Honeywell SILENT KNIGHT Farenhyt Series Installation And Operation Manual

Honeywell SILENT KNIGHT Farenhyt Series Installation And Operation Manual

Intelligent power module

Advertisement

MODEL
RPS-1000
Intelligent Power Module
Farenhyt
Series
E C N : 1 1 - 0 3 1 7
Document 151153
Installation and
L
Rev:
Operations Manual
151153:L
ECN: 15-0644

Advertisement

Table of Contents
loading

Summary of Contents for Honeywell SILENT KNIGHT Farenhyt Series

  • Page 1 MODEL RPS-1000 Intelligent Power Module Farenhyt Series ™ E C N : 1 1 - 0 3 1 7 Document 151153 Installation and Rev: Operations Manual 151153:L ECN: 15-0644...
  • Page 3: Table Of Contents

    Contents Contents Section 1 Overview ..............................1-1 RPS-1000 Description ......................1-1 1.1.1 Maximum Number of SBUS Modules ................1-2 Agency Requirements ......................1-5 About This Manual ........................1-5 How to Contact Silent Knight ....................1-5 Section 2 Before You Begin Installing ....................2-1 What’s in the Box? ........................2-1 Environmental Specifications ....................2-1 Preventing Water Damage .......................2-1 RPS-1000 Board and Terminal Strip Description ..............2-2...
  • Page 4 Contents 3.5.6.1 Door Holder Power ....................3-17 3.5.6.2 Constant Power ......................3-17 3.5.6.3 Resettable Power ....................3-17 Conventional Relay Installation ....................3-17 Silent Knight Fire Product Warranty and Return Policy Manufacturer Warranties and Limitation of Liability 151153...
  • Page 5: Overview

    Overview 151153 Section 1 Overview RPS-1000 Description The RPS-1000 Intelligent Power Module provides additional power and circuits to the IFP-2000, IFP-1000, IFP-1000ECS, IFP-100 or IFP-100ECS FACPs. The RPS-1000 can power all IFP-2000, IFP-1000, IFP-1000ECS, IFP-100 or IFP-100ECS compatible modules, including SLC devices (via a Model 5815XL SLC Expander), remote annunciators (RA-1000);...
  • Page 6: Maximum Number Of Sbus Modules

    Overview 151153 1.1.1 Maximum Number of SBUS Modules The chart below shows the maximum number of compatible modules that can be used in an IntelliKnight installation. Modules can be distributed among the main panel SBUS and each additional RPS-1000 SBUS in virtually any combination. Module or Device Maximum Number RPS-1000 Intelligent Power Module...
  • Page 7 Model RPS-1000 Installation Manual 151153 Figure 1-2 Example RPS-1000 Installation Overview (Details Added)
  • Page 8: Agency Requirements

    Overview 151153 Agency Requirements The RPS-1000 has the same requirements as the main control panel. These requirements are listed in the IFP-1000 Installation Manual (PN 151139) or IFP- 1000ECS Installation Manual (PN 151460). About This Manual This manual covers installation of RPS-1000 hardware. Software configuration information is contained in the IFP-1000 Installation Manual (PN 151139) or IFP- 1000ECS Installation Manual (PN 151460).
  • Page 9: Before You Begin Installing

    Before You Begin Installing 151153 Section 2 Before You Begin Installing What’s in the Box? The Model RPS-1000 ships with the following hardware: • A cabinet with all hardware assembled • Two keys for the front door • Ten 4.7K ohm end-of-line resistors Note: For UL installations Model 7628 4.7k...
  • Page 10: Rps-1000 Board And Terminal Strip Description

    Before You Begin Installing 151153 RPS-1000 Board and Terminal Strip Description Figure 2-1 shows the RPS-1000 circuit board including location of terminals, the DIP switch for setting module ID, and the LED. Figure 2-1 The RPS-1000 Board Layout...
  • Page 11 Model RPS-1000 Installation Manual 151153 Table 2-1: Terminal Strip Description and Electrical Ratings Rating Terminal # and Label Description Voltage Current AC input (hot) 120/240 VAC, 2.7 A 50/60 Hz 1.4 A Earth ground AC input (neutral) 120/240 VAC, 2.7 A 50/60 Hz 1.4 A I/O 6*...
  • Page 12: Earth Fault Resistance

    Before You Begin Installing 151153 Earth Fault Resistance Table 2-2 lists the earth fault resistance detection for each applicable terminal on the FACP. Table 2-2: Earth Fault Resistance Values by Terminal Terminal Label Low Biased High Biased Terminal Function (Values in kohms) High High Number...
  • Page 13: Calculating Current Draw And Standby Battery

    Model RPS-1000 Installation Manual 151153 Calculating Current Draw and Standby Battery This section is for helping you determine the current draw and standby battery needs for your installation. 2.6.1 Worksheet Requirements The following steps must be taken when determining RPS-1000 current draw and standby battery requirements.
  • Page 14: Current Draw Worksheet

    Before You Begin Installing 151153 2.6.2 Current Draw Worksheet For each RPS-1000* in the installation, use this worksheet to determine current requirements during alarm/battery standby operation. (Copy this page if additional space is required.) Table 2-4: Current Draw Calculations Number of Standby Device Current per Device...
  • Page 15: Wiring Specifications

    Model RPS-1000 Installation Manual 151153 If you are using door holders, you do not need to consider door holder current for alarm/battery standby, because power is removed during that time. However, during normal operation, door holders draw current and must be included in the 6.0 A total current that can be drawn from the panel. Use next size battery with capacity greater than required.
  • Page 16 Before You Begin Installing 151153 These cases are marked in the chart with an asterisk (*). Maximum length can never be more than 6,000 feet, regardless of gauge used. (The formula used to generate this chart is shown in the note below). Table 2-5: Wire Distances Per Wire Gauge Wiring Distance: SBUS Modules to Panel Total Worst Case...
  • Page 17 Model RPS-1000 Installation Manual 151153 Wiring Distance calculation example: Suppose a system is configured with the following SBUS modules: 2 - RA-1000 Fire Annunciator 1 - RPS-1000 Intelligent Power Expander 1 - 5865 LED Fire Annunciator 1 - 5824 Parallel/Serial Interface The total worst case current is calculated as follows: RA-1000 Current Draw = 2 x .100 amps...
  • Page 18: Wire Routing

    Before You Begin Installing 151153 2.7.3 Wire Routing You must follow power-limited wiring techniques, which includes maintaining one- quarter inch spacing between power-limited and nonpower-limited circuits and separating high and low voltage circuits. RPS-1000 Board Figure 2-2 Wire Routing Example 2-10...
  • Page 19: Hardware Installation

    Hardware Installation 151153 Section 3 Hardware Installation RPS-1000 installation involves the following steps: • AC power (Section 3.1) and backup battery connection (Section 3.2). • Physical connection to the IFP-1000 or IFP-1000ECS FACP to the controlling RPS-1000 (see Section 3.3). •...
  • Page 20: Battery Connection

    Hardware Installation 151153 Battery Connection The RPS-1000 battery charge capacity is 7.0 to 33.0 AH. Use 12V batteries of the same AH rating. Determine the correct AH rating as per your current load calculation (see Section Table 2-4). Note: When your backup batteries requirements use backup batteries that are to large to fit into the RPS-1000 cabinet.
  • Page 21 Model RPS-1000 Installation Manual 151153 3. Configure the RPS-1000 module by adding it to the system (through JumpStart or manu- ally). You can also assign a name to the module. These procedures are described in the IFP-1000 Installation Manuals (PN 151139) or IFP-1000ECS Installation Manual (PN 151460).
  • Page 22: Setting The Device Id

    Hardware Installation 151153 3.3.1 Setting the Device ID SBUS devices on the IFP-2000 panel are addressed from 1 to 63 and are connected to either SBUS 1 or SBUS 2. Although the addressing scheme allows 63 SBUS devices to be connected to a panel, the actual number is limited by current draw and SBUS bandwidth usage.
  • Page 23: Connecting Sbus Modules To The Rps-1000

    Model RPS-1000 Installation Manual 151153 Connecting SBUS Modules to the RPS-1000 1. Connect SBUS modules to the RPS-1000 as shown in Figure 3-6 or Figure 3-7. 2. All SBUS modules must have an ID. Use the DIP switches on the module board to assign an ID number (1-31) to the module.
  • Page 24: Flexputs™ I/O Circuits

    Hardware Installation 151153 Figure 3-7 SBUS Class B Wiring to RPS-1000 ™ Flexputs I/O Circuits The six Flexput™ circuits are an innovative and versatile feature of the RPS-1000 panel. They can be used as: Class A or B notification circuits, Class A or B initiation circuits (either 2 or 4 wire detectors), or as auxiliary power (resettable, continuous, or door holder).
  • Page 25: Class B Notification Wiring

    Model RPS-1000 Installation Manual 151153 spacing in accordance with NFPA 72. Table 3-1: Approved Releasing Solenoids Manufacturer Part Number Rating Current Freq Asco T8210A107 24 VDC 3A max 0 Hz 8210G207 24 VDC 3A max 0 Hz 3.5.2.1 Class B Notification Wiring You must use an appliance from the list of compatible appliances in the Appendix A.
  • Page 26: Conventional Initiation Circuits

    Hardware Installation 151153 2. Configure the circuit for Class A in programming (see Section 7.5 of the IFP-1000 Instal- lation Manual PN 151139 or IFP-1000ECS Installation manual PN 151460). Regulated Figure 3-9 Class A Notification Appliance Circuit Configuration Note: In programming any point that uses multiple I/O circuits are always referred to as the lowest I/O circuit number used.
  • Page 27: Class A Inputs

    Model RPS-1000 Installation Manual 151153 2. Configure the circuit through programming (see Section 7.5 of the IFP-1000 Installation manual PN 151139 or IFP-1000ECS Installation manual PN 151460). UL Listed EOL Model 7628 4.7 k Figure 3-10 Class B Input Switches 3.5.3.2 Class A Inputs You can connect conventional Class A switches, such as waterflow switches and pull stations, directly to the I/O circuits of the RPS-1000 panel.
  • Page 28: Installing 2-Wire Smoke Detectors

    Hardware Installation 151153 3.5.4 Installing 2-Wire Smoke Detectors Any compatible U.L. listed two-wire smoke detector can be used with the RPS-1000 panel (see Appendix A for list of compatible smoke detectors). Figure 3-12 and Figure 3-13 illustrate how to connect a UL listed 2-wire detector to the control panel. Class B Installation To install a Class B two-wire smoke detector, wire as shown in Figure 3-12.
  • Page 29: Installing 4-Wire Smoke Detectors

    Model RPS-1000 Installation Manual 151153 Note: In programming any point that uses multiple I/O circuits are always referred to as the lowest I/O circuit number used. For example, Figure 3-13 uses both I/O circuit 5 and 6, so in programming it would be referred to as point 5.
  • Page 30: Auxiliary Power Configuration

    Hardware Installation 151153 Installing 4-Wire Class A Smoke Detectors Figure 3-15 illustrates how to install 4-wire Class A detectors. Conventions used for wiring 4-wire Class A loops: 1. Up to two Class A 4-wire loops can be connected to the control panel at once. 2.
  • Page 31 Model RPS-1000 Installation Manual 151153 2. Configure the auxiliary power output through programming for Door Holder, Constant or Resettable power. Figure 3-16 Flexput Circuits Used as Auxiliary Power 3.5.6.1 Door Holder Power Door holder is intended for fire door applications. When there are no alarms in the system and the panel has AC power, door holder circuits have 24-volt power present at their terminals.
  • Page 32 151153 Appendix A Compatible Devices A.1 Notification Appliances For proper operation, you must use polarized devices with a Model 7628 4.7k ohm EOL resistor on each loop. All supervised notification appliances used with the RPS- 1000 must be polarized. Note: Not all devices can use the Sync feature, be sure to check Table A-1 to ensure the device you have chosen will work with this feature.
  • Page 33 151153 Table A-1: Compatible Notification Appliances Manufacturer Model Audio Visual Type Vibrating Bell Vibrating Bell Single Stroke Bell 2700 -M. -R, -T, -Y, -Z Strobe 2701 Series Strobe 2705 Series Strobe 2820 Snyc Temporal Horn/Strobe 2821 Snyc Temporal Horn/Strobe 2824 Horn Strobe 5333 Multi-Tone Horn)
  • Page 34 Model RPS-1000 Installation Manual 151153 Table A-1: Compatible Notification Appliances Manufacturer Model Audio Visual Type 5378 8-Tone Horn/Strobe 5383 8-Tone Horn/Strobe with Sync Strobe 5386 8-Tone Horn/Strobe with Sync Strobe 5387 8-Tone Horn/Strobe with Sync Strobe 5388 8-Tone Horn/Strobe with Sync Strobe 5508 Single Gang Sync Strobe 5509...
  • Page 35 151153 Table A-1: Compatible Notification Appliances Manufacturer Model Audio Visual Type BLVCH Vibrating Chime H12/24-FC Horn H12/24W-FC Horn H12/24K-FC Horn HC12/24-FC Horn HC12/24W-FC Horn HC12/24K-FC Horn P2415-FC Horn/Strobe P2415W-FC Horn/Strobe P2415K-FC Horn/Strobe P241575-FC Horn/Strobe P241575W-FC Horn/Strobe P241575F-FC Horn/Strobe P241575K-FC Horn/Strobe P2430-FC Horn/Strobe P2430W-FC...
  • Page 36 Model RPS-1000 Installation Manual 151153 Table A-1: Compatible Notification Appliances Manufacturer Model Audio Visual Type HG124 Horn HS24-15 Horn/Strobe HS24-30 Horn/Strobe HS24-60 Horn/Strobe HS24-75 Horn/Strobe HS24-110 Horn/Strobe HS24-1575 Horn/Strobe GCC24 Multi Candella Horn/Strobe Ceiling Mount GCCR24 Multi Candella Horn/Strobe Ceiling Mount GCS24 Multi Candella Strobe Ceiling Mount GCSR24...
  • Page 37 151153 Table A-1: Compatible Notification Appliances Manufacturer Model Audio Visual Type Chime Chime CHSR 2-Wire Chime/Strobe CHSW 2-Wire Chime/Strobe Horn Horn Horn Horn WHT Wall 4x4 Horn Red Wall 4x4 HGRL Horn Red Wall 2x4 HGWL Horn WHT Wall 2x4 CHWL Chime WHT Wall 4x4 CHRL...
  • Page 38 Model RPS-1000 Installation Manual 151153 Table A-1: Compatible Notification Appliances Manufacturer Model Audio Visual Type P2WH-P 2-Wire Horn/Strobe High Candela PC2WH 2-Wire Horn/Strobe High Candela PC2WH-P 2-Wire Horn/Strobe High Candela P2RK 2-Wire Horn/Strobe PC2RK 2-Wire Horn/Strobe P2RHK 2-Wire Horn/Strobe High Candela PC2RHK 2-Wire Horn/Strobe High Candela 4-Wire Horn/Strobe...
  • Page 39 151153 Table A-1: Compatible Notification Appliances Manufacturer Model Audio Visual Type Strobe SCRK Strobe SRHK Strobe High Candela SCRHK Strobe High Candela SRL, SRL-P, SRL-SP* Strobe Red Wall 4x4 SWL, SWL-P, SWL-ALERT Strobe White Wall 4x4 SWL-CLR-ALERT* SCRL Strobe Red Ceil 4x4 SCWL Strobe White Ceil 4x4 SCWL-CLR-ALERT...
  • Page 40 Model RPS-1000 Installation Manual 151153 Table A-1: Compatible Notification Appliances Manufacturer Model Audio Visual Type AH-12 Horn AH-24 Horn AH-12WP Horn Weatherproof AH-24WP Horn Weatherproof AMT-241575W Multi-Tone Horn Strobe AMT-24MCW Mutli-Tone Horn Strobe AMT-241575W-NYC Multi-Tone Horn Strobe AMT-12/24 Multi-tone Horn AMT-12/24 NYC Multi-tone Horn AS-121575W...
  • Page 41 151153 Table A-1: Compatible Notification Appliances Manufacturer Model Audio Visual Type HS-24 Horn HS4-241575W Horn/Strobe HS4-24MCW Horn/Strobe HS4-24MCWH Horn/Strobe HS4-24MCC Horn/Strobe MIZ-24S Mini Horn Strobe MT-121575W MultitoneHorn Strobe MT-241575W Multitone Horn Strobe MT-24MCW Multitone Horn Strobe MTWP-2475W Multitone Horn Strobe MTWP-2475C Multitone Horn Strobe MTG-121575W...
  • Page 42 Model RPS-1000 Installation Manual 151153 Table A-1: Compatible Notification Appliances Manufacturer Model Audio Visual Type RSSR-2475W Strobe RSSR-2475C Strobe RSSR-24110C Strobe RSSA-24110W Strobe RSSB-24110W Strobe RSSG-24110W Strobe RSSR-24110W Strobe RSSA-24MCC Multi-Cd Strobe RSSB-24MCC Multi-Cd Strobe RSSG-24MCC Multi-Cd Strobe RSSR-24MCC Multi-Cd Strobe RSSWPA-2475W Strobe Weatherproof RSSWPA-24MCCH...
  • Page 43 151153 A.2 Door Holder Device The following UL listed door holder can be used with the RPS-1000: ESL DHS-1224 A.3 Two-Wire Smoke Detectors Table A-2 lists two-wire smoke detectors that are compatible with the panel. The table is organized by manufacturer. The columns show the number of detectors per loop that can be used.
  • Page 44 Model RPS-1000 Installation Manual 151153 Table A-2: Compatible Two-Wire Smoke Detectors Model Name or Number Compatibility ID Manufacturer (Base model name or number in # per Loop Head Base parentheses.) 425 (S10) 30 / loop 425C (S11) 30 / loop 425CR (S11) 30 / loop 425CRT (S11)
  • Page 45 151153 Table A-2: Compatible Two-Wire Smoke Detectors Model Name or Number Compatibility ID Manufacturer (Base model name or number in # per Loop Head Base parentheses.) SIH-24F (HS-224D OR HSD-224) HD-3 HB-5 30 / loop SLK-12 30 / loop SLK-24F (HS-224D) HD-3 HB-5 30 / loop...
  • Page 46 Model RPS-1000 Installation Manual 151153 Table A-2: Compatible Two-Wire Smoke Detectors Model Name or Number Compatibility ID Manufacturer (Base model name or number in # per Loop Head Base parentheses.) 2451 (B401B) 30 / loop 2451DH (DH 400) 30 / loop 2451TH (B401B) 30 / loop 2800...
  • Page 47 $50 to cover the extra shipping and handling costs over board only returns. Do not return batteries to . Honeywell has the authority to determine if a product is repairable. Products that are deemed un-repairable will be returned to the customer.
  • Page 48 • Repairs and returns should be sent to: Honeywell Fire Systems Attn: Repair Department / RA Number_______________________ 12 Clintonville Road Northford, CT 06472 USA Manufacturer Warranties and Limitation of Liability Manufacturer Warranties. Subject to the limitations set forth herein, Manufacturer warrants that the Products...
  • Page 50 Silent Knight 12 Clintonville Road Northford, CT 06472-1610 203-484-7161 Fax: 203-484-7118 www.silentknight.com www.farenhyt.com...