Be sure to include the total current drawn on the polling loop when figuring the total auxiliary load on the panel's
power supply.
CONTROL PANEL
INPUT LOOP LIMITS:
• 128 mA MAX. LIMIT CURRENT TO 64mA ON ANY
INDIVIDUAL WIRE RUN.
• NO MORE THAN 64 DEVICES MAY BE USED.
NO INDIVIDUAL WIRE RUN CAN EXCEED:

Figure 3-16: Polling Loop Connections Using One 4297 Extender Module

Figure 3-17: Polling Loop Connections Using Multiple Extender Modules

NOTE: The input loop limits stated in Figure 3-16 apply to Figure 3-17 as well.
Wirel
ess
The 5881ENHC RF Receiver, 5869 Holdup Switch Transmitter and 5817CB Wireless Commercial Household
Zone
Transmitter are listed for UL Commercial Burglary applications. All other RF receivers and transmitters are not listed for
Expa
UL Commercial Burglary applications.
nsion
UL
The following table lists the receivers that may be used and the number of zones they support.
5800 Series Receivers
Receiver
5881ENHC
RF System Operation and Supervision
The 5800 RF system operation has the following characteristics:
The receiver responds to a frequency of 345MHz.
The receiver has a nominal range of 200 feet.
Supervised transmitters send a supervisory signal every 70-90 minutes.
Zones 988 and 990 are used to supervise the RF reception of receivers 2 and 1, respectively. The reception is
supervised for two conditions:
1.
The receiver goes "deaf" (doesn't hear from any transmitter) within a programmed interval of time (defined by
program field 1*30).
2.
Proper RF reception is impeded (i.e., jamming or other RF interference). The control checks for this condition
every 45 seconds.
INPUT POLLING LOOP
RPM
RPM
GAUGE
LENGTH
#22
650 FT
#20
950 FT
#18
1500 FT
#16
2400 FT
• DO NOT CONNECT 4297 MODULES IN
SERIES (i.e., DO NOT CONNECT ONE
MODULE'S EXTENSION LOOP TO
ANOTHER MODULE'S INPUT LOOP.)
CONTROL PANEL
COMBINED INPUT AND EXTENSION LOOP LIMITS:
• NO MORE THAN 119 DEVICES COMBINED ON THE INPUT LOOP AND EXTENSION
LOOP #1. NO MORE THAN 119 DEVICES COMBINED ON THE INPUT LOOP AND
EXTENSION LOOP #2.
Zones
up to 128 zones for commercial
Burglary applications
4297
EXTENSION POLLING LOOP LIMITS = SAME AS INPUT LOOP
COMBINED INPUT AND EXTENSION LOOP LIMITS:
• NO MORE THAN 119 DEVICES COMBINED.
4297
INPUT POLLING LOOP
4297
Installing the Control
EXTENSION POLLING LOOP
RPM
RPM
polling_loop_003-V2_BP
EXTENSION POLLING LOOP #1
RPM
EXTENSION POLLING LOOP #2
RPM
polling_loop-004-V1_BP
TO
OTHER
RPMS
3-13