018, C79000-G8976-C468-02...
  • Page 135 The number of typicals to call and the required types depend on the amount and type of data to be sent and received. Note: The instance DBs of these FBs are referenced using the partner object number of the communication partner. TIM 1531 IRC Operating Instructions, 02/2018, C79000-G8976-C468-02...
  • Page 136 This happens if the configuration of the destination address has been completely or partially omitted in a partner for data point typicals. ("PartnerNo" and "Part- nerObjectNo" were not specified, so transmission to all known destination sub- scribers takes place.) PulseCounter When necessary PathStatus PartnerMonitor TIM 1531 IRC Operating Instructions, 02/2018, C79000-G8976-C468-02...
  • Page 137 FC. The best overview is provided when the number of the FC is identical to the subscriber number of the station. TIM 1531 IRC Operating Instructions, 02/2018, C79000-G8976-C468-02...
  • Page 138: Cyclic Interrupt Ob

    When a block that does not exist is called in an S7-300/400 CPU, the CPU normally changes to STOP. The diagnostics buffer indicates which FB, FC or DB was missing. You can then reload the missing block and restart the CPU. TIM 1531 IRC Operating Instructions, 02/2018, C79000-G8976-C468-02...
  • Page 139 FC ST7ObjectTest has a parameter "StopInOtherCases". Here you can specify what happens in other situations (STOP or continue running) if OB121 was called because another data block or an FB or FC is missing. TIM 1531 IRC Operating Instructions, 02/2018, C79000-G8976-C468-02...
  • Page 140: Types

    It contains the following information about the communication partner: – Subscriber number of the partner – Array index of the connection description – Subscriber type – Information whether the partner is local or remote. TIM 1531 IRC Operating Instructions, 02/2018, C79000-G8976-C468-02...
  • Page 141: Master Copies

    Sending typicals process data and send it to the remote partner. They have the ending "_S" Examples: Bin04B_S, Ana04W_S ● Receiving typicals Receiving typicals receive the data from their remote partner. They have the ending "_R" Examples: Bin04B_R, Ana04W_R TIM 1531 IRC Operating Instructions, 02/2018, C79000-G8976-C468-02...
  • Page 142 D = double word function Cmd = Command The amount of data R = real with "Dat256D_x" Set = Setpoint, parameter occupies three col- Par = Parameter umns. Dat = Data (any mixture of information types) TIM 1531 IRC Operating Instructions, 02/2018, C79000-G8976-C468-02...
  • Page 143 Receive maximum of 12 double words with any data / UDInt / DWord / Real DWord Dat256D_S Send maximum of 256 double words with any data DWord Dat256D_R Receive maximum of 256 double words with any data TIM 1531 IRC Operating Instructions, 02/2018, C79000-G8976-C468-02...
  • Page 144: Reoccurring Parameters

    Depending on the use of the typicals, some parameters are programmed differently. Note the typical use described below. TIM 1531 IRC Operating Instructions, 02/2018, C79000-G8976-C468-02...
  • Page 145 If the CPU of the node station maintains both connections to higher- level subscribers as well as to lower-level stations, a data frame with PartnerNo = 0 is transferred to all subscribers in the direction master station and in the direction stations. TIM 1531 IRC Operating Instructions, 02/2018, C79000-G8976-C468-02...
  • Page 146 (DB BasicData), an entry is also made in the diagnostics buffer (event ID B101). The CPU does not change to STOP. The block is then no longer processed, however, until the error in the programming has been corrected. TIM 1531 IRC Operating Instructions, 02/2018, C79000-G8976-C468-02...
  • Page 147 Data type: Range of 0 / 1 ... 32000 values: Default: Explanation: Object number of the partner The number of the object (= DB number) on the partner with which the block communicates. TIM 1531 IRC Operating Instructions, 02/2018, C79000-G8976-C468-02...
  • Page 148 If the programming is incorrect (< 1 or > 32000), an error message is entered in the diagnostic buffer (event ID B102). The CPU does not change to STOP. The block is then no longer processed, however, until the error in the programming has been corrected. TIM 1531 IRC Operating Instructions, 02/2018, C79000-G8976-C468-02...
  • Page 149 Data bit DBm.DBX 0.0 ... n.7 Explanation: Enable block processing • If processing is enabled, all the functions of the block execute. • The response is different if processing has not been enabled: TIM 1531 IRC Operating Instructions, 02/2018, C79000-G8976-C468-02...
  • Page 150 I 0.0 ... I n.7 range: Memory bit M 0.0 ... M n.7 L 0.0 ... L n.7 Data bit DBm.DBX 0.0 ... n.7 Using in typi- Bin04B_S, Ana04W_S, Cnt01D_S/Cnt04D_S, Set01W_R, Par12D_R, cals Dat12D_S, Dat256D_S TIM 1531 IRC Operating Instructions, 02/2018, C79000-G8976-C468-02...
  • Page 151 Default: FALSE Address Memory bit M 0.0 ... M n.7 range: L 0.0 ... L n.7 Data bit DBm.DBX 0.0 ... n.7 Using in typi- Bin04B_S, Ana04W_S, Cnt01D_S/Cnt04D_S, Set01W_R, Par12D_R, cals Dat12D_S, Dat256D_S TIM 1531 IRC Operating Instructions, 02/2018, C79000-G8976-C468-02...
  • Page 152 Data type: BOOL Default: FALSE Explanation: Permanent data transfer This parameter has no significance and is always = FALSE. Note The "Permanent" parameter is no longer supported, it has been retained to ensure compatibility. TIM 1531 IRC Operating Instructions, 02/2018, C79000-G8976-C468-02...
  • Page 153 Q 0.0 ... Q n.7 range: Memory bit M 0.0 ... M n.7 L 0.0 ... L n.7 Data bit DBm.DBX 0.0 ... n.7 Using in typi- Bin04B_R, Ana04W_R, Cnt01D_R/Cnt04D_R, Cmd01B_R, Set01W_S, cals Set01W_R, Par12D_S, Par12D_R, Dat12D_R TIM 1531 IRC Operating Instructions, 02/2018, C79000-G8976-C468-02...
  • Page 154: Time Stamp

    Day * 1 Hour * 10 Hour * 1 RecTimeStamp_2 Minute * 10 Minute * 1 Second * 10 Second * 1 Millisecond * 100 Millisecond * 10 Millisecond * 1 Time status TIM 1531 IRC Operating Instructions, 02/2018, C79000-G8976-C468-02...
  • Page 155: Analog Value Typical Ana04R_S

    These parameters apply to all 4 analog values in common; in other words, it is not possible to set the parameters for the individual analog values. For this reason, each typical should only acquire analog values that should be processed in the same way. TIM 1531 IRC Operating Instructions, 02/2018, C79000-G8976-C468-02...
  • Page 156 Range of TRUE / FALSE values: Default: FALSE Address Input I 0.0 ... I n.7 range: Memory bit M 0.0 ... M n.7 L 0.0 ... L n.7 Data bit DBm.DBX 0.0 ... n.7 TIM 1531 IRC Operating Instructions, 02/2018, C79000-G8976-C468-02...
  • Page 157 If you do not require parameters, simply leave them open. The value 0 is transferred for these analog inputs in the data frame. Parameter: SamplingPeriod Declaration: INPUT Data type: Range of 0 ... 32767 [ms] values: TIM 1531 IRC Operating Instructions, 02/2018, C79000-G8976-C468-02...
  • Page 158 • When there is a general request to the station or a single request for the data frame. Parameter: SmoothingFactor Declaration: INPUT Data type: REAL Range of 1.0 (no smoothing) values: 4.0 (weak smoothing) 32.0 (medium smoothing) 64.0 (strong smoothing) Default: TIM 1531 IRC Operating Instructions, 02/2018, C79000-G8976-C468-02...
  • Page 159: Analog Value Typical Ana04R_R

    Explanation: You can select where the individual analog values received by the FB are output. Addresses of a data block and in the bit memory address area can be mixed as required. If you do not require parameters, simply leave them open. TIM 1531 IRC Operating Instructions, 02/2018, C79000-G8976-C468-02...
  • Page 160: Analog Value Typical Ana04W_S

    For this reason, each typical should only acquire analog values that should be processed in the same way. Parameter Parameter: PartnerNo PartnerObjectNo Enabled ImageMemory Conditional Unconditional For a description, see section Reoccurring parameters (Page 144). TIM 1531 IRC Operating Instructions, 02/2018, C79000-G8976-C468-02...
  • Page 161 ZeroLimitation Declaration: INPUT Data type: BOOL Range of TRUE / FALSE values: Default: TRUE Explanation: Zero limitation If this parameter is activated negative values are be suppressed and replaced with the value 0. TIM 1531 IRC Operating Instructions, 02/2018, C79000-G8976-C468-02...
  • Page 162 TIM and sent at a later point in time. The reason can, for example, be that the data frame is marked as "Conditional spontaneous", see parameter "Conditional". Parameter: MeanValueGeneration Declaration: INPUT Data type: BOOL Range of TRUE / FALSE values: TIM 1531 IRC Operating Instructions, 02/2018, C79000-G8976-C468-02...
  • Page 163 "FaultSuppressionTime" is set to 5 minutes, the mean value is only sent as invalid when more than 1/3 of the analog values acquired are above or below the overshoot or undershoot range in the current mean value calculation period. TIM 1531 IRC Operating Instructions, 02/2018, C79000-G8976-C468-02...
  • Page 164 The maximum value of 2 147 483 647 of a double integer must not be exceeded. When an overflow is detected, the inva- lid mean value of 8000 is transferred for the current mean value calculation period. TIM 1531 IRC Operating Instructions, 02/2018, C79000-G8976-C468-02...
  • Page 165 When MeanValueGeneration = TRUE, i.e. the analog values are sent as mean values, the "ThresholdValue" parameter has no meaning. Parameter: SmoothingFactor Declaration: INPUT Data type: Range of 1 (no smoothing) values: 4 (weak smoothing) 32 (medium smoothing) 64 (strong smoothing) Default: TIM 1531 IRC Operating Instructions, 02/2018, C79000-G8976-C468-02...
  • Page 166 = smoothed value in the current cycle n = smoothed value in previous cycle n-1 = acquired value in the current cycle n k = smoothing factor Parameter: FaultSuppressionTime Declaration: INPUT Data type: Range of 0 ... 32767 values: Default: TIM 1531 IRC Operating Instructions, 02/2018, C79000-G8976-C468-02...
  • Page 167: Analog Value Typical Ana04W_R

    Receive 4 analog values as 16-bit values Parameter Parameter: PartnerNo PartnerObjectNo Enabled For a description, see section Reoccurring parameters (Page 144). Parameter: AnalogOutput_1 … _4 Declaration: OUTPUT Data type WORD Default: TRUE Explanation 0 (W#16#0) TIM 1531 IRC Operating Instructions, 02/2018, C79000-G8976-C468-02...
  • Page 168: Binary Value Typical Bin04B_S

    PartnerObjectNo Enabled ImageMemory Conditional Unconditional TimeStamp For a description, see section Reoccurring parameters (Page 144). Parameter: InputByte_1 … _4 Declaration: INPUT Data type: BYTE Range of See address range values: Default: 0 (B#16#0) TIM 1531 IRC Operating Instructions, 02/2018, C79000-G8976-C468-02...
  • Page 169 For the assignment of the 32 inputs from "InputByte_1" to "InputByte_4" to the 32 bits of the blocking mask, see the following table. InputByte_1 InputByte_2 InputByte_3 InputByte_4 DW#1 Parameter: InversionMask Declaration: INPUT Data type: DWORD TIM 1531 IRC Operating Instructions, 02/2018, C79000-G8976-C468-02...
  • Page 170: Binary Value Typical Bin04B_R

    Receive 4 bytes of binary information Parameter Parameter: PartnerNo PartnerObjectNo Enabled For a description, see section Reoccurring parameters (Page 144). Parameter: OutputByte_1 … _4 Declaration: OUTPUT Data type: BYTE Range of See address range. values: Default: 0 (B#16#0) TIM 1531 IRC Operating Instructions, 02/2018, C79000-G8976-C468-02...
  • Page 171: Command Typical Cmd01B_S

    The 1-out-of-n check is performed by FC Safe. Note FC Safe required With Cmd01B_S, data can only be transmitted when FC Safe is linked in cyclic program. Parameter Parameter: PartnerNo PartnerObjectNo For a description, see section Reoccurring parameters (Page 144). TIM 1531 IRC Operating Instructions, 02/2018, C79000-G8976-C468-02...
  • Page 172 FC Safe (see FC Safe, "InputError" parameter) and continues to be indicated as long as the error remains. Name: CommandInputByte_SW Declaration: IN_OUT Data type BYTE Range of See address range values: TIM 1531 IRC Operating Instructions, 02/2018, C79000-G8976-C468-02...
  • Page 173: Command Typical Cmd01B_R

    Safe. Appropriate error bits are set in the central data block BasicData where they can be queried by the software (see FC Safe). 5.7.1.11 Command typical Cmd01B_R Function Receive 1 byte commands (1-out-of-8 format) TIM 1531 IRC Operating Instructions, 02/2018, C79000-G8976-C468-02...
  • Page 174 • TRUE Multiple output is permitted. A newly received command is written to the current output byte. The command output time is restarted and applies to all pending commands. Parameter: CommandOutputTime Declaration: INPUT TIM 1531 IRC Operating Instructions, 02/2018, C79000-G8976-C468-02...
  • Page 175 To allow the command outputs to be reset both by the command typical itself as well as by the user program (when output time = 0), the parameter was declared as an IN_OUT parameter. TIM 1531 IRC Operating Instructions, 02/2018, C79000-G8976-C468-02...
  • Page 176: Counted Value Typicals Cnt01D_S / Cnt04D_S

    You can use the parameters "GeneralTriggerCommand" and "TriggerInput" at the same time. In this case the transfer is triggered both by an edge change 0 → 1 at "TriggerInput" and when a restore collective command is received. TIM 1531 IRC Operating Instructions, 02/2018, C79000-G8976-C468-02...
  • Page 177 FC PulseCounter (Page 239) and Cyclic interrupt OB (Page 138). The COUNTER data type cannot be preassigned a value. If you configure the Z0 placeholder, the corresponding counted value is not processed. TIM 1531 IRC Operating Instructions, 02/2018, C79000-G8976-C468-02...
  • Page 178: Counted Value Typicals Cnt01D_R / Cnt04D_R

    Counted value typicals Cnt01D_R / Cnt04D_R Function ● Cnt01D_S: Receive 1 counted value (32 bits) ● Cnt04D_S: Receive 4 counted values (32 bits) Parameter Parameter: PartnerNo PartnerObjectNo Enabled For a description, see section Reoccurring parameters (Page 144). TIM 1531 IRC Operating Instructions, 02/2018, C79000-G8976-C468-02...
  • Page 179 Range of TRUE / FALSE values: Default: FALSE Address Output Q 0.0 ... Q n.7 range: Memory bit M 0.0 ... M n.7 L 0.0 ... L n.7 Data bit DBm.DBX 0.0 ... n.7 TIM 1531 IRC Operating Instructions, 02/2018, C79000-G8976-C468-02...
  • Page 180 Range of TRUE / FALSE values: Default: FALSE Address Output Q 0.0 ... Q n.7 range: Memory bit M 0.0 ... M n.7 L 0.0 ... L n.7 Data bit DBm.DBX 0.0 ... n.7 TIM 1531 IRC Operating Instructions, 02/2018, C79000-G8976-C468-02...
  • Page 181 Since the parameter is an in-out parameter (declaration IN_OUT), direct I/O output of the counted value to PQD0 ...PQDn is not permitted. It is also difficult to specify local bit memory with this parameter type and this should not be used. TIM 1531 IRC Operating Instructions, 02/2018, C79000-G8976-C468-02...
  • Page 182: Data Typical Dat12D_S

    The transfer can be triggered by an edge change 0 → 1 at the "TriggerInput" input For time-driven transfer FC Trigger can be used. With "SendAll" you can also specify whether the transfer always includes all data or only the data double words that have changed. TIM 1531 IRC Operating Instructions, 02/2018, C79000-G8976-C468-02...
  • Page 183 You specify whether the entire area is transferred or only the changed part with the "SendAll" parameter. If the setting is FALSE, you need to trigger the transfer via the input parameter "TriggerInput". TIM 1531 IRC Operating Instructions, 02/2018, C79000-G8976-C468-02...
  • Page 184 Parameter: SendAll Declaration: INPUT Data type: BOOL Range of TRUE / FALSE values: TIM 1531 IRC Operating Instructions, 02/2018, C79000-G8976-C468-02...
  • Page 185 Example: P#DB20.DBX 100.0 DWORD 4 Remember the periods and spaces when entering the pointer! Note that the default value (null pointer) is not permitted. A pointer with a real address must be specified. TIM 1531 IRC Operating Instructions, 02/2018, C79000-G8976-C468-02...
  • Page 186: Data Typical Dat12D_R

    The block has parameters of the "ANY" type. Therefore, leave the "Optimized block access" attribute in the properties of the DB disabled. Parameter Parameter: PartnerNo PartnerObjectNo Enabled For a description, see section Reoccurring parameters (Page 144). Parameter: DataOutput Declaration: INPUT Data type: TIM 1531 IRC Operating Instructions, 02/2018, C79000-G8976-C468-02...
  • Page 187: Data Typical Dat256D_S

    "DataOutput", the "NewData" output is set to TRUE for one OB1 cycle. 5.7.1.16 Data typical Dat256D_S Function Send a maximum of 256 double words with any data content TIM 1531 IRC Operating Instructions, 02/2018, C79000-G8976-C468-02...
  • Page 188 If "TriggerInput" is triggered when "SendAllBusy" = TRUE, this leads to the "DataLoss" error message (status in the frame header) if the transfer is triggered again. Only when "SendAllBusy" = FALSE is set is the edge change 0 → 1 triggered at "TriggerInput". TIM 1531 IRC Operating Instructions, 02/2018, C79000-G8976-C468-02...
  • Page 189 DB disabled. Parameter Parameter: PartnerNo PartnerObjectNo Enabled Unconditional TimeStamp For a description, see section Reoccurring parameters (Page 144). Parameter: SendOnChange Declaration: INPUT Data type: BOOL Range of TRUE / FALSE values: Default: FALSE TIM 1531 IRC Operating Instructions, 02/2018, C79000-G8976-C468-02...
  • Page 190 With a dial-up connection, it is possible that the data frame is saved first on the TIM and sent at a later point in time. The reason can, for example, be that the data frame is marked as "Conditional spontaneous", see parameter "Conditional". TIM 1531 IRC Operating Instructions, 02/2018, C79000-G8976-C468-02...
  • Page 191 If there is a single request for this data object or within the framework of a general request, all data words of the area specified by "DataInput" are always transferred. Parameter: DataInput Declaration: INPUT Data type: TIM 1531 IRC Operating Instructions, 02/2018, C79000-G8976-C468-02...
  • Page 192 The edge change 0 → 1 has no effect whatsoever with an external "TriggerIn- put" as long as "SendAllBusy" indicates TRUE. The edge change 0 → 1 of "TriggerInput" only takes effect when "SendAllBusy" = FALSE. TIM 1531 IRC Operating Instructions, 02/2018, C79000-G8976-C468-02...
  • Page 193: Data Typical Dat256D_R

    48 bytes of net data of the output data area. Each time a detected data segment is received, this is indicated by a corresponding status (bit 1 to 22) of the "NewData" output parameter. TIM 1531 IRC Operating Instructions, 02/2018, C79000-G8976-C468-02...
  • Page 194 CPU, but not from the global library. Note DB with standard access The block has parameters of the "ANY" type. Therefore, leave the "Optimized block access" attribute in the properties of the DB disabled. TIM 1531 IRC Operating Instructions, 02/2018, C79000-G8976-C468-02...
  • Page 195 The time taken for the response to the single request is evaluated by the "MonitoringTime" parameter. Note: Consistency of the data output area across segments is only assured if the receive sequence was completed successfully. TIM 1531 IRC Operating Instructions, 02/2018, C79000-G8976-C468-02...
  • Page 196 Example: P#DB20.DBX 100.0 DWORD 200 Remember the periods and spaces when entering the pointer! Note that the default value (null pointer) is not permitted. A pointer with a real address must be specified. TIM 1531 IRC Operating Instructions, 02/2018, C79000-G8976-C468-02...
  • Page 197 The output is intended for user-specific further processing, for example to react in a specific way to receipt of new data. If you do not require the parameter, simply leave it open. Parameter: DataStatus Declaration: OUTPUT Data type: BYTE TIM 1531 IRC Operating Instructions, 02/2018, C79000-G8976-C468-02...
  • Page 198: Parameter Typical Par12D_S

    Parameter typical Par12D_S Function Send 1 to 12 parameter values (each 1 double word) and receive the current, locally valid parameter values from the partner. The 1-out-of-n check is performed by FC Safe. TIM 1531 IRC Operating Instructions, 02/2018, C79000-G8976-C468-02...
  • Page 199 The transmission of the entered values is then triggered by pressing this button. The entire data area specified by "ParameterInput" is transferred. TIM 1531 IRC Operating Instructions, 02/2018, C79000-G8976-C468-02...
  • Page 200 (applies to ST7cc, not for an S7 CPU). Note DB with standard access The block has parameters of the "ANY" type. Therefore, leave the "Optimized block access" attribute in the properties of the DB disabled. TIM 1531 IRC Operating Instructions, 02/2018, C79000-G8976-C468-02...
  • Page 201 The FB enters the detected 1-out-of-n error in the diagnostic buffer (event ID B172). As long as the error remains, the error status is indicated via the "InputError" output of FC Safe (see FC Safe, "InputError" parameter). TIM 1531 IRC Operating Instructions, 02/2018, C79000-G8976-C468-02...
  • Page 202 New parameters are read in again only when previously for the length of an OB1 cycle in the CPU, no software input via a command, setpoint or parameter block was detected. Parameter: ApplyRemoteParamAuto Declaration: INPUT Data type: BOOL Range of TRUE / FALSE values: TIM 1531 IRC Operating Instructions, 02/2018, C79000-G8976-C468-02...
  • Page 203 How the parameters at ParameterInput are processed depends on whether they are hardware or software entries and how the transfer of this data area is triggered. You will find more information on this in the section "Function" above. TIM 1531 IRC Operating Instructions, 02/2018, C79000-G8976-C468-02...
  • Page 204 Range of TRUE / FALSE values: Default: FALSE Address Output Q 0.0 ... Q n.7 range: Memory bit M 0.0 ... M n.7 L 0.0 ... L n.7 Data bit DBm.DBX 0.0 ... n.7 TIM 1531 IRC Operating Instructions, 02/2018, C79000-G8976-C468-02...
  • Page 205 M 0.0 ... M n.7 range: Data bit DBm.DBX 0.0 ... n.7 This is an in/out parameter (declaration IN_OUT). It is difficult to specify local bit memory with this parameter type and this should not be used. TIM 1531 IRC Operating Instructions, 02/2018, C79000-G8976-C468-02...
  • Page 206 M 0.0 ... M n.7 range: Data bit DBm.DBX 0.0 ... n.7 This is an in/out parameter (declaration IN_OUT). It is difficult to specify local bit memory with this parameter type and this should not be used. TIM 1531 IRC Operating Instructions, 02/2018, C79000-G8976-C468-02...
  • Page 207 The automatic reset would not work with a digital input. The result would be a constant synchronization as long as the parameter has a 1 signal. If you do not require the parameter, simply leave it open. TIM 1531 IRC Operating Instructions, 02/2018, C79000-G8976-C468-02...
  • Page 208: Parameter Typical Par12D_S

    (applies to ST7cc, not for an S7 CPU). Note DB with standard access The block has parameters of the "ANY" type. Therefore, leave the "Optimized block access" attribute in the properties of the DB disabled. TIM 1531 IRC Operating Instructions, 02/2018, C79000-G8976-C468-02...
  • Page 209 Range of TRUE / FALSE values: Default: FALSE Address Input I 0.0 ... I n.7 range: Memory bit M 0.0 ... M n.7 L 0.0 ... L n.7 Data bit DBm.DBX 0.0 ... n.7 TIM 1531 IRC Operating Instructions, 02/2018, C79000-G8976-C468-02...
  • Page 210 Memory" = TRUE. This ensures that the optional synchronization of the input and output area on the partner is always performed correctly (see Par12D_S, parameters "ApplyRemoteParamMan" and "ApplyRemoteParamAuto"). Parameter: ContinuousEnterFunct Declaration: INPUT Data type: BOOL Range of TRUE / FALSE values: TIM 1531 IRC Operating Instructions, 02/2018, C79000-G8976-C468-02...
  • Page 211 "LocalParameterInput" area by software. If you do not require the parameter, simply leave it open. Parameter: LocalParameterInput Declaration: INPUT Data type: Range of See address range values: Default: P#P 0.0 VOID 0 (null pointer) TIM 1531 IRC Operating Instructions, 02/2018, C79000-G8976-C468-02...
  • Page 212 Example: P#DB20.DBX 100.0 DWORD 4 Remember the periods and spaces when entering the pointer! Note that the preset value (null pointer) is not permitted. A pointer with a real address must be specified. TIM 1531 IRC Operating Instructions, 02/2018, C79000-G8976-C468-02...
  • Page 213 M 0.0 ... M n.7 Data bit DBm.DBX 0.0 ... n.7 This is an in/out parameter (declaration IN_OUT). It is difficult to specify local bit memory with this parameter type and this should not be used. TIM 1531 IRC Operating Instructions, 02/2018, C79000-G8976-C468-02...
  • Page 214: Fc Safe

    In every CPU in which commands and/or setpoints are acquired, the FC Safe needs to be called in OB1 to complete of all command and setpoint FBs. The FC has separate monitoring for entries via different system memory areas. They are divided into hardware entries and software entries: TIM 1531 IRC Operating Instructions, 02/2018, C79000-G8976-C468-02...
  • Page 215 • 1 ... 32000 Range of values for delay time Explanation: Delay time in ms for commands and setpoints that are input via hardware. A delay time of at least 1000 ms is recommended. TIM 1531 IRC Operating Instructions, 02/2018, C79000-G8976-C468-02...
  • Page 216 "EnterInput" input is re- leased. If you do not require the parameter, specify a memory or data bit in the memory area of the local data. TIM 1531 IRC Operating Instructions, 02/2018, C79000-G8976-C468-02...
  • Page 217 When an error is detected, the output remains set to the 1 signal until you request the group signal to be reset via the "ResetError" input. If you do not require the parameter, specify a memory or data bit in the memory area of the local data. TIM 1531 IRC Operating Instructions, 02/2018, C79000-G8976-C468-02...
  • Page 218: Setpoint Typical Set01W_S

    It can also be used for entering setpoints at an operator panel (OP). In this the adoption must be triggered by a function key on the OP. If you do not require the parameter, simply leave it open. TIM 1531 IRC Operating Instructions, 02/2018, C79000-G8976-C468-02...
  • Page 219 WORD Range of See address range. values: Default: 0 (W#16#0) Address Input words IW0 ... IWn range: PIW0 ... PIWn Memory words MW0 ... MWn LW0 ... LWn Data words DBm.DBW0 ... n TIM 1531 IRC Operating Instructions, 02/2018, C79000-G8976-C468-02...
  • Page 220 (event ID B172). Appropriate error bits are also set in the central data block BasicData where they can be queried by the software. For further details, refer to the description of FC Safe. Parameter: ReturnedSetpoint Declaration: OUTPUT Data type: WORD TIM 1531 IRC Operating Instructions, 02/2018, C79000-G8976-C468-02...
  • Page 221 After startup of the local or partner CPU, or after restoring a connection, an automatic general request ensures that the local currently valid status is dis- played at "LocalOperation". If you do not require the parameter, simply leave it open. TIM 1531 IRC Operating Instructions, 02/2018, C79000-G8976-C468-02...
  • Page 222: Setpoint Typical Set01W_R

    Receive 1 setpoint in the station as a 16 bit value or enter locally and return the local setpoint to the master station Parameter Parameter: PartnerNo PartnerObjectNo Enabled ImageMemory Conditional Unconditional TimeStamp For a description, see section Reoccurring parameters (Page 144). TIM 1531 IRC Operating Instructions, 02/2018, C79000-G8976-C468-02...
  • Page 223 Range of TRUE / FALSE values: Default: FALSE Address Input I 0.0 ... I n.7 range: Memory bit M 0.0 ... M n.7 L 0.0 ... L n.7 Data bit DBm.DBX 0.0 ... n.7 TIM 1531 IRC Operating Instructions, 02/2018, C79000-G8976-C468-02...
  • Page 224 WORD Range of See address range values: Default: 0 (W#16#0) Address Input words IW0 ... IWn range: PIW0 ... PIWn Memory words MW0 ... MWn LW0 ... LWn Data words DBm.DBW0 ... n TIM 1531 IRC Operating Instructions, 02/2018, C79000-G8976-C468-02...
  • Page 225 MW0 ... MWn LW0 ... LWn Data words DBm.DBW0 ... n Explanation: Setpoint output word. The setpoint sent by the partner object or entered locally at "LocalSetpointIn- put" is output at the "SetpointOutput" output. TIM 1531 IRC Operating Instructions, 02/2018, C79000-G8976-C468-02...
  • Page 226: Optional Blocks

    The only destination subscribers it knows are those to which it has a configured connection. At the receiving end, the data frame therefore contains the destination subscriber number but the destination object number is 0. TIM 1531 IRC Operating Instructions, 02/2018, C79000-G8976-C468-02...
  • Page 227 If a list already exists, FC ListGenerator checks to see whether the existing DB is long enough for the currently required number of references. If the length is adequate, 0 is entered as the content and the addresses are written again and sorted. TIM 1531 IRC Operating Instructions, 02/2018, C79000-G8976-C468-02...
  • Page 228: Fc Partnermonitor

    The FC can be called at any point in the cyclic user program (in OB1). If you want to monitor and control more than one subscriber, include an appropriate number of FC PartnerMonitor in the user program. TIM 1531 IRC Operating Instructions, 02/2018, C79000-G8976-C468-02...
  • Page 229 The time is retriggered as long as the signal 1 is present at the "PermanentCall_On" input. The time specified here applies to a permanent connection in a dial-up net- work as well as to a permanent connection (continuous polling) on a dedicated line. TIM 1531 IRC Operating Instructions, 02/2018, C79000-G8976-C468-02...
  • Page 230 0 = No connection 1 = Outgoing call activated 2 = Incoming call established 3 = Outgoing call established 4 = Permanent connection registered 5 = Permanent connection established 6 = Permanent connection disconnected TIM 1531 IRC Operating Instructions, 02/2018, C79000-G8976-C468-02...
  • Page 231 In-out parameters The following parameters are in/out parameters (declaration IN_OUT): • GeneralRequest • PermanentCall_On • PermanentCall_Off It is difficult to specify local bit memory with this parameter type and this should not be used. TIM 1531 IRC Operating Instructions, 02/2018, C79000-G8976-C468-02...
  • Page 232 Name: PermanentCall_On Declaration: IN_OUT Data type: BOOL Range of Input I 0.0 ... I n.7 values: Memory bit M 0.0 ... M n.7 Data bit DBm.DBX 0.0 ... n.7 TIM 1531 IRC Operating Instructions, 02/2018, C79000-G8976-C468-02...
  • Page 233 FC PartnerMonitor is used in a station. Name: PermanentCall_Off Declaration: IN_OUT Data type: BOOL Range of Input I 0.0 ... I n.7 values: Memory bit M 0.0 ... M n.7 Data bit DBm.DBX 0.0 ... n.7 TIM 1531 IRC Operating Instructions, 02/2018, C79000-G8976-C468-02...
  • Page 234: Fc Partnerstatus

    If you want to monitor more than 8 subscribers, include the appropriate number of FCs PartnerStatus in the user program. The partner can be an ST7 CPU or an ST7cc to which a connection was configured, or a local TIM. TIM 1531 IRC Operating Instructions, 02/2018, C79000-G8976-C468-02...
  • Page 235 Assignment of the status bits in the "PartnerStatus" output byte depending the parameters Partner1 ... "Partner8": Partner Value: • 0 = partner disrupted, not set in the parameters or unknown • 1 = partner OK TIM 1531 IRC Operating Instructions, 02/2018, C79000-G8976-C468-02...
  • Page 236: Fc Pathstatus

    FC calls need to be programmed in the user program program. Parameter Name: Partner Declaration: INPUT Data type: Range of 1 ... 32000 (subscriber number) values: Explanation: SINAUT subscriber no. of the partner Name: PathStatus Declaration: OUTPUT Data type: BYTE TIM 1531 IRC Operating Instructions, 02/2018, C79000-G8976-C468-02...
  • Page 237 Status bit Status bit Interfaces 5 (7) 4 (6) TIM 3V-IE TIM 4R-IE TIM 1531 IRC Ethernet "IE1" (X2) Ethernet "IE1" (X3) Ethernet "IE1" (X1) Ethernet "IE2" (X4) Ethernet "IE2" (X2) Serial "WAN1" (X1) Serial "WAN1" (X1) Ethernet "IE3" (X3) Serial "WAN2"...
  • Page 238 Block library TeleControl ST7 5.7 Master copies Coding options - TIM 1531 IRC Same coding of the configured interface for the main and the substitute path means that there is no path redundancy (only 1 interface configured). The path status is output via the bits of the main path (1st path).
  • Page 239: Fc Pulsecounter

    When reading out from the process image of the inputs (PII) count pulses could remain undetected. Explanation: Input byte for count pulses. The parameters for inputs for count pulse acquisition can can be set in bytes. TIM 1531 IRC Operating Instructions, 02/2018, C79000-G8976-C468-02...
  • Page 240 ... _4) in the actual counted value function blocks "Cnt01D_S" and "Cnt04D_S". These function blocks out read the assigned counter and then reset it. As the placeholder for parameters that are not required, it is recommended to specify the counter C0. TIM 1531 IRC Operating Instructions, 02/2018, C79000-G8976-C468-02...
  • Page 241: Fc St7Objecttest

    Explanation: The CPU should change to STOP in other error situations. For details of the parameter see above, section "Function". • TRUE: CPU changes to STOP. • FALSE: CPU continues to run. TIM 1531 IRC Operating Instructions, 02/2018, C79000-G8976-C468-02...
  • Page 242: Fc Testcopy

    "Watch and force tables" directory of the CPU. If the settings are to be retained even after CPU startup, they can also be stored directly in the start values of the individual BConnection instances of the DB BConnectData. TIM 1531 IRC Operating Instructions, 02/2018, C79000-G8976-C468-02...
  • Page 243: Db Testcopydata

    Receive filter: Start index no. Reserve SpareDBB14 BYTE SendCopy function Send_TgrmType BYTE Send filter: Message type (MT) Send_DestSubscr Send filter: Destination subscriber Send_DestObject Send filter: Destination object no. Send_SourceSubscriber Send filter: Source subscriber no. TIM 1531 IRC Operating Instructions, 02/2018, C79000-G8976-C468-02...
  • Page 244 2. This is followed by a separation sign AAAA for sent messages, EEEE for received messages. 3. Storage of the first message from the frame block. 4. Separation identifier AAAA, or EEEE: 5. Storage of the last frame from the message block. 6. Block end identifier FFFF. TIM 1531 IRC Operating Instructions, 02/2018, C79000-G8976-C468-02...
  • Page 245 FC TestCopy uses the following parameters for determining the minimum length for the DB TestCopyData: Parameter Parameter name Length Length of communication buffer 76 or 202 bytes * ComBuffer Minimum frame length 14 bytes MinTgrm Offset management area Offset 40 bytes TIM 1531 IRC Operating Instructions, 02/2018, C79000-G8976-C468-02...
  • Page 246: Operation Of Testcopymonitor

    The following assignment applies for the coding: ● Bit 0...3 Modes (0, 1, 2, 3) for die direction "RecvCopy" (copy receive frames) ● Bit 4...7 Modes (0, 1, 2, 3) for the direction "SendCopy" (copy send frames) TIM 1531 IRC Operating Instructions, 02/2018, C79000-G8976-C468-02...
  • Page 247 Write for RecvCopy function • Mode 3: Fill DB TestCopyData once, then set mode 0. Fill for SendCopy function • Fill for RecvCopy function • Delete the entire DB TestCopyData and reset to default TIM 1531 IRC Operating Instructions, 02/2018, C79000-G8976-C468-02...
  • Page 248 Copy all data frames regardless of the start index no. * "Xxxx": Placeholder for "Recv" or "Send" The desired filter tags can be easily added using the tag names of the TestCopy DB. TIM 1531 IRC Operating Instructions, 02/2018, C79000-G8976-C468-02...
  • Page 249: Fc Timetask

    Data byte 4 Minute * 10 Minute * 1 Data byte 5 Second * 10 Second * 1 Data byte 6 Milliseconds * 100 Milliseconds * 10 Data byte 7 Milliseconds * 1 Time status TIM 1531 IRC Operating Instructions, 02/2018, C79000-G8976-C468-02...
  • Page 250: Fc Trigger

    DB BasicData, data byte 7 (time status byte, bit 0 = 1) is marked as being valid. The accuracy with which FC Trigger operates depends on the accuracy of the time and on the OB1 cycle time. TIM 1531 IRC Operating Instructions, 02/2018, C79000-G8976-C468-02...
  • Page 251 Further explanation: Refer to the parameter "Month_Year". Name: Second_Day Declaration: INPUT Data type: WORD Explanation Specifies the values for seconds and day. Further explanation: Refer to the parameter "Month_Year". Name: Month_Year Declaration: INPUT Data type: WORD TIM 1531 IRC Operating Instructions, 02/2018, C79000-G8976-C468-02...
  • Page 252 "TriggerOutput" is set for one OB1 cycle. All time parameters can be used to specify the point in time. Parameters not required should be assigned FF. They are ignored during the check for reaching the time. TIM 1531 IRC Operating Instructions, 02/2018, C79000-G8976-C468-02...
  • Page 253 Only the specifications for hours, minutes and seconds are relevant. The date parameters are ignored. A time interval can also only be set in hours or in minutes or in seconds. Time parameters not required should be assigned FF. TIM 1531 IRC Operating Instructions, 02/2018, C79000-G8976-C468-02...
  • Page 254 The permitted ranges of values for the parameters Hours, Minutes, Seconds, Day, Month and Year were not kept to. Apart from FF, the following can be configured: Hours 00-23 01-31 Minutes 00-59 Month 01-12 Seconds 00-59 Year 00-99 TIM 1531 IRC Operating Instructions, 02/2018, C79000-G8976-C468-02...
  • Page 255: System Blocks

    The tasks of the various "BasicTask_*" FCs for handling basic communication tasks are the same in the respective CPU type. The only parameter of the FC is identical in each case. When the TD7onCPU is generated, the correct FC is automatically created in the respective CPU. TIM 1531 IRC Operating Instructions, 02/2018, C79000-G8976-C468-02...
  • Page 256: Db Basicdata

    DB BasicData is automatically generated in the required length preset with the subscriber and connection specific data and then saved in the block directory of the CPU. TIM 1531 IRC Operating Instructions, 02/2018, C79000-G8976-C468-02...
  • Page 257: Fc Create

    Auxiliary block for entering SINAUT system messages in the diagnostics buffer of the CPU. 5.7.3.5 FC Distribute Auxiliary block for distribution of the data located in the receive mailbox to the data point typicals responsible or to the node objects in the subscriber records. TIM 1531 IRC Operating Instructions, 02/2018, C79000-G8976-C468-02...
  • Page 258: Fc Search

    FB BCom also ensures that received frames are distributed immediately to the receive objects responsible in the CPU. To do this FB BCom calls FC Distribute as an auxiliary block. 5.7.4.2 BConnect FB Validity S7-1500 TIM 1531 IRC Operating Instructions, 02/2018, C79000-G8976-C468-02...
  • Page 259: Db Bconnectdata

    SFBs "BSEND" and "BRCV". FB BCom also ensures that received frames are distributed immediately to the receive objects responsible in the CPU. To do this FB BCom calls FC Distribute as an auxiliary block. TIM 1531 IRC Operating Instructions, 02/2018, C79000-G8976-C468-02...
  • Page 260: Db Bcomdata

    DB PComData Instance data block for the communication block FB PCom. The instance DB makes the communication mailbox available and contains the following: ● The receive mailbox (ReceiveBuffer) ● A send mailbox (SendBuffer) TIM 1531 IRC Operating Instructions, 02/2018, C79000-G8976-C468-02...
  • Page 261: Communication Blocks Xcom (Cpu300)

    X connections the DB is required more than once. DB XComData is automatically generated in the required length preset with the connection specific data and then saved in the block directory of the CPU. TIM 1531 IRC Operating Instructions, 02/2018, C79000-G8976-C468-02...
  • Page 262 Block library TeleControl ST7 5.7 Master copies TIM 1531 IRC Operating Instructions, 02/2018, C79000-G8976-C468-02...
  • Page 263: The Web Server (Wbm)

    Web browser either via the HTTP or HTTPS protocol: – http://<Address> – https://<Address> When selecting the protocol, make sure that it is released in the configuration of the TIM ("Web server" tab). TIM 1531 IRC Operating Instructions, 02/2018, C79000-G8976-C468-02...
  • Page 264: General Functions Of The Wbm

    The automatic update of the WBM display is disabled. Switches on the automatic update of the WBM display. Switches off the automatic update of the WBM display. Prints out the current WBM page TIM 1531 IRC Operating Instructions, 02/2018, C79000-G8976-C468-02...
  • Page 265: Start Page

    Start page Figure 6-1 Start page of the WBM The page shows general data of the module. General ● Station name Parameter configured in STEP 7 ● Module name Parameter configured in STEP 7 TIM 1531 IRC Operating Instructions, 02/2018, C79000-G8976-C468-02...
  • Page 266: System

    ● Rack ● Slot Module information ● Device name - not relevant - ● Module name Parameter configured in STEP 7 Vendor information ● Vendor ● Serial number Serial number of the device TIM 1531 IRC Operating Instructions, 02/2018, C79000-G8976-C468-02...
  • Page 267: Sd Card

    ● Adopt PC time If you click the "Adopt PC time" button, the TIM adopts the time of day from the connected PC. 6.5.4 ● NTP server list Shows the addresses of the configured NTP servers. TIM 1531 IRC Operating Instructions, 02/2018, C79000-G8976-C468-02...
  • Page 268: Web Server

    This page displays the most important version data of the firmware currently being used. If a new firmware version is available for the TIM, you will find this on the Internet pages of Siemens Industry Online Support: Link: (https://support.industry.siemens.com/cs/ww/en/ps/21764/dl) TIM 1531 IRC...
  • Page 269 Digitally signed and encrypted firmware prevents manipulation by third parties To be able to check the authenticity of the firmware, the firmware is digitally signed by Siemens. This allows manipulation by third parties to be detected and prevented. Note Do not operate during the update During the update of the firmware until the TIM restarts, the WBM is not blocked.
  • Page 270: Operating Status

    6.7.1 Diagnostics messages Diagnostics messages Table The table lists the last diagnostics events to occur on the TIM with the following information: ● Number Consecutive number ● Time Time of the diagnostics event TIM 1531 IRC Operating Instructions, 02/2018, C79000-G8976-C468-02...
  • Page 271 Below you will find several examples of events that are entered in the diagnostics buffer: ● TIM startup ● Change to the configuration ● Establishment/abort of the communications connection ● Time-of-day synchronization ● Power failure TIM 1531 IRC Operating Instructions, 02/2018, C79000-G8976-C468-02...
  • Page 272: Notifications

    ● The three Ethernet interfaces of the TIM are selected via the upper tabs. – X1 ... X3 ● The parameters of the selected interface are shown in the lower series of tabs: – IPv4 parameters – IPv6 parameters – Statistics TIM 1531 IRC Operating Instructions, 02/2018, C79000-G8976-C468-02...
  • Page 273 Behavior of the network setting: – Automatic – Manual setting for transmission speed and direction dependency ● Mode Used transmission speed and direction dependency (duplex/half duplex) ● Connection medium Connected medium (copper / optical) TIM 1531 IRC Operating Instructions, 02/2018, C79000-G8976-C468-02...
  • Page 274: Telecontrol

    ● Frames in the send mailbox Number of unsent frames waiting for transfer. Telecontrol 6.9.1 Partner information The tab shows you information on the communications partners and the connection status of the TIM. TIM 1531 IRC Operating Instructions, 02/2018, C79000-G8976-C468-02...
  • Page 275 TIM of the remote station – CPU CPU of the remote station – CP ... CP of the remote station CP 1243-8 IRC / CP 1542SP-1 IRC) ● Subscriber number Subscriber number of the partner TIM 1531 IRC Operating Instructions, 02/2018, C79000-G8976-C468-02...
  • Page 276 Local ID (decimal) of the S7 connection ● Local TSAP Local TSAP of the S7 connection ● Remote TSAP Remote TSAP of the S7 connection ● IP address IP address of the CPU TIM 1531 IRC Operating Instructions, 02/2018, C79000-G8976-C468-02...
  • Page 277 ● Time master Display of the active option: Yes / No Transmission path 1 / 2 ● Address IP address or WAN address of the interface of the TIM ● Interface Interface of the TIM TIM 1531 IRC Operating Instructions, 02/2018, C79000-G8976-C468-02...
  • Page 278 When the send buffer is 90% full, the TIM switches to the forced image mode. See also section Process image, type of transmission, event classes (Page 113). ● Overflow Send buffer 100% full TIM 1531 IRC Operating Instructions, 02/2018, C79000-G8976-C468-02...
  • Page 279: Data Points

    TIM can be recorded. The frame traffic of the TIM is recorded for a defined time or for a configurable number of frames. The log files are stored as PCAP files on the connected PC and can be evaluated with the Wireshark program, for example. TIM 1531 IRC Operating Instructions, 02/2018, C79000-G8976-C468-02...
  • Page 280 Via the input box, you specify the number of frames. Max. number of frames: 500 s ● Start With this button you start the logging. ● Stop With this button you stop the logging. TIM 1531 IRC Operating Instructions, 02/2018, C79000-G8976-C468-02...
  • Page 281: Diagnostics And Upkeep

    Here, you can obtain the following static information on the selected module: ● General General information on the module ● Diagnostics status Information on the diagnostics status ● Ethernet interface[X1/2/3] Address and statistical information TIM 1531 IRC Operating Instructions, 02/2018, C79000-G8976-C468-02...
  • Page 282 From a PC you can use HTTP/HTTPS to access the Web pages (WBM) of the TIM. The WBM returns a variety of information. For access to the content, refer to the section The Web server (WBM) (Page 263). TIM 1531 IRC Operating Instructions, 02/2018, C79000-G8976-C468-02...
  • Page 283: Online Functions

    8. Click on the icon next to the "PG/PC interface" drop-down list. The "Establish remote connection via telecontrol" dialog box opens. 9. Make the necessary entries in this dialog (see below) and click on "Connect". TIM 1531 IRC Operating Instructions, 02/2018, C79000-G8976-C468-02...
  • Page 284: Update Firmware

    Update firmware New firmware versions of the TIM If a new firmware version is available for the TIM, you will find this on the Internet pages of Siemens Industry Online Support: Link: (https://support.industry.siemens.com/cs/ww/en/ps/21764/cert) Firmware files have the file format *.upd.
  • Page 285 ● You have copied the new firmware file from your PC to the SD card using a suitable card reader. ● You have saved a backup file of the firmware file currently being used. TIM 1531 IRC Operating Instructions, 02/2018, C79000-G8976-C468-02...
  • Page 286 "RUN" flashes alternately green and yellow. • "ERROR" flashes. • "CONNECT" flashes. • Startup successfully completed, start of the firmware For the LED pattern during the restart, refer to the section Startup - LED pattern (Page 49). TIM 1531 IRC Operating Instructions, 02/2018, C79000-G8976-C468-02...
  • Page 287: Resetting To Factory Settings

    2. During the restart, continue to hold the switch in the "MRES" position. If the LED pattern of step 2 occurs (see below) the TIM is reset. For information on the switch settings, refer to the section Switch (Page 35). TIM 1531 IRC Operating Instructions, 02/2018, C79000-G8976-C468-02...
  • Page 288: Snmp

    SNMP is a protocol for management and diagnostics of networks and nodes in the network. To transmit data, SNMP uses the connectionless UDP protocol. The information on the properties of SNMP-compliant devices is entered in MIB files (MIB = Management Information Base). TIM 1531 IRC Operating Instructions, 02/2018, C79000-G8976-C468-02...
  • Page 289 The following groups of the MIB II standard are not supported: – Adress Translation (AT) – EGP – Transmission ● Siemens Automation MIB The following exceptions / restrictions apply to the TIM. Write access is permitted only for the following MIB objects of the system group: – sysContact –...
  • Page 290: Processing Status Of The Messages (Sms / E-Mail)

    The configured DNS server could not resolve specified domain name. 8413 Due to an internal error in the DNS subsystem, the domain name could not be resolved. 8414 An empty character string was specified as the domain name. TIM 1531 IRC Operating Instructions, 02/2018, C79000-G8976-C468-02...
  • Page 291 Recipient address ("To" or "Cc"). 8554 Transfer failed 85xx Other error message from the e-mail server Apart from the leading "8", the message corresponds to the three-digit error number of the SMTP protocol. TIM 1531 IRC Operating Instructions, 02/2018, C79000-G8976-C468-02...
  • Page 292: Module Replacement

    If you insert the SD card of the TIM being replaced in the new TIM, when it restarts it reads the configuration data from the SD card of the replaced TIM. TIM 1531 IRC Operating Instructions, 02/2018, C79000-G8976-C468-02...
  • Page 293: Technical Specifications

    Technical specifications Technical specifications Table 8- 1 Technical specifications - TIM 1531 IRC Technical specifications Article number 6GK7 543-1MX00-0XE0 Attachment to Industrial Ethernet Quantity 1 x gigabit interface (X1) • 2x Fast Ethernet interface (X2, X3) • Design RJ-45 jack, galvanically isolated...
  • Page 294 DIN rail for SIMATIC S7-1500 (article numbers 6ES7590-1Axx0-0AB0) Product functions ** * For details, refer to the IK PI catalog, cabling technology ** You will find further characteristics and performance data in the section Application and functions (Page 13). TIM 1531 IRC Operating Instructions, 02/2018, C79000-G8976-C468-02...
  • Page 295: Pinout Of The Ethernet Interfaces

    D2- bidirectional D4+ bidirectional D4- bidirectional ● X2 / X3 Fast Ethernet interfaces View of an RJ-45 jack Signal name Assignment Transmit Data + Transmit Data - Receive Data + Receive Data - TIM 1531 IRC Operating Instructions, 02/2018, C79000-G8976-C468-02...
  • Page 296: Pin Assignment Of The Serial Interface

    The DCE can transfer the data coming from the DTE. Schirm On connector housing DCE = data communication equipment (connected modem) DTE = data terminal equipment (TIM / CP) Fore the switchover RS-232 ↔ RS-485 see section . TIM 1531 IRC Operating Instructions, 02/2018, C79000-G8976-C468-02...
  • Page 297: Approvals

    EC L174, 01/07/2011, page 88-110 The EC Declaration of Conformity is available for all responsible authorities at: Siemens Aktiengesellschaft Division Process Industries and Drives Process Automation DE-76181 Karlsruhe Germany TIM 1531 IRC Operating Instructions, 02/2018, C79000-G8976-C468-02...
  • Page 298 Notes on use in hazardous areas according to ATEX / IECEx (Page 41). You should also note the information in the document "Use of subassemblies/modules in a Zone 2 Hazardous Area" that you will find on the Internet at the following address: Link: (https://support.industry.siemens.com/cs/ww/en/view/78381013) TIM 1531 IRC Operating Instructions, 02/2018, C79000-G8976-C468-02...
  • Page 299 Ta: Refer to the temperature class on the type plate Note the conditions for the safe deployment of the product according to the section Notes on use in hazardous areas according to UL HazLoc and FM (Page 42). TIM 1531 IRC Operating Instructions, 02/2018, C79000-G8976-C468-02...
  • Page 300 SIMATIC NET products are regularly submitted to the relevant authorities and approval centers for approvals relating to specific markets and applications. If you require a list of the current approvals for individual devices, consult your Siemens contact or check the Internet pages of Siemens Industry Online Support: Link: (https://support.industry.siemens.com/cs/ww/en/ps/21764/cert)
  • Page 301: Dimension Drawings

    Dimension drawings All dimensions in the dimension drawings are in millimeters. Figure A-1 TIM 1531 IRC: Front view and side view Figure A-2 TIM 1531 IRC: Side view with cover open TIM 1531 IRC Operating Instructions, 02/2018, C79000-G8976-C468-02...
  • Page 302 Dimension drawings TIM 1531 IRC Operating Instructions, 02/2018, C79000-G8976-C468-02...
  • Page 303: Accessories

    Power supply Power supplies for the TIM Excerpt from the Siemens program for power supplies SITOP and S7-1500: ● SITOP PSU100C 24 V / 0.6 A stabilized power supply, input: AC 120/230 V, output: DC 24 V / 0.6 A Article number: 6EP1331-5BA00 ●...
  • Page 304 24 MB and 32 GB. SMCs up to 32 GB memory capacity are supported. Article numbers: 6ES7954-8Lx02-0AA0 x is a placeholder for: F / L / P / T You will find the cards on the pages of the Siemens Industry Mall using the search term "6ES7954". TIM 1531 IRC...
  • Page 305: Routers, Modems, Antennas

    Link: (https://support.industry.siemens.com/cs/ww/en/view/109740148) • Modem MD4 Modems for ISDN networks Product notification on the Internet: Link: (https://support.industry.siemens.com/cs/ww/en/view/67637816) When using the serial interface for dedicated line and dialup networks, use suitable products of other vendors. TIM 1531 IRC Operating Instructions, 02/2018, C79000-G8976-C468-02...
  • Page 306: Modem Md720

    Transmission speed: 19200 bps Permitted range: 300 ... 57600 bps Wireless interface Antenna connector Number: Implementation: SMA socket Impedance: 50 Ω nominal Frequency bands GPRS / CSD: Quad band: 850, 900, 1800, 1900 MHz TIM 1531 IRC Operating Instructions, 02/2018, C79000-G8976-C468-02...
  • Page 307: Router Scalance M

    SHDSL router for IP communication via 2- and 4-wire cables, ITU-T standard G.991.2 / SHDSL.biz, SHDSL topology: Point-to point, bonding, line bridge mode; routing mode with VPN, firewall, NAT, 1 Ethernet interface with 4-port switch, 1 digital input, 1 digital output Article number 6GK5826-2AB00-2AB2 TIM 1531 IRC Operating Instructions, 02/2018, C79000-G8976-C468-02...
  • Page 308: Mobile Wireless Antennas

    1 digital input, 1 digital output – Version for Europe Article number: 6GK5876-4AA00-2BA2 – Version for North America Article number: 6GK5876-4AA00-2DA2 Information on the devices can be found on the Internet pages of Siemens Industry Online Support: Link: (https://support.industry.siemens.com/cs/ww/en/ps/15982) B.3.4 Mobile wireless antennas...
  • Page 309 You will find detailed information in the device manual. You will find this on the Internet on the pages of Siemens Industry Online Support: Link: (https://support.industry.siemens.com/cs/ww/en/view/48729835) TIM 1531 IRC Operating Instructions, 02/2018, C79000-G8976-C468-02...
  • Page 310: Cables, Connecting Cables

    TIM (RS-232) with a third-party modem Cable length 2.5 m 6NH7701-0AR Test cable Crossover connecting cable for connection of two TIM modules via their RS-232 interface (without the interposition of a null modem) Cable length 6 m TIM 1531 IRC Operating Instructions, 02/2018, C79000-G8976-C468-02...
  • Page 311 Accessories B.4 Cables, connecting cables Plug pin assignment of the standard connecting cables Figure B-3 6NH7701-4AL Figure B-4 6NH7701-5AN Figure B-5 6NH7701-4BN TIM 1531 IRC Operating Instructions, 02/2018, C79000-G8976-C468-02...
  • Page 312: Cable For Rs-485 Connection

    B.4.2 Cable for RS-485 connection Accessories for RS-485 operation of the serial interface Excerpt from the Siemens accessories program PROFIBUS or RS-485 operation ● Cable – PROFIBUS FC standard cable GP, bus cable 2-wire, shielded, special design for fast installation, sold by the meter 02YSY (ST) CY, 1x2x0.64 / 2.55-150 VI KF 40 FR...
  • Page 313: Step 7 V5 Configuration Of The Proxy

    For information on this, refer to section Exporting configuration data (Page 316). The data exported from STEP 7 V5 is adopted later in the STEP 7 Basic project for the S7-1200/1500 communication module. TIM 1531 IRC Operating Instructions, 02/2018, C79000-G8976-C468-02...
  • Page 314: Proxies In Hw Config

    HW Config catalog under: SIMATIC 300 > SINAUT ST7 > TIM IE They have the following names: ● PROXY CP1243-8 IRC ● PROXY TIM 1531 IRC Figure C-1 PROXY modules in the catalog TIM 1531 IRC Operating Instructions, 02/2018, C79000-G8976-C468-02...
  • Page 315: Special Features Of The Proxy Tim 1531 Irc

    C.3 Special features of the PROXY TIM 1531 IRC Special features of the PROXY TIM 1531 IRC Properties of the TIM or the "PROXY TIM 1531 IRC" Compared to TIM 4R-IE, the TIM 1531 IRC and PROXY TIM 1531 IRC have the following differences: ● Interfaces Similar to the TIM, the proxy has the following interfaces: –...
  • Page 316: Exporting Configuration Data

    (SDBs) just as with TIM modules. Follow the steps below to export the configuration data of the proxy: 1. Open the SINAUT diagnostics and service tool with the relevant project. 2. Select the proxy. TIM 1531 IRC Operating Instructions, 02/2018, C79000-G8976-C468-02...
  • Page 317 Opening the "SDB display" dialog The "SDB display" dialog opens. With the drop-down list box "System data blocks" you can display the contents of the individual SDBs. This is however not relevant for exporting the configuration data. TIM 1531 IRC Operating Instructions, 02/2018, C79000-G8976-C468-02...
  • Page 318 A text file with the data of all SINAUT SDBs is saved in the file directory. Note TXT file for STEP 7 in the TIA Portal. You then need the exported text file to import it into the respective successor module in STEP 7 Basic / Professional. TIM 1531 IRC Operating Instructions, 02/2018, C79000-G8976-C468-02...
  • Page 319: Documentation References

    Documentation references Where to find Siemens documentation ● Article numbers You will find the article numbers for the Siemens products of relevance here in the following catalogs: – SIMATIC NET - Industrial Communication / Industrial Identification, catalog IK PI – SIMATIC - Products for Totally Integrated Automation and Micro Automation, catalog...
  • Page 320 Siemens AG Link: (https://support.industry.siemens.com/cs/ww/en/ps/15923/man) SIMATIC NET MODEM MD2 Operating Instructions Siemens AG Link: (https://support.industry.siemens.com/cs/ww/en/view/17163799) SIMATIC NET MODEM MD3 Operating Instructions Siemens AG Link: (https://support.industry.siemens.com/cs/ww/en/view/17164329) SIMATIC NET MODEM MD4 Operating Instructions Siemens AG Link: (https://support.industry.siemens.com/cs/ww/en/view/17165032) TIM 1531 IRC Operating Instructions, 02/2018, C79000-G8976-C468-02...
  • Page 321 Link: (https://support.industry.siemens.com/cs/ww/en/ps/21162/man) /13/ SIMATIC NET SINAUT ST7 System Manual - Volume 1: Station control system - Band 2: Software (STEP 7 V5) - Volume 3: Software (STEP 7 Professional) Siemens AG Link: (https://support.industry.siemens.com/cs/ww/en/ps/21771/man) TIM 1531 IRC Operating Instructions, 02/2018, C79000-G8976-C468-02...
  • Page 322 Documentation references /13/ TIM 1531 IRC Operating Instructions, 02/2018, C79000-G8976-C468-02...
  • Page 323: Glossary

    Spontaneous / conditional spontaneous / unconditional spontaneous frame → Communications processor Module for expanded communications tasks that provides the CPU with additional interface types or communications options. Central Processing Unit Main processor of a SIMATIC controller TIM 1531 IRC Operating Instructions, 02/2018, C79000-G8976-C468-02...
  • Page 324 See also "Inter-station communication" Context: Telecontrol / SINAUT Distributed Network Protocol DNP3 TIM → Digital Subscriber Line Standards for transmission of telephone and Internet data with transmission speeds up to 1000 Mbps. TIM 1531 IRC Operating Instructions, 02/2018, C79000-G8976-C468-02...
  • Page 325 Memory area for the process image in a telecontrol module Each data frame is saved exactly one time in the image memory. New values of a data point overwrite the existing value in the image memory. See also send buffer TIM 1531 IRC Operating Instructions, 02/2018, C79000-G8976-C468-02...
  • Page 326 Standard for a digital transmission network for telephone, telefax, telex, teletext and datex- J/L/P services. The data of various services can be transferred simultaneously. Telephone connections normally operate at transmission speeds of 56 to 64 Kbps. TIM 1531 IRC Operating Instructions, 02/2018, C79000-G8976-C468-02...
  • Page 327 The WAN interfaces of the TIM are set to the network node type "Master station". MCC - Mobile Country Code PLMN → Messages Emails and SMS in the TeleControl context See also Data frame. MNC - Mobile Network Code PLMN → TIM 1531 IRC Operating Instructions, 02/2018, C79000-G8976-C468-02...
  • Page 328 ● Time-of-day synchronization ● Counted value storage ● Coordinated connection establishment and termination in a dial-up network ● Message indicating station startup and station failure ● Requests for and transmission of subscriber records TIM 1531 IRC Operating Instructions, 02/2018, C79000-G8976-C468-02...
  • Page 329 TIM. If a polled station has no stored data, it responds with an acknowledgment message and the polling cycle then continues by polling the next station. TIM 1531 IRC Operating Instructions, 02/2018, C79000-G8976-C468-02...
  • Page 330 The connection is multipoint-compliant; in other words, up to 32 subscribers can be connected. Request to send Signal in the data flow control S0 interface Basic interface of ISDN for connecting end devices TIM 1531 IRC Operating Instructions, 02/2018, C79000-G8976-C468-02...
  • Page 331 System for networking SIMATIC stations with a control station via WAN. The control center can also be a SIMATIC station or a PC-based control center, for example, WinCC with the SINAUT ST7cc add-on. TIM 1531 IRC Operating Instructions, 02/2018, C79000-G8976-C468-02...
  • Page 332 (SMSC) using a store-and-forward technique. They are buffered there and then forwarded to the recipient. The sender can query the status of the message in the SMS center or can request acknowledgment of delivery. SMSC Short Message Service Center TIM 1531 IRC Operating Instructions, 02/2018, C79000-G8976-C468-02...
  • Page 333 If the data has "normal" priority, it is first stored on the TIM. This data is then sent the next time a TIM 1531 IRC Operating Instructions, 02/2018, C79000-G8976-C468-02...
  • Page 334 SINAUT network. Subcycle Main cycle / sub-cycle → TD7 software SINAUT TD7 Library → Telecontrol Interface Module Communication module that handles all data transmission functions provided by the SINAUT system independently. TIM 1531 IRC Operating Instructions, 02/2018, C79000-G8976-C468-02...
  • Page 335 – The TIM 3V-IE versions have an RS-232 and an Ethernet interface. – The TIM 4R-IE has two RS-232 / RS-485 and two Ethernet interfaces. – The TIM 1531 IRC has two RS-232 / RS-485 and two Ethernet interfaces. ● DNP3 TIM A DNP3 TIM uses the DNP3 telecontrol protocol.
  • Page 336 Glossary TIM 1531 IRC Operating Instructions, 02/2018, C79000-G8976-C468-02...
  • Page 337: Index

    Firewall, 19 Firmware Partner status - diagnostics, 283 Version, 3 Path redundancy, 56 Forced image mode, 114 READ, 16 General request supervision time, 104 Recycling, 6 GET, 16, 16 Redundant telecontrol connection, 56 TIM 1531 IRC Operating Instructions, 02/2018, C79000-G8976-C468-02...
  • Page 338 Subscriber number, 57 Substitute path, 56 System data blocks, 316 Terminating resistor, 47 Time stamp, 20, 89, 104 Time-of-day synchronization, 20 Training, 6 Transmission mode, 117 Trigger tag - resetting, 116 Unsolicited, 117 TIM 1531 IRC Operating Instructions, 02/2018, C79000-G8976-C468-02...

Table of Contents