APPENDIX A - USER INTERFACE MENUS (CON'T)
BACview Menu
POINT NAME
HOME>CONFIG>
UNIT
Fan Mode
Power Fail Restart Delay
Fan Off Delay
Minimum Cooling SAT
Maximum Heating SAT
Vent Dmpr Pos / DCV Min Pos
Economizer Purge Min Pos
Low Fan Econ Min Pos
DCV Max Vent Damper Pos
Supply Fan Service Alarm Timer
Comp 1 Service Alarm Timer
Comp 2 Service Alarm Timer
Filter Service Alarm Timer
Pushbutton Override
Setpoint Adjustment
Setpoint Adjustment Range
Cooling Lockout Temperature
Economizer High OAT Lockout Temp
HP Rev Cycle Lockout Temp
Heating Lockout Temperature
Pre Occupancy Purge
Purge Time
Unocc Free Cool
Min Setpoint Separation
Occupancy Source
Configuration Menus
BACnet Object
RANGE
UNIT CONFIGURATION
UNIT CONFIGURATION
fan_mode
1=Auto
2=Continuous
3=Always On
start_delay
0- 30 sec
fan_delay_off
0- 180 sec
sat_cl_min
45- 75 ° F
sat_ht_max
85- 150° F
econ_min
0- 100 %Open
econ_purge_min
0- 100 %Open
econ_min_2
0- 100 %Open
iaq_dpr_max
0- 75 %Open
sfan_service_hrs
0- 9999 hr
comp1_service_hrs
0- 9999 hr
comp2_service_hrs
0- 9999 hr
filter_service_hrs
0- 9999 hr
pb_enable
Disable/Enable
stpt_adj_enable
Disable/Enable
stpt_adj_range
+/- 0- 5 ° F
oat_cl_lockout
0- 80° F
oat_ec_lockout
55- 80° F
hp_rev_cycle_lockout
- 20- 30° F
oat_ht_lockout
35- 150° F
preocc_purge
Disable/Enable
purge_time
60 min
ntfc_ena
Disable/Enable
min_stpt_sep
2- 10 ° F
occ_source
1=Always occupied
2=BACnet Schedule
3=BAS On/Off
4=Remote Occ Input
31
DEFAULT
Field Assistant Menu
Properties>Equipment>
Configuration>
Unit Configuration
Continuous
5
90
50
120
20
40
33
50
600
0
0
600
Enable
Enable
5
45
75
- 3
65
Disable
0- 240 min
Disable
5
Always Occupied