en | Connections
Caution!
Compliance with EN50130-4 Alarm Standard – CCTV for Security Applications
To meet the requirements of the EN50130-4 Alarm Standard, an ancillary uninterruptable
!
power (UPS) supply is necessary. The UPS must have a Transfer Time between 2–6 ms and a
Backup Runtime of greater than 5 seconds for the power level as specified on the product
datasheet.
11.3

Ethernet Connections

Caution!
Ethernet cables must be routed through earth-grounded conduit capable of withstanding the
!
outdoor environment.
Cable Type
Maximum Distance
Ethernet
Terminal Connector
High PoE
Note: Consult the National Electrical Code (NEC) or other regional standards for cable
bundling requirements and limitations.
11.4

Camera Connections

All electrical and data connections from the camera are made from the connectors in the base
of the camera.
2019-11 | 2.1 |
Cat5e/Cat6 Shielded Twisted Pair (STP) Ethernet (directly to the
camera, or to a network switch between the camera and the network)
Note: Cat5e/Cat6 Shielded Twisted Pair (STP) cable is required in
order to meet European regulatory EMC standards.
100 m (330 ft)
10BASE-T/100BASE-TX, auto-sensing, half/full duplex
RJ45, Male
For models with attached illuminators: Use the 95 W midspan sold by
Bosch.
For models without illuminators: Use the 60 W midspan sold by Bosch,
or a midspan that is compliant to the IEEE 802.3at, class 4 standard.