Section 14. Checking Gas Input Rate - Thermo Pride Thermo Pace Downflow/Horizontal Furnace Installer's Information Manual

Table of Contents

Advertisement

5.
Attach manometer to 1/8" NPT manual shut-off valve
just installed.
6.
Slowly open equipment shut-off valve in gas supply line
just ahead of furnace.
"Operating Instructions" inside front door.
7.
Slowly open 1/8" NPT manual shut-off valve leading to
manometer.
8.
Read manifold pressure on manometer.
9.
Adjust manifold pressure by turning gas control
regulator adjusting screw clockwise to increase
pressure or tu rning counter-clockwise to decrease
pressure. Manifold pressure must be within allowable
range below:
??
Natural gas manifold pressure must be between
3.2 and 3.8 inches W.C.
??
Propane gas (LP) manifold pressure must be
between 9.7 and 10.3 inches W.C.
NOTE: For natural gas, if gas flow rate cannot be properly
set within these pressure ranges then you must change
main burner orifices to obtain proper gas flow rate.
10. Shut off furnace. Turn off gas at equipment shut-off
valve in gas supply line just ahead of furnace. Install
outlet-pressure-tap plug in gas control. Turn on gas.
11. Check regulator-adjustment-cover screw and gas
control plug for gas leaks. Use a commercial soap
solution made for leak detection.
12. Replace burner access panel using three screws
removed in step 2.
SECTION 14. CHECKING GAS
INPUT RATE
It is the installer's responsibility to see that the Btu input
rate of the furnace is properly adjusted. Under-firing could
cause inadequate heat, primary heat exchanger corrosion
and/or ignition problems. Over-firing could cause sooting,
flame impingement and/or overheating of heat exchanger.
WARNING: Failure to adjust furnace to the proper
firing rate could cause heat exchanger failure.
Depending on your local gas heating value and elevation,
you may need to adjust manifold pressure or change
orifices to get proper gas input rate. Check with your local
gas supplier to determine heating value (Btu/cu.ft.) of
natural gas in your area.
NOTE: If furnace is being installed at an altitude of more
than 2000 feet above sea level, you must derate the
furnace. See Section 15, "Derating For High Altitude."
NATURAL GAS INPUT RATE
Natural gas heating value (Btu/cu.ft.) can vary significantly.
Before starting natural gas input check, obtain gas heating
value at your location from local supplier. You will need a
stopwatch to measure actual gas input.
Page 26
Start furnace following
1.
Gas supply pressure must be between 5 and 7 inches
W.C. for natural gas. See Section 12, "Gas Supply
Pressure and Pilot Adjustment."
2.
Turn off all other gas appliances. You may leave pilots
on.
3.
Start furnace following "Operating Instructions" inside
front door. Let furnace warm up for 6 minutes.
4.
Locate gas meter.
fewest cubic feet of gas and how many cubic feet per
revolution it represents. This is usually one-half, one or
two cubic feet per revolution.
5.
With stopwatch, measure time it takes to consume two
cubic feet of gas.
??
If dial is one cubic foot per revolution, measure
time for two revolutions.
??
If dial is two cubic feet per revolution, measure
time for one revolution.
6.
Divide this time by two. This gives average time for
one cubic foot of gas to flow through meter. Example:
If it took 58 seconds for two-cubic feet to flow, it would
take 29 seconds for one-cubic foot to flow.
7.
Calculate gas input using this formula:
Gas Heating Value (Btu/cu.ft.)
X 3,600 sec/hr
Gas input =
Time (Seconds for
one cubic foot of gas)
Example: Assume it took 29 seconds for one cubic foot of
gas to flow and heating value of 1,000 Btu/cu.ft.
1,000 x 3,600
Gas Input =
29
If you left no other pilots on, this is the furnace gas input.
8.
If you left water heater, dryer or range pilots on, allow
for them in calculating correct furnace gas input. A
quick way is to allow 1,000 Btu per hour for a water
heater, 500 Btu per hour for dryer and 500 Btu per hour
for each range burner pilot.
Example:
If you left gas water heater, dryer, two range burner pilots
and one oven pilot on, allow:
Water heater pilot
Dryer pilot
2 range burner pilots
1 range oven pilot
Subtracting 3,000 Btu per hour from 124,138 Btu per hour
measured above equals 121,138 Btu per hour. This would
be the correct furnace gas input after allowing for pilots left
on.
9.
Manifold pressure may be adjusted within the range of
3.2 inches W.C. to 3.8 inches W.C. to get rated input ±
2 percent.
See Section 13, "Manifold Pressure
Adjustment."
If you cannot get rated input with
manifold pressure within the allowable range, you must
change orifices.
See Section 17, "Changing Main
Burner Orifices."
Determine which dial has the
= Btu/hour
= 124,138 Btu per hour
1,000 Btu per hour
500 Btu per hour
1,000 Btu per hour
500 Btu per hour
3,000 Btu per hour
Installer's Information Manual