Detector Connections - Honeywell FS20X Series User Manual

Fire and flame detectors
Hide thumbs Also See for FS20X Series:
Table of Contents

Advertisement

FS20X Fire and Flame Detectors

Detector Connections

The electronics module has six-pin and ten-pin keyed, removable connectors with
female screw terminal plugs. These connect to the two respective male connectors
with analog, digital, and relay interfaces (see
and connector for relay configurations. For digital and analog configurations, use the
six-pin plug (J1) and connector.
J2 Connector
Pin
Connection
1
Auxiliary NC
2
Auxiliary NO
3
Auxiliary COM
4
Alarm NC
5
Alarm NO
6
Alarm COM
7
Fault NO
8
Fault COM
9
+24 VDC
10
DC return
Figure 16. Electronics module, rear view (contacts shown with no power applied)
N OT I C E
Do not open the electronics module as this will void all warranties.
Avoid wire splices whenever possible. Good wiring practices simplify installation,
improve reliability, and facilitate maintenance. If wire splices are necessary, solder
and properly insulate them.
24
Figure
16). Use the ten-pin plug (J2)
J1 Connector
Pin
1
DC return
2
RS-485-A
3
RS-485-B
4
+24 VDC
5
4-20mA source
6
4-20mA sink
Connection

Advertisement

Table of Contents
loading

Table of Contents