Bryant 580J 04-30 Controls, Start-Up, Operation And Troubleshooting page 42

Table of Contents

Advertisement

BACview Menu
POINT NAME
HOME>CONFIG>
UNIT
Fan Mode
Power Fail Restart Delay
Fan Off Delay
Minimum Cooling SAT
Maximum Heating SAT
Vent Dmpr Pos / DCV Min Pos
Economizer Purge Min Pos
Low Fan Econ Min Pos
DCV Max Vent Damper Pos
Supply Fan Service Alarm Timer
Comp 1 Service Alarm Timer
Comp 2 Service Alarm Timer
Filter Service Alarm Timer
Pushbutton Override
Setpoint Adjustment
Setpoint Adjustment Range
Cooling Lockout Temperature
Economizer High OAT Lockout Temp
HP Rev Cycle Lockout Temp
Heating Lockout Temperature
Pre Occupancy Purge
Purge Time
Unocc Free Cool
Min Setpoint Separation
Occupancy Source
CONFIGURATION POINTS (CON'T)
BACnet Object
UNIT CONFIGURATION
UNIT CONFIGURATION
fan_mode
start_delay
fan_delay_off
sat_cl_min
sat_ht_max
econ_min
econ_purge_min
econ_min_2
iaq_dpr_max
sfan_service_hrs
comp1_service_hrs
comp2_service_hrs
filter_service_hrs
pb_enable
stpt_adj_enable
stpt_adj_range
oat_cl_lockout
oat_ec_lockout
hp_rev_cycle_lockout
oat_ht_lockout
preocc_purge
purge_time
ntfc_ena
min_stpt_sep
occ_source
RANGE
1=Auto
Continuous
2=Continuous
3=Always On
0- 30 sec
5
0- 180 sec
90
45- 75 ° F
50
85- 150° F
120
0- 100 %Open
20
0- 100 %Open
40
0- 100 %Open
33
0- 75 %Open
50
0- 9999 hr
600
0- 9999 hr
0
0- 9999 hr
0
0- 9999 hr
600
Disable/Enable
Enable
Disable/Enable
Enable
+/- 0- 5 ° F
5
0- 80° F
45
55- 80° F
75
- 20- 30° F
- 3
35- 150° F
65
Disable/Enable
Disable
60 min
0- 240 min
Disable/Enable
Disable
2- 10 ° F
5
1=Always occupied
Always Occupied
2=BACnet Schedule
3=BAS On/Off
4=Remote Occ Input
42