3: Current Draw Worksheet For Sd Slc Devices - Honeywell Silent knight 5895XL Installation And Operation Manual

Intelligent power module
Hide thumbs Also See for Silent knight 5895XL:
Table of Contents

Advertisement

Before You Begin Installing
Auxiliary Devices Current
Notification Appliance Circuits
5495/5499 Power Supply
Notification Appliances Current
Total current ratings of all devices in system (line A + line B + C)
Total current ratings converted to amperes (line D x .001):
Number of standby hours:
Multiply lines E and F.
Alarm sounding period in hours. (For example, 5 minutes = .0833 hours)
Multiply lines E and H.
Add lines G and I.
1.
The FACP can only support 5 devices w/LED's on. This current draw has been added to the panels alarm current.
2.
The SK-DUCT housing contains a vacant mount for a SK-RELAY (sold separately). Current draw for the SK-RELAY is calculated by
increasing the SK-RELAY row of the calculation sheet by one for each SK-RELAY used with a SK-DUCT.
3.
SK-BEAM-T draws a maximum of 500mA from Auxiliary power only when the test feature is used. this should be considered when
determining auxiliary power capacity but not calculated into current requirements for day to day operation.
4.
If using door holders, you do not need to consider door holder current for alarm/battery standby, because power is removed during that
time. However, during normal operation, door holders draw current and must be included in the 6.0A total current that can be drawn
from the panel.
5.
Use next size battery with capacity greater than required.
6.
Total does not include isolator devices or accessory bases.
2.6.3 Current Draw Worksheet for SD SLC Devices
Use Table 2.5 to determine current requirements during alarm/battery standby operation when SD SLC devices are installed.
For each device use this formula:
5895XL Intelligent Power Module
(Current draw from battery)
Additional 5895XL
(Daisy-chained to this module)
Addressable SLC Devices
SD500-AIM
SD500-MIM
SD500-PS
SD500-ARM
SD505-HEAT
SD505-PHOTO
12
Table 2.4 Current Draw Worksheet for SK SLC Devices
Device
# of Devices
Refer to device manual for current rating.
5
Table 2.5 Current Draw Worksheet for SD SLC Devices
Device
This column
1*
(7 max.)
Current per Device
Alarm/Standby:
Alarm/Standby:
Alarm/Standby:
Alarm/Standby:
24 VDC
One input circuit:
Both input circuits: 30 mA
Alarm:
Alarm:
Alarm:
Alarm:
Total standby AH
Total alarm AH
Total ampere hours
required
# of Devices
Current per Device
X
This column
Standby
Alarm:
Standby
Alarm:
Standby/Alarm:
5895XL Manual - P/N 151142-L8:L 08/09/2017
Calculating Current Draw and Standby Battery
Standby
Current
mA
mA
mA
mA
mA
mA
mA
mA
15 mA
mA
mA
mA
mA
mA
A
H
AH
AH
Standby
Current
=
Current per number of devices.
40 mA
40 mA
mA
160
10 mA
mA
10
1
.55 mA
Alarm
Current
mA
mA
mA
mA
mA
mA
mA
mA
mA
mA
mA
mA
A
H
AH
5
Alarm
Current
160 mA
mA
mA
mA
mA
mA
mA
mA
mA
mA
mA
mA
mA
mA
mA