Cooling Speed Set-ups
Factory
SW1 Switch
Settings
NOTE: All information is approximate. Results will vary by installation.
Air Flow
Fan
Control SW1
Switch
Clg.
Settings
Tonage
Cool
6-OFF
5-OFF
2
799
4-OFF
6-OFF
5-OFF
2.5
1017
4-ON
6-OFF
5-ON
3
1210
4-OFF
6-OFF
5-ON
3.5
1404
4-ON
6-ON
5-OFF
4
1622
4-OFF
6-ON
5
2010
5-ON
4-OFF
Figure 18-3: Cooling blower motor speed chart
Static
Pressure
Continous
in W.C.
0.2"
500
0.5"
0.2"
508
0.5"
0.2"
605
0.5"
0.2"
702
0.5"
0.2"
799
0.5"
0.2"
993
0.5"
30
Watts
Amps
102
1.16
165
1.83
149
1.68
238
2.60
213
2.35
306
3.27
304
3.32
419
4.40
462
4.83
584
5.96
813
8.18
1000
10.1