APPENDIX A - USER INTERFACE MENUS (CON'T)
BACview Menu
POINT NAME
STANDBY
System Mode
Space Temperature
LOGIN/LOGOUT
Admin or User Password
HOME
HOME>
SYSTEM SETTINGS>
BACnet
BACnet Device Instance:
Base BACnet Device ID:
Autogenerate Device ID?
Keypad
Inactivity Timeout:
BACnet Write Priority:
UserPw
Password:
NETWORK
Max Masters
Max Info Frames
APDU Timeout (ms)
APDU Retries
MS/TP Baud Rate
ClockSet
Time (hh:mm:ss):
Date (dd- mmm- yy):
DST
Start Time:
Amount:
Entry #
Beg (mm- dd- yy)
End (mm- dd- yy)
TimeMstr
Time Sync Mode
Time Sync Interval
System Settings Menu
BACnet Object
RANGE
RTU Open
run_status
1=Off
2=Fan Only
3=Economizer
4=Cooling
5=Heating
6=Dehumidification
7=Test
8=Shutdown
9=Unocc Free Cooling (NT-
FC)
10=Fire Shutdown
11=IAQ Override
12=Pre- OCC Purge
space_temp
xxx ° F
Press any key to activate
****
Select function below
SYSTEM SETTINGS
xxxxxxx
xxxxxxx
Y/N
Keypad Configuration
1- 255 minutes
0- 16
View/Set User
****
NETWORK
this_device/64
1- 127
this_device/63
1- 999
this_device/11
1- 10000
this_device/73
1- 10
this_device/4161(1)
9600- 76800
Set Current Time/Date (24 hr clock)
DST
BACnet Time Master
No Broadcast
Local Broadcast
Global Broadcast
1- 9999 minutes
29
DEFAULT
Field Assistant Menu
User: 0000 Admin: 1111
1610100
1610100
Y
10
0
BACview Only
0000
127
10
3000
3
76800
No Broadcast
5