Adjustment Of Heat Input Rate - Thermo Pride OD6FA072D48R Installation And Operation Manual

Oil fired furnace
Hide thumbs Also See for OD6FA072D48R:
Table of Contents

Advertisement

ii.
CARBON DIOXIDE (CO 2 ) OR OXYGEN (O 2 ): Take a CO 2 sample from flue passageway. It is
possible to achieve readings of up to 14% CO 2 (or 2% O 2 ), but it is better to have a slightly lower
CO 2 (or higher O
) reading with zero smoke measured. To achieve a lower CO 2 reading, open the air
2
band, or shutter, on the burner until zero smoke is measured.
For example, if a 13% CO 2 (or 3.5% O 2 ) is recorded at a trace of smoke, open the air shutter until zero
smoke is measured with a 12% CO
Adjustment of the burner to achieve a slightly lower CO 2 reading is recommended, although it slightly
reduces combustion efficiency, to keep the heating system within normal operating conditions though
external conditions may vary. Some "out-of-spec" conditions which may adversely affect burner
performance are, low oil supply temperature, dirty (contaminated) oil, low heating content (BTU/gal) oil,
cold heat exchanger surfaces, and downdraft conditions. By adjusting the burner in this manner, an
operational tolerance is established allowing the burner to function well, even under less than ideal
conditions. This results in less service and maintenance during a heating season.
iii. FLUE GAS TEMPERATURE: The flue gas temperature will vary to some extent depending on the
heat input rate, duct design, and the amount of air flow across the heat exchanger. The suggested
minimum net flue gas temperature is 350ºF, and the maximum gross flue gas temperature is 500ºF.
The lower the flue gas temperature, the higher the heating efficiency. However, stack temperatures
under 350ºF may result in condensation of water vapor in the flue gases, which in turn promotes
corrosion of the heat exchanger.
iv. TEMPERATURE RISE: Temperature rise is equal to the supply air temperature minus return air
temperature. Under steady state operating conditions, the temperature rise across the heating section
should be approximately 65ºF. A higher temperature rise will slightly lower the heating efficiency. A
lower temperature rise will slightly raise efficiency, but may cause condensation.
The supply air temperature should be measured in the supply air trunkline approximately 12 inches
downstream of the supply air outlet of the appliance.
NOTICE: Minimum temperature rise is 50ºF.; maximum temperature rise is 80ºF.
k.
After final adjustments are completed, tighten all screws to fix the positions of the burner air band.
l.
Check for the presence of oil leaks. Correct any oil leaks found.
m.
Reassemble the burner compartment cover.
n.
Start and stop the unit several times while checking for proper ignition of the burner. The flame
should ignite and stabilize without any significant rumbles or pulsations.

3. Adjustment Of Heat Input Rate:

This appliance was shipped from the factory with one, fixed, main burner nozzle sized to produce the low-
fire input rate using no. 2 fuel oil at the pump pressure shown on the rating label. The input rate can be
changed to the high-fire by switching to the larger burner nozzle and increasing the pump pressure.
The main burner oil nozzles for this unit were selected based upon the following assumed characteristic
values of the fuel oil suitable for use with this appliance design:
For no. 2 distillate fuel (domestic heating) oil having a higher heating value of 140,000 BTU per gallon
and a specific gravity of 0.88 @ 60ºF. (or "gravity" of 30º API @ 60ºF.).
It is possible to make minor adjustments to the heat input rate by adjusting the pump pressure.
Sizeable changes in input rate (especially reductions) should be made by replacing the burner nozzle.
To adjust the pump pressure to the main burner:
(or 4.5% O 2 ).
2
42

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents