FS20X Fire and Flame Detectors
DIP Switch SW2
Figure 25. Eight-position DIP switch SW2
Alarm Relay
Latching
Non-latching
Sensitivity Levels
Very High (4)
High (3)
Medium (2)
Low (1)*
*The low sensitivity range is not compliant
with the requirements of EN 54-10:2002.
Auxiliary Relay
No Verify Time
5 Sec. Verify Time
10 Sec. Verify Time
20 Sec. Verify Time
32
SW2 Configuration
Default settings are highlighted in grey.
SW2-1
on
off
SW2-2
SW2-3
on
on
on
off
off
off
on
off
off
SW2-4
SW2-5
on
on
on
off
off
off
on
Factory Use Only
off
off
SW2
1 2 3 4 5 6 7 8
**If the fault relay is de-energized,
SW2-6
off
ON
OFF
Fault Relay
SW2-8
Energized
on
De-energized**
off
the detector will not report loss
of power faults.
Alarm Relay
SW2-7
Energized
on
De-energized
off