BACview Menu
HOME>CONFIG>
SERVICE
Unit Type
Compressor Stages
Face Split Coil
Economizer Exists
Fan Control
VFD Input
Max VFD Output
Min VFD Output
Dehum Min VFD Output
Reversing Valve Type
Heat Type
Number of Heat Stages
Continuous Occupied Exhaust
RH Control
DCV Control
Indoor CO2 Sensor Value @ Min mA
Indoor CO2 Sensor Value @ Max mA
Outdoor CO2 Sensor Value @ Min mA
Outdoor CO2 Sensor Value @ Max mA
(Field Assistant Only)
System Space Temperature
System Space RH
System Space AQ
System Outdoor AQ
System Cool Demand Level
System Heat Demand Level
System Outdoor Air Temperature
HOME>CONFIG>
SERVICE>TEST
Service Test
Fan Test
High Speed Fan Test
Compressor 1 Test
Compressor 2 Test
Heat 1 Test
Heat 2 Test
Reversing Valve Test
Dehumidification Test
Power Exhaust Test
Economizer Test
VFD Speed Test
2012Bryant Heating & Cooling Systems. D 7310 W. Morris St. D Indianapolis, IN 46231
Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations.
CONFIGURATION POINTS (CON'T)
POINT NAME
BACnet Object
unit_type
comp_stages
face_split
econ_exist
fan_type
vfd_in_type
max_vfd_spd
min_vfd_spd
dehum_min_vfd
rev_vlv_type
heat_type
heat_stages
occ_exh
rh_enable
dcv_enable
iaq_ref_lo_ppm
iaq_ref_hi_ppm
oaq_ref_lo_ppm
oaq_ref_hi_ppm
system_spt
system_rh
system_iaq
system_oaq
cool_demand_level
heat_demand_level
system_oat
test_enable
fan_test
hi_spd_test
comp1_test
comp2_test
heat1_test
heat2_test
rev_vlv_test
dehum_test
pexh_test
econ_test
vfd_spd_test
RANGE
SERVICE
SERVICE CONFIGURATION
1=Heat/Cool
Heat/Cool (580/558J and 581/55J models)
2=HP O/B Ctrl
HP Y1/W1 Ctrl (548J and 549J models)
3=HP Y1/W1 Ctrl
One stage/ Two Stage
One Stage (sizes 04- 07, and A08- A12)
Two Stages (sizes 08- 30)
Yes/No
Yes
No/Yes
No (No FIOP)
Yes (FIOP)
1=Single Speed
Single Speed (04- 07. and A08- 12)
2=Two Speed
Two Speed (units with VFD option)
3=Variable Speed
0- 10Vdc/2- 10Vdc
2- 10Vdc
33- 100%
1
33- 100%
0.4
50- 100%
0.6
O output type/B output type
O output type
Electric/Gas
Gas (580J/581J Series Units)
Electric (558J/551J/548J/549J Series
Units)
1 / 2 / 0 (no heat)
0 (558J/551J series cooling only units)
1 (All 548J and 549J, Low Nox units,
2 (580/558J04 and 08- 09 med,
No/Yes
No
Disable/Enable
Disable
Enable (units with Perfect Humidity option)
Disable/Enable
Disable
0- 9999ppm
0
0- 9999ppm
2000
0- 9999ppm
0
0- 9999ppm
2000
0- 3
0
0- 3
0
SERVICE TEST
Disable/Enable
Disable
Disable/Enable
Disable
Disable/Enable
Disable
Disable/Enable
Disable
Disable/Enable
Disable
Disable/Enable
Disable
Disable/Enable
Disable
Disable/Enable
Disable
Disable/Enable
Disable
Disable/Enable
Disable
0- 100 %Open
0
0- 100%
0
Edition Date: 11/12
44
DEFAULT
single phase gas units, 580/558J04- 09
low and 580/558J05- 07 med heat 3
phase gas units)
580/558J05- 09 high heat 3 phase gas
units, 581/551J04- 09 3 phase gas units
and All 12- 30 gas units)
Catalog No: TS- 5580J- 01
Replaces: New