Function block "Locking functions"

On the software side, all settings can be locked to prevent tampering.
Also, the settings required for district heat applications can be locked on the hardware
side.

26.1 Operating line

Line
Function, parameter
198
Locking of settings

26.2 Locking the settings on the software side

On operating line 198, the settings made on the controller can be locked on the soft-
ware side. This means that the settings made can still be called up on the controller,
but cannot be changed. Locking may comprise:
• All settings
• Only the settings required for the district heat parameters
The settings can be changed via the bus.
The procedure is the following:
1. Press buttons
and
2. Press buttons
,
3. Now, operating line 198 appears in the display. The following locking choices are
available:
0 = no locking
1 = all settings are locked
2 = Only the settings required for the district heat parameters are locked (operating
lines 101 to 117)
After locking all settings, the following setting elements remain operative:
• The buttons for selecting the operating lines
• The Info button
No longer operative will be:
• The buttons for the readjustment of values
• The bar for changing the basic setting of the heating curve
• The knob for readjustment of the room temperature
• The operating mode buttons
• The manual mode button
26.3 Locking the settings for district heat on the
hardware side
The settings for district heat (operating lines 101 through 117) can be locked by bridg-
ing terminals H3
M. This locking has priority over locking on the software side. If lock-
ings are made on the hardware side, settings via the bus can no longer be changed
either.
To make the link across H3-M inaccessible, the controller can be sealed to prevent its
removal.
Refer to section "28 Handling".
Basic Documentation RVL471
26 Function block "Locking functions"
together until
,
and
, one after the other.
Unit
Factory
setting
0
appears in the display.
Range
0...2
95/118