4. Step: Entering Alarm Value
buttons. Then click the Apply button. In this case, if OK is pressed,
the change is recorded. If you want to change without recording,
press Back button.
5. Step: Entry of TRIP Alarm Value
Alarm temperature setpoint. The desired temperature value is set via
the arrow keys. Then click the Apply button. In this case, if OK is
pressed, the change is recorded. If you want to change without
recording, press the Back key.
6. Step: Selection of Parameters for Fan Study
Fan start temperature value must be higher than Fan stop
temperature value. The cursor keys move to the desired setting and
then the Select key is pressed. In this case, the background color of
the setting parameter is red, and the font color is white.
With the Up and Down arrow keys, the parameter setting is set to the
desired value and then the Back key is pressed. For each parameter,
you can switch between parameters using the Select and Back keys.
After the parameters are set, the Apply button is pressed for
recording. In this case, if OK is pressed, the change is recorded. If
you want to change without recording, press the Back key.
7. Step: Determination of Instantaneous Increase of Temperature Value
Value is set to the desired position. It refers to the temperature rise
value in the room. If it is desired to turn this feature off, the parameter
is set to OFF. Then click the Apply button. In this case, if OK is
pressed, the change is recorded. If you want to change without
recording, press the Back key. After recording, the device starts to
operate normally.
MAINPAGE
Trip, Fan and Error conditions on this screen at the same time.
11/10/2016 14:25
ch1
ch2
ch3
ch4
Menu
REPORT
It records and displays the faults and alarms that occurred during
the operation of the device.There are 40 recording memories
and when the recording memory is exceeded, the first recording
is deleted and a new recording is made.
Report records :
Fault(sudden temperature change)fault,
In the form of Alarm and Trip . Arrow keys switch between the
pages. When Exit button is pressed, return to homepage is made.
You can set Alarm Temperature Set value by Up, Down
The temperature set point for TRIP should be higher than the
There are five parameters for the fan setting.
With the arrow keys, Instantaneous Temperature Increase
Users can see the most needed temperature values, Manual Fan, Silent Alarm, Alarm,
System
Normal
85
ºC
83
ºC
84
ºC
32
ºC
Report
FAN
11/10/2016 14:25
ALARM SET.
Enter Alarm Set Value
130 ºC
Apply
11/10/2016 14:25
TRIP SET.
Enter Trip Set Value
150 ºC
Apply
11/10/2016 14:25
11/10/2016 14:25
FAN SET.
FAN SET.
Enter Fan Parameter Values
Enter Fan Parameter Values
Select Fan Modes
Select Fan Modes
CH123
CH123
Fan Switching On
Fan Switching On
100 ºC
100 ºC
Fan Switching Off
Fan Switching Off
85 ºC
85 ºC
1 min
1 min
Fan ON Time (Tp)
Fan ON Time (Tp)
Fan OFF Time (Ts)
Fan OFF Time (Ts)
1 hr
1 hr
Select
Select
Apply
Apply
11/10/2016 14:25
FAN SET.
Enter Fan Parameter Values
Select Fan Modes
CH123
Fan Switching On
100 ºC
Fan Switching Off
85 ºC
1 min
Fan ON Time (Tp)
Fan OFF Time (Ts)
1 hr
Select
Apply
11/10/2016 14:25
FAULT SET.
Enter Temprature Diff. Value
05 ºC/sec
Apply
11/10/2016 14:25
TRIP
85
ch1
ºC
Open
ch2
ºC
Circuit
84
ch3
ºC
32
ch4
ºC
Report
Menu
FAN
Reset
11/10/2016 14:25
No ChNo
Type
Date
01
ch2
Trip
23/09/17 15:35
02
ch2
Alarm
23/09/17 15:30
1/8
Exit