CHAPTER
3
Learn what you can do with your Honeywell Midas®-M Detector, from commissioning to
Maintenance

Comissioning

Comissioning should be followed carefully and only performed by suitably trained personnel.
WARNING
Before carrying out any work, ensure local and site procedures are followed. Ensure that
the associated control panel is inhibited to prevent false alarms.
1. Ensure the detector is wired correctly.
2. Ensure that the correct sensor cartridge is fitted. (If the cartridge has not been stored at room
temperature, allow one hour for equilibration.)
3. Ensure the ON/OFF switch on the bottom of the mounting bracket assembly is in the ON
position.
4. Apply power to the system. Wait for a couple of minutes until the start-up routine completes.
5. After the start-up routine, the detector will display the Normal/Monitoring Operating Mode.
6. Perform a leak test to ensure all connections are secure. '
time.
7. Allow the detector to stabilize until the '
The maximum warm-up time is dependent on sensor type. Refer to individual cartridge data
sheets. Warm-up times are typically much faster.
8. Ensure the correct ID code is selected in Set-up > alarm menu
9. If this is a first-time start-up, the "
the 'O' button to clear the message.
Midas-M
Device & Web Operations
Detect New Cartridge ~
Waiting...
' message is no longer displayed after booting.
Warm-up
" message could be displayed. Press
29
' will be displayed on booting
User Manual