Checking Gaskets And Thermal Insulation Sections; Checking All Connections On The Heating Water Side For Tightness; Cleaning And Reconnecting The Condensate Drain System - Viessmann VITOCROSSAL 200 CM2 Service Instructions For Contractors

400 to 620 kw gas condensing boiler with matrix cylinder burner, for open flue and room sealed operation, permissible operating pressure 6 bar
Hide thumbs Also See for VITOCROSSAL 200 CM2:
Table of Contents

Advertisement

Cleaning the combustion chamber and heating...
Cleaning agent manufacturer's instructions

Checking gaskets and thermal insulation sections

1. Check the gaskets and packing cords in the boiler
door for damage.
2. Check the thermal insulation components on the
boiler door for damage.

Checking all connections on the heating water side for tightness

Danger
There is a risk of injury when working on pres-
surised components.
The connections on the heating water side must
only be opened after the boiler has been dep-
ressurised.
Only drain the boiler with a suction pump when
the boiler air vent valve is open.

Cleaning and reconnecting the condensate drain system

Note
Clean the inside of the condensate drain system at
least annually.
Commissioning, inspection, maintenance
(cont.)
Recommendation:
"Fauch 600" and "Antox 75 E"
Manufacturer:
Hebro Chemie GmbH
Rostocker Strasse 40
D-41199 Mönchengladbach
3. Replace any damaged components.
Note
Also check the connections for the control equipment
and the minimum pressure switch (low water indicator)
for tightness.
C
B
A
D
Fig. 22
25