Screen Saver; Off Mode; Factory Settings; Technicial Specifications - KAEL Muhendislik Elektronik TC - PT100 Manual

For dry type medium voltage transformers
Table of Contents

Advertisement

3.10 SCREEN SAVER

Used to activate the screen saver or to change to the otomatic screen
protection mode. Choose one of the ON/OFF options by using the Up/Down
buttons and press the Apply button. If the OK button is pressed, all changes
will be saved into the memory. To discard the changes made, press the Back
button. If Screen saver is running in the ON mode while screen shows the
Mainpage, then the screen saver is activated after 5 minutes later and only the
status bar is shown on the screen. If the screen saver is running in the OFF
mode, the screen will refresh itself every 5 minutes automatically.

OFF Mode

11/10/2016 14:25
85
ch1
ºC
Screen will be
83
ch2
ºC
refreshed after
84
5 seconds
ch3
ºC
32
ch4
ºC
Menu
FAN

4. FACTORY SETTINGS

If you press return to factory settings, the device returns to its original settings. The Language, Temperature
Unit, Channel 4, Alarm, Trip, Fan, Fault settings are entered in order.
Date and time should be checked.
NOT1: The password is reset.
NOT2: After a few seconds of pressing the return to factory settings button, it will be directed to the opening screen
Temperature Unit
Channel 4 (Ch4) Setting
Alarm Set Value
Trip Set Value
Fan working mode
Fan Start Value
Fan Stop Value
Fan ON time (Tp)
Fan OFF time (Ts)
Fault (∆T) Temperature Change Value : 5 ºC/s
Password Usage
Date – Time

Technicial Specifications

97 mm
96 mm
Report
: ºC
: off (disabled)
: 130 ºC
: 150 ºC
: CH123
: 100 ºC
: 85 ºC
: 1 minute
: 1 hour
: off (disabled)
: Must be set.
Operating Voltage (Un)
Operating Frequency
Supply Power Consumption
Relays (4 pieces)
Screen
Device Protection Class
Terminal protection class
Accuracy
Sensor Type
Ambient Temperature
EMC - Immunity
EMC - Emission
56 mm
Installation Type
Dimensions
11/10/2016 14:25
SCREEN SAVER
Screen Saver Settings
ON
ON Mode
11/10/2016 14:25
Press a key...
: 24.... 240 VAC / DC (±10%)
: 50/60 Hz
: < 5VA
: max.16A/240 Vac
: 2,4" color TFT
: EN 60529
IP 40
: IP 00
: ±1% fully scale ±1 digit
: RTD sensor, Pt100 type, 3 wire
(max. 1.5mm²)
: - 20 °C .... + 60 °C
: EN 61000-6-2
: EN 61000-6-3
: to panel cover from front
: 96x96x56 mm
Apply

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents