Bosch PRAESENSA Installation Manual page 62

Public address and voice alarm system
Hide thumbs Also See for PRAESENSA:
Table of Contents

Advertisement

62
en | System controller | PRA-SCL/SCM/SCS
System size
    Networked devices
    Zones
Configuration
Power transfer
Power supply input A/B
    Input voltage range
    Input voltage tolerance
Power consumption (24 V)
    Duty mode
    Per active port
Supervision
Run fault (watchdog reset)
System integrity
    Fault report time
Site specific data integrity
    Fault report time
    Supervised message storage
Power supply input A/B
Network interface
Ethernet
    Protocol
    Redundancy
Audio/control protocol
    Network audio latency
    Audio data encryption
    Control data security
Ports
Environmental
Climatic conditions
Temperature
    Operating
    Storage and transport
Humidity (non condensing)
Air pressure (operating)
2019.11 | V1.00 |
Installation manual
250 (single subnet)
500
Web server/browser
24 to 48 VDC
20 to 50 VDC
3.9 W
0.4 W
All processors
< 100 s
< 1 hour
90 min
Undervoltage
100BASE‑TX,
1000BASE‑T
TCP/IP
RSTP
OMNEO
10 ms
AES128
TLS
5
-5 to +50 °C
(23 to 122 °F)
-30 to +70 °C
(-22 to 158 °F)
5 to 95 %
560 to 1070 hPa
Bosch Security Systems B.V.