5895XL Board and Terminal Strip Description

2.4 5895XL Board and Terminal Strip Description
Figure 2.3 shows the 5895XL circuit board including location of terminals, the DIP switch for setting module ID, and the LED.
Terminal # and Label
1
L
2
G
3
N
4
X
5
O
6
X
7
O
8
X
9
O
10
X
11
O
12
X
13
O
5895XL Manual - P/N 151142-L8:L 08/09/2017
Figure 2.3 The 5895XL Board Layout
Table 2.1 : Terminal Strip Description and Electrical Ratings
Description
AC input (hot)
Earth ground
AC input (neutral)
I/O 6*
Flexput™ Circuit
I/O 5*
Flexput™ Circuit
I/O 4*
Flexput™ Circuit
I/O 3*
Flexput™ Circuit
I/O 2*
Flexput™ Circuit
Rating
Voltage
120/240 VAC,
2.7 A
50/60 Hz
1.4 A
N/A
N/A
120/240 VAC,
2.7 A
50/60 Hz
1.4 A
24 VDC
3.0 A Notification Circuits
100 mA Initiation Circuits
24 VDC
3.0 A Notification Circuits
100 mA Initiation Circuits
24 VDC
3.0 A Notification Circuits
100 mA
Initiation Circuits
24 VDC
3.0 A Notification Circuits
100 mA Initiation Circuits
24 VDC
3.0 A Notification Circuits
100 mA Initiation Circuits
Before You Begin Installing
Current
7

Advertisement