Connecting The 5895Xl To The Facp - Honeywell Silent knight 5895XL Installation And Operation Manual

Intelligent power module
Hide thumbs Also See for Silent knight 5895XL:
Table of Contents

Advertisement

Connecting the 5895XL to the FACP

Wire batteries in series to produce a 24-volt equivalent. Do not parallel batteries to increase the AH rating.
3.3 Connecting the 5895XL to the FACP
1.
Connect the 5895XL to the appropriate SBUS. The 5895XL can be connected directly to the FACP or can be daisy-chained to
another 5895XL. Figure 3.7 and Figure 3.8 show both connections.
2.
Use on-board DIP switch to assign an ID#. (See Section 3.3.1) Figure 2.3 shows the location of the DIP switches on the 5895XL
board.
3.
Configure the 5895XL module by adding it to the system (through JumpStart or manually). You can also assign a name to the
module. These procedures are described in the FACP Installation Manual.
(FACP SBUS)
5895XL
Terminals 30-33 are used only for connection
5895XL to the FACP or to the controlling 5895XL.
Use 5895XL Terminals 16-19 to connect other
SBUS modules (SLC expanders, annunciators,
5895XL Manual - P/N 151142-L8:L 08/09/2017
To Panel
Red
Battery Jumper
(P/N 140694)
Shipped With 5895XL
12V Battery
Figure 3.6 Battery Connection
5895XL Board
(5895XL-1)
Figure 3.7 Class B 5895XL Connection to FACP
Replace batteries every 5 years.
Black
12V Battery
5895XL Board
(5895XL-2)
Hardware Installation
To next 5895XL
and other SBUS
modules.
19