Viessmann Vitopend 100-W Installation And Service Instructions Manual page 51

Table of Contents

Advertisement

Further details regarding the individual steps
6.0 to 24.8 kW
Rated heating output
Natural gas (12T)
Nozzle ø
Nozzle pressure
based on a supply pressure of 20 mbar
7.5 to 30 kW
Rated heating output
Natural gas (12T)
Nozzle ø
Nozzle pressure
based on a supply pressure of 20 mbar
9.0 to 36 kW
Rated heating output
Natural gas (12T)
Nozzle ø
Nozzle pressure
based on a supply pressure of 20 mbar
Note
The values for nozzle pressure given in
the tables apply to the following ambi-
ent conditions:
Commissioning, inspection, maintenance
(cont.)
kW
mm
mbar
kW
mm
mbar
kW
mm
mbar
■ Air pressure: 1013 mbar
■ Temperature: 15 °C
Wobbe index see page 42.
6.0
24.8
1.20
1.20
1.0
15.5
7.5
30
1.20
1.20
1.0
15.8
9.0
36
1.20
1.20
1.0
13.9
51