4.3.1.3 setting the date

In the general settings menu press /\ or \/ until the screen below appears:
the date can be changed by pressing set.
First set the days by pressing the - and + buttons and press ok. then set the month by pressing the - and +
buttons. Finally set the year by pressing the - and + buttons and close by pressing ok.

4.3.1.4 setting the module surface area

the surface area of the membrane modules is preset in the factory. this only needs to be changed whenever
the modules are replaced with another type.
In the general settings menu press /\ or \/ until the screen below appears:
the surface area can be changed by pressing set. set the surface area by pressing the - and + buttons and
press ok.

4.3.2 changing the flush settings

In the flush settings menu all the parameters concerning cleaning can be changed.
In the setup menu press /\ or \/ until the screen below appears:
12
EN

4.3.2.1 setting the start time

the default start time of the cleaning cycle is 01:00 (1:00 am).
In the flush setting menu press /\ or \/ until the screen below appears:
the start time can be changed by pressing set.
First set the hours by pressing the - and + buttons and press ok. then set the minutes by pressing the - and
+ buttons and close by pressing ok. In case multiple LineGuards are installated in parallel, the start time of
the cycles needs to be set out-of-phase with a 15 minutes time difference.

4.3.2.2 setting the cleaning cycle interval

the default cleaning cycle interval is one day. During low usage periods (if little or no water is being used)
the interval can be changed to, for example, seven days.
In the flush setting menu press /\ or \/ until the next screen appears:
the interval can be changed by pressing set.
set the interval by pressing the - and + buttons and press ok.

4.3.2.3 setting the duration of the forward flush

the forward flush is the duration in seconds the modules are forward flushed.
the default value of the duration of the forward flush is 10 seconds. In case of low quality water the duration
should be increased. In the flush setting menu press /\ or \/ until the screen below appears:
the duration of the forward flush can be changed by pressing set.
set the duration by pressing the - and + buttons and press ok.
13
EN