APPENDIX B - THIRD PARTY POINTS LIST (CON'T)
Read/
Point Name
Write
High Space Temperature
R
High Speed Fan Test
R/W
HP Rev Cycle Lockout Temp
R/W
Humidistat Input Status
R
Indoor Air Quality
R
Indoor Air Quality CO2 (ppm)
R
Indoor Air Quality Sensor
R
Input 1 Function
R/W
Input 2 Function
R/W
Input 3 Function
R/W
Input 3 Switch Configuration
R/W
Input 5 Function
R/W
Input 5 Switch Configuration
R/W
Input 8 Function
R/W
Input 8 Switch Configuration
R/W
Input 9 Function
R/W
Input 9 Switch Configuration
R/W
input_1
R
input_10
R
input_11
R
input_2
R
input_3
R
input_4
R
input_5
R
input_6
R
input_7
R
input_8
R
input_9
R
Low Fan Econ Min Pos
R/W
Low Space Temperature
R
Maximum Heating SAT
R/W
Minimum Cooling SAT
R/W
Number Of Heat Stages
R/W
Occ Relative Humidity Setpoint
R/W
Occupancy Contact
R
Occupancy Source
R/W
Occupancy Status
R
Optimal Start
R/W
Optimal Start Type
R/W
Outdoor Air Quality CO2 (ppm)
R
Outdoor Air Quality Sensor
R
Outdoor Air Temp Sensor
R
Outdoor Air Temperature
R
Override Time Remaining
R
Password Protected Output
R/W
Variable
Power Exhaust Relay State
R
Power Exhaust Setpoint
R/W
Power Exhaust Test
R/W
Power Fail Restart Delay
R/W
Reset Comp 1 Runtime Alarm
R/W
Reset Comp 2 Runtime Alarm
R/W
Reset Filter Alarm
R/W
Reset Supply Fan Runtime
R/W
Alarm
Safety Chain
R
Safety Chain Feedback
R
Schedule
R/W
Service Test
R/W
(in alphabetical order)
BACnet
BACnet Point Name
Object ID
spt_hi_alarm
BV:7011
discrete in
hi_spd_test
BV:81010
hp_rev_cycle_lockout
AV:9004
float value
humstat_status
BV:1006
iaq_alarm
BV:7005
discrete in
iaq
AV:1009
float value
iaq_sensor_fail
BV:7039
discrete in
ai1_function
MSV:81001
ai2_function
MSV:81002
di3_function
MSV:81003
di3_type
MSV:81013
di5_function
MSV:81005
di5_type
MSV:81015
di8_function
MSV:81008
di8_type
MSV:81018
di9_function
MSV:81009
di9_type
MSV:81019
ai_1
AI:1001
ai_10
AI:1010
ai_11
AI:1011
ai_2
AI:1002
di_3
BI:1003
di_4
BI:1004
di_5
BI:1005
ai_6
AI:1006
ai_7
AI:1007
di_8
BI:1008
di_9
BI:1009
econ_min_2
AV:9030
float value
spt_lo_alarm
BV:7012
discrete in
sat_ht_max
AV:83004
sat_cl_min
AV:83003
heat_stages
MSV:91004
occ_dehum_stpt
AV:3011
float value
occ_contact_status
BV:1007
occ_source
MSV:1002
occ_status
BV:2008
discrete in
optm_start
AV:9026
float value
start_type
MSV:2009
unsigned int
oaq
AV:1012
float value
oaq_fail
BV:7006
discrete in
oat_fail
BV:7029
discrete in
oa_temp
AV:1003
float value
ovrde_time
AV:2016
float value
ppo
AV:90000
pexh
BV:2010
pexh_stpt
AV:3010
float value
pexh_test
BV:81008
start_delay
AV:9007
float value
comp1_rntm_clr
BV:7514
comp2_rntm_clr
BV:7515
filter_rntm_clr
BV:7517
discrete out
sfan_rntm_clr
BV:7510
safety_alarm
BV:7024
discrete in
safety_status
BV:1009
schedule
BV:8000
test_enable
BV:81000
Modbus
N2
Network
Network
Register
Register
Point
Point
Type
#
Type
Address
10035
BI
40071
ADF
10033
BI
40073
ADF
10037
BI
40089
ADF
10039
BI
40083
ADF
10018
BI
40147
ADF
40154
ADI
40085
ADF
10041
BI
10027
BI
27
40087
ADF
40093
ADF
40097
ADF
40127
ADF
22
BO
10043
BI
38
Lonworks
SNVT Type
SNVT Name
35
SNVT_switch (95)
nvoHiSpaceTemp
30
SNVT_temp_p (105)
nviHPRevCLckTemp
33
SNVT_switch (95)
nvoIAQAlm
31
SNVT_ppm (29)
nvoIAQ
37
SNVT_switch (95)
nvoIAQSensor
32
SNVT_lev_percent (81)
nviLowFanEconMin
39
SNVT_switch (95)
nvoLoSpaceTemp
36
SNVT_lev_percent (81)
nviOccRHSP
18
SNVT_switch (95)
nvoOccStatus
61
SNVT_time_hour (124)
nviOptimalStart
20
SNVT_count_inc (9)
nviOptimalStType
37
SNVT_ppm (29)
nvoOAQ
41
SNVT_switch (95)
nvoOAQSensor
38
SNVT_temp_p (105)
nvoOAT
41
SNVT_time_min (123)
nvoOvrTimeRemain
43
SNVT_lev_percent (81)
nviPwrExhSP
58
SNVT_time_sec (107)
nviUnitStartDly
22
SNVT_switch (95)
nviResetFiltAlm
43
SNVT_switch (95)
nvoSafetyChain

Advertisement