Current range
Remark
Output active power / typical
Constant overload current for a short
circuit when powering up, typical
Short-time overload current for a short
circuit during operation, typical
Duration of the overcurrent overload
capability for a short circuit during
operation
Remark
Can be connected in parallel to increase
the power rating
Remark
Number of devices that can be
connected in parallel to increase the
power rating, quantity
Output characteristic
Figure 6-2
SITOP PSU8200 1ph
Operating Instructions, 06.2014, C98130-A7633-A1-2-7629
6EP3333-8SB00-0AY0
(24 V/5 A)
0 to 5 A
At Ue<100 V / <200 V: 80% Ia rated
120 W
6 A
15 A
25 ms
Every minute
Yes
Switchable characteristic curve with switch A (see Figure 2-4 Status indicators
and signaling PSU8200 1ph (Page 12))
2
See Figure 6-3 Output characteristic
curve 6EP3333-8SB00-0AY0 stand-
alone operation (Page 34)
Startup delay/voltage rise
Technical data
6EP3334-8SB00-0AY0
(24 V/10 A)
0 to 10 A
+60 to +70 °C derating:
approx. 2% Ia rated/K
At Ue<100 V / <200 V: 80% Ia rated
240 W
12 A
30 A
25 ms
Every minute
2
See Figure 6-4 Output characteristic
curve 6EP3334-8SB00-0AY0 stand-
alone operation (Page 34)
6.2 Output
33