5 Installation Procedure

MECHATROLINK-II Option LED Display

Option has four LEDs that identify the option card or communication status.

Defining Option LED States

A - 1000-Series Label
LED
State
ON
RUN
OFF
ON
ERR
Flashing
OFF
ON
TX
OFF
ON
RX
OFF
*1
For more information about the communication error, refer to
5
Installation Procedure

Section Safety

DANGER
Electrical Shock Hazard. Do not examine, connect, or disconnect wiring on an energized drive. Before
servicing, disconnect all power to the equipment and wait for the time specified on the warning label at a minimum. The internal
capacitor stays charged after the drive is de-energized. The charge indicator LED extinguishes when the DC bus voltage
decreases below 50 Vdc. When all indicators are OFF, measure for dangerous voltages to make sure that the drive is safe. If
you do work on the drive when it is energized, it will cause serious injury or death from electrical shock.
WARNING
Electrical Shock Hazard. Do not operate the drive when covers are missing. Replace covers and shields
before you operate the drive. Use the drive only as specified by the instructions. Some figures in this section include drives
without covers or safety shields to more clearly show the inside of the drive. If covers or safety shields are missing from the
drive, it can cause serious injury or death.
WARNING
Electrical Shock Hazard. Only let approved personnel install, wire, maintain, examine, replace parts, and
repair the drive. If personnel are not approved, it can cause serious injury or death.
WARNING
Electrical Shock Hazard. Do not remove covers or touch circuit boards while the drive is energized. If you
touch the internal components of an energized drive, it can cause serious injury or death.
WARNING
Electrical Shock Hazard. Do not use damaged wires, put too much force on the wiring, or cause damage to
the wire insulation. Damaged wires can cause serious injury or death.
WARNING
Fire Hazard. Tighten all terminal screws to the correct tightening torque. Connections that are too loose or too
tight can cause incorrect operation and damage to the drive. Incorrect connections can also cause death or serious injury from
fire.
NOTICE
Observe correct electrostatic discharge (ESD) procedures when touching the option. Failure to obey can
cause ESD damage to the option circuitry.
10
Figure 4.2 Option LED Labels
Table 4.2 MECHATROLINK-II Operation LED Status
Status
Power supply on
Power supply off
Connection Error
SI-T3 error
Normal operation
Sending data
Not sending data
Receiving data
Not receiving data
B - GA500, GA700, GA800, CR700,
and CH700 Label
• The SI-T3 has power and is prepared for operation • An internal, self-diagnostic check
completed in the SI-T3
• The drive has no power
• The SI-T3 is not properly connected to the drive, or the SI-T3 has no power
• An internal, self-diagnostic check completed in the SI-T3
• The SI-T3 is not properly connected to the drive
*1
• Communication error
Error found during the SI-T3 self-diagnostic check
• The SI-T3 is properly connected to the drive
• Communication normal
Data is being sent (LED may appear to be flashing)
• No data being sent
• During reset
Data is being sent (LED may appear to be flashing)
• No data being received
• During reset
Troubleshooting on page
37.