Forced Charging; Protection Against Discharging; Purpose; Mode Of Operation - Siemens RVL471 Basic Documentation

Heating and domestic hot water controller
Table of Contents

Advertisement

With storage tank
sensor(s)
With thermostat(s)
Flow temperature
Siemens Building Technologies
HVAC Products

19.7 Forced charging

On operating line 131, it is possible to select whether or not forced charging of the
d.h.w. storage tank shall take place daily when d.h.w. heating is released for the first
time. With forced charging, the d.h.w. storage tank will also be charged when the d.h.w.
temperature lies between the switch-on and the switch-off temperature. The switch-off
point remains the same.
If d.h.w. heating is released 24 hours a day, forced charging takes place every day at
midnight. If activated, the legionella function also leads to forced charging.

19.8 Protection against discharging

19.8.1

Purpose

With plant types using a d.h.w. storage tank, protection against discharging is ensured
during overrun of the d.h.w. charging pump. This function makes certain that the d.h.w.
will not be cooled down again during pump overrun.
19.8.2

Mode of operation

If the flow temperature is lower than the d.h.w. storage tank temperature,
• pump overrun will be terminated prematurely (plant types x–1, and x–2)
• the changeover valve will be driven to the position "Heating circuit" (plant types x–3)
If the storage tank is equipped with two sensors, the sensor measuring the higher tem-
perature is considered.
The flow temperature is acquired with sensors B1 and B3, depending on the type of
plant, or obtained from the data bus (LPB) as the common flow temperature.
If the flow temperature is lower than the setpoint of the d.h.w. temperature,
• pump overrun will be terminated prematurely (plant types x–1, and x–2)
• the changeover valve will be driven to the position "Heating circuit" (plant types x–3)
The flow temperature is ascertained as follows, depending on the type of plant and the
bus connection:
Plant type
Controller with no bus (LPB) Controller with bus (LPB)
1–1
No protection against dis-
charging
1–2
Sensor B3
2–1
Sensor B1
2–2
Sensor B3
2–3
Sensor B1
3–1
Sensor B1
3–2
Sensor B3
3–3
Sensor B1
4–1
Sensor B1
4–2
Sensor B3
5–1
Sensor B1
5–2
Sensor B3
6–1
Sensor B1
6–2
Sensor B3
Basic Documentation RVL471
19 Function block "D.h.w. storage tank"
Common flow temperature from data bus
(if present), otherwise no protection
against discharging
Sensor B3
Sensor B1
Sensor B3
Sensor B1
Sensor B1
Sensor B3
Sensor B1
Sensor B1
Sensor B3
Sensor B1
Sensor B3
Sensor B1
Sensor B3
75/118
CE1P2524E
23.10.2002