APPENDIX A - USER INTERFACE MENUS (CON'T)
BACview Menu
POINT NAME
HOME>MAINT
Occupancy Status
Temp Compensated Start
Learning Adaptive Start
Pre Occupancy Purge
Space Temp Sensor
Setpoint Adjustment
Relative Humidity Source
IAQ Source
OAQ Source
Outdoor Air Temperature Source
Safety Chain Feedback
Fire Shutdown Status
Compressor Safety Status
Calculated Min Econ Pos
Calculated Min PE Pos
Active Compressor Stages
Active Heat Stages
Enthalpy Status
Humidistat Input Status
Filter Status
Door Contact Status
Reset Supply Fan Runtime Alarm
Reset Comp 1 Runtime Alarm
Reset Comp 2 Runtime Alarm
Reset Filter Runtime Alarm
BAS On / Off
Schedules
Pushbutton Override
Occupancy Contact
Override Time Remaining
Supply Fan Runtime
Compressor 1 Runtime
Compressor 2 Runtime
Filter Runtime
Maintenance Menu
BACnet Object
UNIT MAINTENANCE
occ_status
tcs_status
- Or-
- Or-
aos_status
purge
spt_status
stpt_adj
rh_source
iaq_source
oaq_source
oat_status
safety_status
firedown_status
comp_status
cal_min_econ_pos
cal_pe_stpt
comp_run
heat_run
enthalpy_status
humstat_status
filter_status
door_contact_status
sfan_rntm_clr
comp1_rntm_clr
comp2_rntm_clr
filter_rntm_clr
OCCUPANCY MAINTENANCE
keypad_ovrde
schedule
pb_status
occ_contact_status
ovrde_time
RUNTIME MAINTENANCE
sfan_rntm
comp1_rntm
comp2_rntm
filter_rntm
RANGE
MAINTENANCE
Occupied/Unoccupied
Inactive/Active
Inactive/Active
1=Sensor Failure
2=SPT Sensor
3=T55/T56
4=Network
6=Locked Value
x ° F
1=N/A
2=Local
3=Network
5=Locked Value
1=N/A
2=Local
3=Network
5=Locked Value
1=N/A
2=Local
3=Network
5=Locked Value
1=N/A
2=Local
3=Network
5=Locked Value
Off/Run Enabled
Run Enabled/Shutdown
Normal/Trouble
0- 100%
0- 100%
0- 2
0- 2
High/Low
High/Low
Clean/Dirty
Off/On
Run/Clear
Run/Clear
Run/Clear
Off/On
1=Inactive
2=Occupied
3=Unoccupied
Unoccupied/Occupied
Off/Active
Off/On
0- 240 min
xxxxx hr
xxxxx hr
xxxxx hr
xxxxx hr
36
DEFAULT
Field Assistant Menu
Properties>Equipment>
Maintenance
Run
Run
Run
Off
Inactive