Propagation Of Electromagnetic Interference - Siemens SIMATIC RF600 System Manual

Hide thumbs Also See for SIMATIC RF600:
Table of Contents

Advertisement

RF600 system planning
4.10 Guidelines for electromagnetic compatibility (EMC)
● Feed the connected shield through to the module without interruption.
● Use braided shields, not foil shields.
Line and signal filter
● Use only line filters with metal housings
● Connect the filter housing to the cabinet chassis using a large-area low-HF-impedance
connection.
● Never fix the filter housing to a painted surface.
● Fix the filter at the control cabinet inlet or in the direction of the source.
4.10.4

Propagation of electromagnetic interference

Three components have to be present for interference to occur in a system:
● Interference source
● Coupling path
● Interference sink
Figure 4-19
If one of the components is missing, e.g. the coupling path between the interference source
and the interference sink, the interference sink is unaffected, even if the interference source
is transmitting a high level of noise.
The EMC measures are applied to all three components, in order to prevent malfunctions
due to interference. When setting up a plant, the manufacturer must take all possible
measures in order to prevent the occurrence of interference sources:
● Only devices fulfilling limit class A of VDE 0871 may be used in a plant.
● Interference suppression measures must be introduced on all interference-emitting
devices. This includes all coils and windings.
● The design of the system must be such that mutual interference between individual
components is precluded or kept as small as possible.
Information and tips for plant design are given in the following sections.
100
Propagation of interference
System Manual, 06/2019, J31069-D0171-U001-A22-7618
SIMATIC RF600

Advertisement

Table of Contents
loading

Table of Contents