FS20X Fire and Flame Detectors

Additional Performance Specifications

Flame Response Sensitivity
This table provides typical response times for various fuels:
Location
Fuel
Acetylene
Acetylene
Diesel
Ethanol
Hydrogen
IPA
Indoors
JP4
JP8
Methane
Methanol
n-Heptane 6 in X 6 in (15.2 cm X 15.2 cm)
Silane
Acetylene
Acetylene
Acetylene
Diesel
Ethanol
Hydrogen
Out-
IPA
doors
JP4
JP8
Methane
Methanol
n-Heptane 12 in X 12 in (0.3 m X 0.3 m)
Silane
40
MultiBand IR plus UV Detector
Fire Size
12 in (0.30 m) plume - medium flame
10 - 12 in (0.25 - 0.30 m) plume - lazy flame
6 in X 6 in (15.2 cm X 15.2 cm)
12 in X 12 in (0.3 m X 0.3 m)
3/8 in dia. (9.5 mm) orifice, 32 in (0.8 m) plume
6 in X 6 in (15.2 cm X 15.2 cm)
6 in X 6 in (15.2 cm X 15.2 cm)
6 in X 6 in (15.2 cm X 15.2 cm)
3/8 in dia. (9.5 mm) orifice, 32 in (0.8 m) plume
12 in X 12 in (0.3 m X 0.3 m)
1/32 dia (0.8 mm) orifice, 12 in (0.3 m) plume
12 - 16 in (0.30 - 0.41 m) plume - large flame
12 in (0.30 m) plume - medium flame
10 - 12 in (0.25 - 0.30 m) plume - lazy flame
12 in X 12 in (0.3 m X 0.3 m)
12 in X 12 in (0.3 m X 0.3 m)
3/8 in dia. (9.5 mm) orifice, 32 in (0.8 m) plume
12 in X 12 in (0.3 m X 0.3 m)
12 in X 12 in (0.3 m X 0.3 m)
12 in X 12 in (0.3 m X 0.3 m)
3/8 in dia. (9.5 mm) orifice, 32 in (0.8 m) plume
12 in X 12 in (0.3 m X 0.3 m)
1/32 dia (0.8 mm) orifice, 12 in (0.3 m) plume
Typical
Distance
Response
(ft/m)
Time
(seconds)
35/10.7
2
40/12.2
< 2
87/26.5
< 3
50/15.2
< 3
85/25.9
< 3
87/26.5
< 3
75/22.9
< 3
87/26.5
3
70/21.3
< 3
40/12.2
< 3
87/26.5
< 3
30/9.1
< 2
100/30.5
< 3
100/30.5
< 4
90/27.4
< 3
150/45.7
4
60/18.3
< 3
75/22.9
< 3
150/45.7
< 3
150/45.7
< 4
150/45.7
< 4
60/18.3
2
40/12.2
< 2
200/61.0
< 4
50/15.2
< 3